Omron 3G3RX2 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Omron 3G3RX2 high-function general-purpose inverter series. Search or filter through the complete fault code directory below.
Power Range
0.4 – 132 kW (0.5 – 175 HP)
Supply Voltage
3-Phase 200V / 400V Class
Control Modes
Sensorless Vector, V/f & PM Motor
Operator Interface
Full-Color LCD Operator / USB
Complete Omron 3G3RX2 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E001, E007, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E001 Overcurrent Error | Cause: A large current flowed in the inverter. 1. Steep load change or motor hunting during operation. 2. Insufficient acceleration/deceleration time or large load inertia. 3. Short circuit or ground fault in output lines. 4. Motor is locked. Remedy:
|
| E005 Motor Overload Error | Cause: Internal electronic thermal function detected motor overload. 1. Heavy load condition continued. 2. Thermal level set too high. 3. Insufficient acceleration/deceleration torque. Remedy:
|
| E006 Braking Resistor Overload Error | Cause: Usage rate of braking resistor (BRD) exceeded the set limit [bA-60]. 1. Insufficient deceleration time. 2. Large load inertia or continuous regenerative operation. Remedy:
|
| E007 Overvoltage Error | Cause: P-N voltage exceeded approx 410 Vdc (200V class) or 820 Vdc (400V class). 1. Insufficient deceleration time. 2. Load inertia is too large causing regeneration. 3. Motor rotated by external force (fan, crane). 4. Power supply voltage abnormality. Remedy:
|
| E008 Memory Error | Cause: Built-in memory problem or CPU error. 1. Noise interference. 2. Power turned off during memory access. Remedy:
|
| E009 Undervoltage Error | Cause: Main power supply voltage decreased (below ~160Vdc for 200V class or ~320Vdc for 400V class). 1. Power failure or unstable power supply. 2. Insufficient power supply capacity. 3. Internal circuit failure or capacitor deterioration. Remedy:
|
| E010 Current Detector Error | Cause: Problem with the built-in current detector. 1. Current detector circuit broken. 2. Noise source nearby. Remedy:
|
| E011 CPU Error | Cause: Malfunction in built-in CPU. 1. CPU broken. 2. Noise interference. 3. Data inconsistency during writing. Remedy:
|
| E012 External Trip Error | Cause: Signal from external device triggered trip. 1. Wiring wrong or terminal logic reversed. 2. External equipment commanded a trip. Remedy:
|
| E013 USP Error | Cause: Operation command entered when power was turned ON (when USP function enabled). Remedy:
|
| E014 Ground Fault Error | Cause: Ground fault detected between inverter output and motor at power-on. 1. Ground fault in wires or motor. 2. Motor insulation deterioration. Remedy:
|
| E015 Incoming Overvoltage Error | Cause: High incoming voltage held for 100 seconds while output stopped. Remedy:
|
| E016 Instantaneous Power Failure Error | Cause: Instantaneous power failure or voltage decrease in R, S, T. 1. Power supply voltage decreased. 2. Contact fault in breaker/contactor. Remedy:
|
| E019 Temperature Detector Error | Cause: Temperature detector circuit disconnection or failure. Remedy:
|
| E020 Cooling Fan Speed Reduction Error | Cause: Fan rotation speed decreased causing high temperature. 1. Foreign object in fan. 2. Fan reached end of life. Remedy:
|
| E021 Temperature Error | Cause: Internal temperature is too high. 1. High carrier frequency. 2. Clogged heatsink fins. 3. High ambient temperature. Remedy:
|
| E024 Input Open-phase Error | Cause: Phase loss detected in input line (when [bb-65]=01). 1. Loose connection or disconnection in input. 2. Single-phase input used erroneously. Remedy:
|
| E030 IGBT Error | Cause: Instantaneous overcurrent or main element failure. 1. Short circuit or ground fault. 2. Output element failure. 3. Motor rotation locked. Remedy:
|
| E034 Output Open-phase Error | Cause: Phase loss detected in output line (when [bb-66]=01). 1. Loose connection or wire break to motor. 2. Internal motor disconnection. Remedy:
|
| E035 Thermistor Error | Cause: Abnormal temperature detected via external thermistor. 1. Motor overheating. 2. Improper thermistor setting or wiring. Remedy:
|
| E036 Brake Error | Cause: Brake check signal problem during brake release waiting time. 1. Signal line disconnected. 2. Brake function setting incorrect. Remedy:
|
