Parker Hannifin Drives Fault Codes & Troubleshooting
Comprehensive technical diagnostic directory for Parker SSD Drives AC variable frequency inverters, DC590+ digital DC converters, and precision motion servo amplifiers. Select your drive model series below to access parameter checks, trip descriptions, and physical inspection workflows.
Parker AC Variable Frequency Drives
13 ModelsModular Industrial System Inverter (Series V & P) with Ethernet IP & Profinet Protocols (0.75 to 250 kW)
High-Performance Multi-Axis Systems Drive (Standalone & Common DC Bus Architecture)
High-Power Modular Plug-in Inverter Cabinet Solution (Up to 400 kW)
Classic High-End Closed-Loop Flux Vector Inverter with 6901 MMI Console (0.75 to 1000 kW)
Industrial System AC Drive Module for Single & Coordinated Multi-Motor Processing
Compact Micro Sensorless Vector Drive for Standard Industrial Automation (0.2 to 180 kW)
Dedicated Inverter Optimized for Fan, Centrifugal Pump, and HVAC Variable Torque Loads
Next-Gen Compact General Purpose Inverter with Built-in STO (Safe Torque Off)
Advanced General Purpose Inverter with Onboard Ethernet, Modbus TCP & Multi-Protocol Options
Dedicated Fan & Pump Industrial Drive with Built-in Energy Saving & Sleep Macros
Classic Simple AC Drive for Basic Speed Control of Three-Phase Induction Motors (0.25 to 7.5 kW)
Sensorless Vector Variant of AC650 with Enhanced Low-Speed Starting Torque (Up to 110 kW)
General Purpose Compact AC Drive with Integrated Dynamic Braking Transistor
Parker Industrial DC Drives
2 ModelsWorld-Standard Digital DC Drive (15 A to 2700 A) for Extruders, Converting, Web Handling & Cranes
Four-Quadrant Fully Regenerative DC Thyristor Drive for Dynamic Reversing & Overhauling Loads
Parker Motion & Servo Systems
5 ModelsHigh-Performance Compact Servo Drive with Real-Time EtherCAT & BiSS-C High-Resolution Feedback
Dedicated Low-Voltage DC & AC Micro Servo System for Packaging, AGVs & Small Automation
Compact Digital Standalone Servo Drive for Brushless Servo Motors with Integrated Positioner
Multi-Axis Modular Servo Drive System Designed for Dynamic Packaging & Multi-Axis Robotic Tooling
Dual-Axis & Single-Axis Digital Brushless Servo Controllers for Coordinated Automation
Most Common Parker SSD Fault Codes
Diagnostic Quick Reference| Trip Message / Code | Legacy Display | Trip Name & Nature | Recommended First Check |
|---|---|---|---|
| OVERVOLTAGE | DCOV / OV | DC Bus Overvoltage | Extend deceleration ramp time; inspect dynamic braking resistor connections across terminals DC+ and DBR. |
| DESAT (OVERCURRENT) | OC | Instantaneous Overcurrent / Desat | Output phase short-circuit or IGBT desaturation. Disconnect motor leads and inspect with a 500V Megohmmeter. |
| UNDERVOLTAGE | DCUV / UV | DC Bus Undervoltage | Mains incoming voltage sagged or phase lost. Measure incoming AC supply line across L1, L2, L3 terminals. |
| HEATSINK DTRP | OH | Heatsink Overtemperature | Power stack internal temperature sensor exceeded safety limit. Clean heatsink channels and verify cooling fan operation. |
| MOTOR OVERTEMP | OT | Motor Thermistor / I²t Trip | Motor thermistor circuit (TH1/TH2) open or sustained operation beyond rated motor continuous full load current. |
| CURRENT LIMIT | I-LIM | Current Limit Timeout | Drive operated at maximum current clamp for longer than allowed stall window. Inspect machine for mechanical jamming. |
| FIELD OVER I | F-OC (DC590+) | DC Field Overcurrent | DC motor field current exceeded calibrated threshold. Check DC motor shunt field resistance and supply voltage. |
| SPEED FEEDBACK | SPD-ERR | Encoder / Tachometer Failure | Feedback signal missing or differential encoder channels out of phase. Verify encoder wiring and screening. |
How to Clear & Reset Parker SSD Drive Trips
- Keypad Reset: Press the red STOP/RESET key on the 6901, 6511, or AC30 graphical operator keypad.
- Digital Input Reset: Momentarily pulse the digital terminal configured for “Trip Reset” (Menu: TRIP MANAGEMENT $\rightarrow$ TRIP RESET).
- DSE Lite / DSE890 Software: Connect via serial / USB / Ethernet interface, open the online diagnostics window, and click “Acknowledge / Reset Trip”.
- Fieldbus Control Word: Set the Trip Reset bit (Bit 7 or manufacturer control word bit) from `0` to `1` via Profinet, Ethernet/IP, or CANopen master PLC.
- Power Cycle: Disconnect the incoming 3-phase mains supply, wait until the internal DC bus discharge LED turns off completely, and restore mains power.