Parker AC10 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker AC10 compact variable speed drive series. Search or filter through the complete fault code directory below.
Power Range
0.2 – 180 kW (0.25 – 250 HP)
Supply Voltage
230V (1/3-Ph) & 400–480V (3-Ph)
Control Modes
V/Hz & Sensorless Vector (SVC)
Operator Interface
LED Keypad & DSE Lite PC Tool
Complete Parker AC10 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC, OE, or LU).
| Fault Code | Cause & Solution |
|---|---|
| AErr | Line Disconnected - Analog signal line disconnected - Signal source is broken - Change the signal line - Change the signal source |
| CE Communication Timeout | Communication fault - PC/PLC does not send command at fixed time - Check communication line for reliable connected |
| Err1 Password is Wrong | Cause: Password is Wrong. Solution: - When password function is enabled, password is set wrong - Set password correctly |
| Err2 Tuning Parameters Wrong | Cause: Tuning Parameters Wrong Solution: - incorrect motor parameters entered - Connect motor correctly - Enter correct motor data |
| Err3 Current Malfunction Before Running | Cause: Current MalfunctionBefore Running. Solution: - Current alarm signal exists before running - Check if control board is properly connected to power board |
| Err4 Current Zero Excursion Malfunction | Cause: Current Zero Excursion Malfunction. Solution: - Flat cable is loosened - Current detector is broken - Check the flat cable |
| Err5 PID Parameters are set Wrong | Cause: PID Parameters are set Wrong. Solution: - PID parameters are set wrong. - Set the parameters correctly. |
| FL Flycatching Fault | Cause: FL Flycatching Fault. Solution: - Flycatching failure. - Track again. |
| GP Ground fault | Cause: GP Ground fault. Solution: - Motor cable is broken and short- circuit to earth - The insulation of motor is broken and short circuit to earth - Inverter has fault - Change motor cable - Repair or replace motor - SEE ALSO: OC, OC2 and ERR4 |
| L.U. / LU Under-Voltage | Cause: Under-Voltage Protection. Solution: - Low voltage on the input side - Check if supply voltage is normal - Check if parameter setting is correct |
| OC/OC2 Overcurrent | Cause: Overcurrent. - Too short acceleration time - Short circuit at output side - Locked rotor with motor - Parameter tuning is not correct - Prolong acceleration time - Ask if motor is cable broken - Check if motor overloads - Reduce VVVF compensation value - Measure parameter correctly |
| OC1 Overcurrent | Cause: Overcurrent. - Too short acceleration time - Short circuit at output side - Locked rotor with motor - Parameter tuning is not correct - Prolong acceleration time - Ask if motor is cable broken - Check if motor overloads - Reduce VVVF compensation value - Measure parameter correctly |
| O.E. / OE DC Over-Voltage | Cause: DC Over-Voltage. - Supply voltage too high - Load inertia too big - Deceleration time too short - Motor inertia rise again - Parameter of speed loop PID is set abnormally Solution: - Check if rated voltage is input - Add braking resistance(optional) - Increase deceleration time - Set the parameter of rotary speed loop PID correctly |
| O.H. / OH Heatsink Overheat | Cause: - Environment temperature too high - Poor ventilation - Fan damaged - Carrier wave frequency or compensation curve is too high Solution: - Improve ventilation - Clean air inlet and outlet and radiator - Install as required - Change fan - Decrease carrier wave frequency or compensation curve |
| O.L1 / OL1 Inverter Overload | Cause & Solution: 1. Inverter Overload - Load too heavy - Reduce load; check drive ratio - Increase inverter’s capacity |
| O.L2 / OL2 Motor Overload | Cause & Solution: 1. Motor Overload. - Load too heavy - Reduce load: check drive ratio - Increase motor’s capacity |
| PCE PMSM tuning fault | Cause & Solution: PMSM tuning fault - Load is too heavy - Motor parameters measurement is wrong - Decrease the load - Measure motor parameters correctly |
| P.F1. / PF1 Input Phase Loss | Cause & Solution: Input Phase Loss. - Phase loss with input power - Check if power input is normal - Check if parameter setting is correct |
| PF0 Output Phase Loss | Cause & Solution: Output Phase Loss. - Motor is broken - Motor wire is loose - Inverter is broken - Check if wire of motor is loose - Check if motor is broken |
How to Clear & Reset Parker AC10 Drive Faults
- Keypad Reset: Press the red STOP / RESET key (marked O) directly on the integrated front 7-segment LED keypad. If operating under terminal control, remove the Run command prior to clearing the fault.
- Digital Input Reset (Terminal Control): Configure a digital input (parameters F316 to F323) for function 9 (Fault Reset), then apply a momentary 24V DC pulse to the assigned terminal (e.g., DI1–DI8).
- DSE Lite PC Tool: Connect your PC to the drive’s RJ45 communication port via a USB-to-RS485 interface converter, launch Parker DSE (Drive System Explorer) Lite software, and issue a “Trip Reset” command from the diagnostics window.
- Modbus RTU Communication: Write a reset bit command (`0` to `1` transition) to the control register via the integrated RS485 serial communication port.
- Power Cycle: Disconnect main AC incoming power, wait at least 5 minutes until the LED display and charge indicators completely extinguish (confirming intermediate DC bus capacitors have discharged below 50VDC), then reapply mains power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that the intermediate DC bus voltage measures strictly below 50VDC across terminals [+] and [-] (or DC bus test points) before inspecting motor leads, opening terminal covers, or touching terminals U, V, and W on the Parker AC10 drive.