Omron 3G3MX2-V2 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Omron 3G3MX2-V2 multi-function compact inverter series. Search or filter through the complete fault code directory below.

Multi-Function Compact Inverter Power: 0.1 to 15 kW (0.12 to 20 HP) Integrated Safety STO (ISO 13849-1 PLd)
Power Range 0.1 – 15 kW (0.12 – 20 HP)
Supply Voltage 200V / 400V (1-Ph & 3-Ph)
Control Modes V/f & Sensorless Vector (SLV)
Operator Interface Digital Keypad / CX-Drive PC Tool

Complete Omron 3G3MX2-V2 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E01, E07, or Overcurrent).

Fault Code and MeaningCause and Remedy
E01
Overcurrent protection (Constant speed)

Cause: Rapid load fluctuation, output short-circuit, or ground fault during constant speed.



Remedy:

  • Eliminate load fluctuation.

  • Check the output wiring.

  • Check the output wiring and the motor for ground faults.


E02
Overcurrent protection (Deceleration)

Cause: Rapid deceleration causing large current.



Remedy:

  • Increase the deceleration time.


E03
Overcurrent protection (Acceleration)

Cause: Rapid acceleration, motor locked, torque boost too high, or PM motor adjustment issue.



Remedy:

  • Increase the acceleration time.

  • Check the motor and wiring (is motor locked?).

  • Decrease the torque boost setting.

  • If a PM motor is in use, ensure motor is set and adjusted properly.


E04
Overcurrent protection (Others)

Cause: DC injection braking power too high.



Remedy:

  • Decrease the braking power.


E05
Overload protection

Cause: The inverter output current exceeded limits (motor overload).



Remedy:

  • Reduce the load rate (Is the load too heavy?).

  • Adjust the thermal level (b012/b212) to an appropriate level.

  • Increase the acceleration time (ensure torque is sufficient).


E06
Braking resistor overload protection

Cause: Usage rate of regenerative braking circuit exceeds value set in b090.



Remedy:

  • Increase the deceleration time (reduce rapid deceleration).

  • Increase the operation cycle time.


E07
Overvoltage protection

Cause: High DC voltage due to regenerative energy or high incoming voltage (>400VDC for 200V class / >800VDC for 400V class).



Remedy:

  • Increase the deceleration time.

  • Check the output wiring and motor for ground faults.

  • Decrease the amount of regeneration (is motor rotated from load side?).

  • Lower the incoming voltage or install AC reactor.


E08
EEPROM error

Cause: Error in built-in EEPROM due to external noise or abnormal temperature.



Remedy:

  • Take measures against noise source.

  • Check the cooling fin for clogging and clean it.

  • Perform parameter initialization if error persists after power cycle.


E09
Undervoltage

Cause: Incoming voltage drops below specified level; Control circuit failure.



Remedy:

  • Check the power supply voltage.

  • Check the power supply capacity.

  • Check if smoothing capacitor has deteriorated over time.


E10
Current detector error

Cause: Error in the current detector.



Remedy:

  • The inverter has a defect; repair it.


E11
CPU error

Cause: Malfunction or error in built-in CPU.



Remedy:

  • Take measures against large noise sources.

  • The inverter has a defect; repair it.


E12
External trip

Cause: Multi-function input allocated to External Trip (12: EXT) turned ON.



Remedy:

  • Check the external equipment for defects.

  • Take measures against noise sources.


E13
USP error

Cause: Power supply turned on while RUN signal was ON (when USP function selected).



Remedy:

  • Check the RUN command (ensure it is off before power on).


E14
Grounding protection

Cause: Ground fault detected between inverter output and motor upon power on.



Remedy:

  • Check output wiring and motor for ground faults.

  • Disconnect output wiring to check if fault is in inverter itself.

  • Check the main circuit.


E15
Incoming overvoltage protection

Cause: Incoming voltage in overload state for 100s (DC voltage >390VDC for 200V / >780VDC for 400V).



Remedy:

  • Lower the incoming voltage.

  • Suppress power supply fluctuation.

  • Install AC reactor in input power circuit.


E19
Temperature detection error

Cause: Cooling fin temperature detection system error (e.g., disconnection).



Remedy:

  • The Inverter is faulty; repair it.


E21
Abnormal temperature

Cause: Main circuit temperature exceeds limit (high ambient temp, fan issue).



Remedy:

  • Check installation (is it vertical?).

  • Decrease ambient temperature.

  • Check cooling fan (Set b092 to Always enabled; check fan power).

  • Clean cooling fins if clogged.


E22
CPU communication error

Cause: Malfunction in CPU during communications.



Remedy:

  • Take measures against noise.

  • The inverter is faulty; repair it.


E25
Main circuit error

Cause: Error occurred in the main circuit board.



Remedy:

  • Take measures against noise.

  • The inverter is faulty; repair it.


