Omron 3G3MX2-V2 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Omron 3G3MX2-V2 multi-function compact inverter series. Search or filter through the complete fault code directory below.
Power Range
0.1 – 15 kW (0.12 – 20 HP)
Supply Voltage
200V / 400V (1-Ph & 3-Ph)
Control Modes
V/f & Sensorless Vector (SLV)
Operator Interface
Digital Keypad / CX-Drive PC Tool
Complete Omron 3G3MX2-V2 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E01, E07, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E01 Overcurrent protection (Constant speed) | Cause: Rapid load fluctuation, output short-circuit, or ground fault during constant speed. Remedy:
|
| E02 Overcurrent protection (Deceleration) | Cause: Rapid deceleration causing large current. Remedy:
|
| E03 Overcurrent protection (Acceleration) | Cause: Rapid acceleration, motor locked, torque boost too high, or PM motor adjustment issue. Remedy:
|
| E04 Overcurrent protection (Others) | Cause: DC injection braking power too high. Remedy:
|
| E05 Overload protection | Cause: The inverter output current exceeded limits (motor overload). Remedy:
|
| E06 Braking resistor overload protection | Cause: Usage rate of regenerative braking circuit exceeds value set in b090. Remedy:
|
| E07 Overvoltage protection | Cause: High DC voltage due to regenerative energy or high incoming voltage (>400VDC for 200V class / >800VDC for 400V class). Remedy:
|
| E08 EEPROM error | Cause: Error in built-in EEPROM due to external noise or abnormal temperature. Remedy:
|
| E09 Undervoltage | Cause: Incoming voltage drops below specified level; Control circuit failure. Remedy:
|
| E10 Current detector error | Cause: Error in the current detector. Remedy:
|
| E11 CPU error | Cause: Malfunction or error in built-in CPU. Remedy:
|
| E12 External trip | Cause: Multi-function input allocated to External Trip (12: EXT) turned ON. Remedy:
|
| E13 USP error | Cause: Power supply turned on while RUN signal was ON (when USP function selected). Remedy:
|
| E14 Grounding protection | Cause: Ground fault detected between inverter output and motor upon power on. Remedy:
|
| E15 Incoming overvoltage protection | Cause: Incoming voltage in overload state for 100s (DC voltage >390VDC for 200V / >780VDC for 400V). Remedy:
|
| E19 Temperature detection error | Cause: Cooling fin temperature detection system error (e.g., disconnection). Remedy:
|
| E21 Abnormal temperature | Cause: Main circuit temperature exceeds limit (high ambient temp, fan issue). Remedy:
|
| E22 CPU communication error | Cause: Malfunction in CPU during communications. Remedy:
|
| E25 Main circuit error | Cause: Error occurred in the main circuit board. Remedy:
|
| E26 Analog current input error | Cause: Excessive current flows through analog current input terminal FI. Remedy:
|
| E30 Driver error | Cause: Momentary overcurrent (350%+), abnormal temp, or drive power drop detected by driver IC. Remedy:
|
| E35 Thermistor error | Cause: External thermistor detected abnormal temp or wiring issue. Remedy:
|
| E36 Brake error | Cause: Inverter cannot recognize ON/OFF status of brake within detection time (b124). Remedy:
|
| E37 Emergency shutoff | Cause: Safety input terminal GS1/GS2 active. Remedy:
|
| E38 Low speed overload protection | Cause: Overload detected in extremely low speed range (0.2 Hz or lower). Remedy:
|
| E40 Digital Operator connection failure | Cause: Disconnection communicating with remote Digital Operator. Remedy:
|
| E41 Modbus communication error | Cause: Timeout occurred (Communication Error C076 is set to Trip). Remedy:
|
| E43 to E45 DriveProgramming error | Cause: Program error. Remedy:
|
| E50 to E59 User trip | Cause: User trip executed via DriveProgramming. Remedy:
|
| E60 to E68 Option error | Cause: Error received from the option unit (e.g., EtherCAT). Remedy:
|
| E69 Option timeout | Cause: Timeout in communications between inverter and option unit. Remedy:
|
| E80 Encoder disconnection | Cause: Encoder wiring disconnected or improperly connected. Remedy:
|
| E81 Overspeed | Cause: Motor rotation speed exceeds Maximum Frequency x Overspeed Error Level. Remedy:
|
| E83 Position control range trip | Cause: Current position out of range set in Position Limit Setting (P072, P073). Remedy:
|
| E99 STO internal fault error | Cause: Fault detected in STO input terminal or internal safety circuit. Remedy:
|
How to Clear & Reset Omron 3G3MX2-V2 Drive Faults
- Keypad Reset: Press the red STOP/RESET key on the integrated front digital operator. Note that if parameter b102 (Reset selection) is set to restrictive modes, the trip can only be cleared when the run command is cancelled.
- Multi-Function Input Reset (RS): Pulse the digital input terminal assigned to function 18 [RS: Reset] (configured in parameters C001 to C007). Ensure the input is held closed for at least 12 ms and then opened.
- CX-Drive / Sysmac Studio PC Tool: Connect your PC to the drive via the integrated mini-USB port, go to the Trip Monitor / Status screen in Omron CX-Drive, and click “Fault Reset”.
- Fieldbus / Modbus RTU Command: Write a logic high (`1`) to the Reset bit in the inverter command coil/register via embedded Modbus RTU (terminals SP/SN) or optional fieldbus interfaces (EtherCAT, DeviceNet, CompoNet, PROFIBUS-DP).
- Power Cycle: Disconnect main AC power supply, wait until the front display and internal CHARGE LED turn off completely (approx. 5 to 10 minutes for DC bus capacitor discharge), then re-apply input power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous voltage remains stored in the internal DC bus capacitors after powering off. Always verify with a calibrated digital multimeter that the voltage across intermediate DC bus terminals [+1 / +] and [-] measures strictly below 50 VDC, and ensure the red CHARGE indicator lamp is completely off before servicing wiring or touching terminals U/T1, V/T2, and W/T3.