| E038 Low-speed Range Overload Error | Cause: Output at low frequency (0.2 Hz or below) overload. Remedy:
|
| E039 Controller (Inverter) Overload Error | Cause: Electronic thermal function detected inverter controller overload. 1. Heavy load. 2. High load inertia. Remedy:
|
| E040 Keypad Communication Error | Cause: Timeout in communication with LCD Operator. 1. Loose connection. 2. Noise interference. Remedy:
|
| E041 RS485 Communication Error | Cause: Timeout in RS485 (Modbus-RTU) communication. Remedy:
|
| E042 RTC Error | Cause: Real Time Clock battery low or data reset. Remedy:
|
| E043 EzSQ Illegal Instruction Error | Cause: Invalid instruction in EzSQ program or noise corruption. Remedy:
|
| E044 EzSQ Nest Count Error | Cause: Subroutine nesting exceeds 8 times. Remedy:
|
| E045 EzSQ Executive Instruction Error | Cause: Program flow error (e.g., missing "next" for "for", division by zero, invalid parameter access). Remedy:
|
| E050 to E059 EzSQ User-assigned Errors | Cause: User-defined error triggered by EzSQ program instructions. Remedy:
|
| E060 to E069 Option 1 Errors | Cause: Error in option mounted in Slot 1. 1. Option not securely mounted. Remedy:
|
| E070 to E079 Option 2 Errors | Cause: Error in option mounted in Slot 2. Remedy:
|
| E080 to E089 Option 3 Errors | Cause: Error in option mounted in Slot 3. Remedy:
|
| E090 to E093 STO Error / FS Option Error | Cause: Path error in functional safety circuit. Remedy:
|
| E100 Encoder Disconnection Error | Cause: PG option feedback lost. 1. Wiring disconnected. 2. Power loss to encoder. Remedy:
|
| E104 Position Control Range Error | Cause: Position counter exceeded range limits. Remedy:
|
| E105 Speed Deviation Error | Cause: Deviation between command and feedback exceeded limit [bb-83]. Remedy:
|
| E106 Position Deviation Error | Cause: Position deviation exceeded limit [bb-86]. Remedy:
|
| E107 Over-speed Error | Cause: Speed exceeded limit [bb-80]. Remedy:
|
| E110 Contactor Error | Cause: Error in contactor sequence (COK signal missing). Remedy:
|
| E112 PG Option Unit Connection Error | Cause: PG option unit removed or connection lost. Remedy:
|
| E120 PID Abnormal Start Error | Cause: PID feedback did not reach target level during soft-start. 1. Target value too low. 2. Wires disconnected. Remedy:
|
| Alarm: LIM Limiting Operation | Cause: Output is being limited by Overload, Torque, Overcurrent, or Overvoltage suppression. LIM Code 01: Overcurrent suppression / DC braking. LIM Code 02: Overload limit / Acceleration time too short. LIM Code 03: Overvoltage suppression / Deceleration time too short. Remedy:
|
| Alarm: ALT Advance Notice | Cause: Pre-warning level reached. ALT Code 01: Overload pre-warning. ALT Code 02: Motor thermal warning. ALT Code 03: Inverter thermal warning. Remedy:
|
| Alarm: RETRY Retry Standby | Cause: Inverter is waiting to retry after a trip or power-off. Remedy:
|
| Alarm: NRDY Not Ready | Cause: Inverter cannot operate. Codes: Trip exists (01), Main power missing (02), Reset active (03), STO active (04), Internal check (05), Setting inconsistency (06). Remedy:
|
How to Clear & Reset Omron 3G3RX2 Drive Faults
- Keypad Reset: Press the red STOP/RESET key on the standard LCD digital operator panel once the trip condition has been cleared.
- Multi-Function Digital Input (RS): Pulse the digital input terminal assigned to function 028 [RS] (Reset) configured via parameters [CA-01] through [CA-11] (turn ON for at least 12 ms, then turn OFF).
- CX-Drive Software: Connect a PC using a standard Micro-USB cable to the port on the LCD operator, open Omron CX-Drive or Sysmac Studio, and click “Fault Reset” in the drive status monitor.
- Fieldbus / Modbus RTU: Send a reset command by writing to the Modbus control register via built-in RS-485 terminals (SP/SN) or through optional fieldbus communication units (EtherCAT 3G3AX-RX2-ECT, PROFINET, or EtherNet/IP).
- Power Cycle: Disconnect AC mains power, wait until the internal CHARGE LED and the LCD screen turn off completely (allow at least 10–15 minutes for bus capacitor discharge), and restore mains input power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [P/+] and [N/-] (and [PD/+1]) before inspecting motor leads, opening terminal covers, or touching output terminals U/T1, V/T2, and W/T3 on the Omron 3G3RX2 inverter.