E26
Analog current input error

Cause: Excessive current flows through analog current input terminal FI.



Remedy:

  • Check for short-circuit or incorrect wiring in FI wiring.

  • If wiring is fine, control circuit board is faulty (Repair).


E30
Driver error

Cause: Momentary overcurrent (350%+), abnormal temp, or drive power drop detected by driver IC.



Remedy:

  • Check output wiring for short-circuit.

  • Check output wiring and motor for ground fault.

  • Check IGBT (Main element damaged?).

  • Clean cooling fin if clogged.


E35
Thermistor error

Cause: External thermistor detected abnormal temp or wiring issue.



Remedy:

  • Check motor temperature.

  • Check if thermistor is damaged.

  • Separate wiring to prevent noise in thermistor signal.


E36
Brake error

Cause: Inverter cannot recognize ON/OFF status of brake within detection time (b124).



Remedy:

  • Check if brake ON/OFF function is working.

  • Increase the b124 value (Time set too short?).

  • Check wiring for brake confirmation signal.


E37
Emergency shutoff

Cause: Safety input terminal GS1/GS2 active.



Remedy:

  • Check GS1/GS2 wiring and sequence.

  • Check GS Input Operation Selection (b145) setting.


E38
Low speed overload protection

Cause: Overload detected in extremely low speed range (0.2 Hz or lower).



Remedy:

  • Reduce the load rate.


E40
Digital Operator connection failure

Cause: Disconnection communicating with remote Digital Operator.



Remedy:

  • Check/replace the cable.

  • Note: Detection disabled when b165 is set to 02.


E41
Modbus communication error

Cause: Timeout occurred (Communication Error C076 is set to Trip).



Remedy:

  • Check communication speed setting.

  • Check if wiring distance is appropriate.

  • Check for disconnected wires.

  • Check terminating resistor setting.


E43 to E45
DriveProgramming error

Cause: Program error.



Remedy:

  • For details, refer to the DriveProgramming User's Manual.


E50 to E59
User trip

Cause: User trip executed via DriveProgramming.



Remedy:

  • Refer to the DriveProgramming User's Manual.


E60 to E68
Option error

Cause: Error received from the option unit (e.g., EtherCAT).



Remedy:

  • For details, refer to the manual for the specific option unit.


E69
Option timeout

Cause: Timeout in communications between inverter and option unit.



Remedy:

  • Check that option unit housing is mounted properly.

  • Check fixation screws are not loose.

  • Option unit may be faulty.


E80
Encoder disconnection

Cause: Encoder wiring disconnected or improperly connected.



Remedy:

  • Check encoder wiring.

  • Adjust P077 (Detection Time) and P015 (Creep Speed).


E81
Overspeed

Cause: Motor rotation speed exceeds Maximum Frequency x Overspeed Error Level.



Remedy:

  • Check encoder wiring.

  • Check number of encoder pulses (P011).

  • Check load conditions.

  • Adjust Output Frequency Setting (F001) or Overspeed Detection Level (P026).


E83
Position control range trip

Cause: Current position out of range set in Position Limit Setting (P072, P073).



Remedy:

  • Check the current position.

  • Check parameter settings (P072, P073, P060-P067).

  • Check the origin.


E99
STO internal fault error

Cause: Fault detected in STO input terminal or internal safety circuit.



Remedy:

  • Perform a periodic functional test (Safety function check).

  • The internal safety circuit is faulty; repair it.


How to Clear & Reset Omron 3G3MX2-V2 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET key on the integrated front digital operator. Note that if parameter b102 (Reset selection) is set to restrictive modes, the trip can only be cleared when the run command is cancelled.
  2. Multi-Function Input Reset (RS): Pulse the digital input terminal assigned to function 18 [RS: Reset] (configured in parameters C001 to C007). Ensure the input is held closed for at least 12 ms and then opened.
  3. CX-Drive / Sysmac Studio PC Tool: Connect your PC to the drive via the integrated mini-USB port, go to the Trip Monitor / Status screen in Omron CX-Drive, and click “Fault Reset”.
  4. Fieldbus / Modbus RTU Command: Write a logic high (`1`) to the Reset bit in the inverter command coil/register via embedded Modbus RTU (terminals SP/SN) or optional fieldbus interfaces (EtherCAT, DeviceNet, CompoNet, PROFIBUS-DP).
  5. Power Cycle: Disconnect main AC power supply, wait until the front display and internal CHARGE LED turn off completely (approx. 5 to 10 minutes for DC bus capacitor discharge), then re-apply input power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous voltage remains stored in the internal DC bus capacitors after powering off. Always verify with a calibrated digital multimeter that the voltage across intermediate DC bus terminals [+1 / +] and [-] measures strictly below 50 VDC, and ensure the red CHARGE indicator lamp is completely off before servicing wiring or touching terminals U/T1, V/T2, and W/T3.