Parker AC20F Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker AC20F advanced hydraulic purpose and compact inverter drive series. Search or filter through the complete fault code directory below.
Power Range
1.5 – 180 kW (2 – 250 HP)
Supply Voltage
380–480V AC (3-Phase) / 230V
Control Modes
V/Hz, Vector & Hydraulic P/Q
Operator Interface
Keypad & DSE Lite PC Tool
Complete Parker AC20F Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC, OE, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 1 Over Voltage | Cause: The drive internal DC link voltage is too high.
Remedy:
|
| 2 Stack Over I | Cause: The motor current exceeded the capabilities of the power stack.
Remedy:
|
| 3 Under Voltage | Cause: DC link low trip.
Remedy:
|
| 4 Over Current | Cause: The motor current being drawn from the drive is too high.
Remedy:
|
| 5 Current Lim | Cause: (V/Hz mode only) Current exceeded 200% of stack rated current for 1 second.
Remedy:
|
| 6 Motor Stall | Cause: The motor has stalled (not rotating). Drive in current limit >200 seconds.
Remedy:
|
| 7 Inverse Time | Cause: A prolonged overload condition, exceeding the Inverse Time allowance. Remedy:
|
| 8 Motor I2t | Cause: (PMAC Motor only) Prolonged load condition exceeding motor rated current.
Remedy:
|
| 9 Low Speed I | Cause: Motor drawing too much current (>100%) at zero output frequency.
Remedy:
|
| 10 Heatsink Temp | Cause: Drive heatsink temperature too high.
Remedy:
|
| 11 Internal Temp | Cause: Processor or ambient temperature within power stage too high.
Remedy:
|
| 12 Motor Temp | Cause: The motor temperature is too high.
Remedy:
|
| 13 Dynamic Brake | Cause: External dynamic brake resistor has been overloaded.
Remedy:
|
| 14 Digout Load | Cause: 24V output voltage dropped by Digital output overload > 50 mA. Remedy:
|
| 15 Anin 1 Over | Cause: Analog Input current > 30 mA (Overload detected only in Current Mode). Remedy:
|
| 16 Anin 2 Over | Cause: Analog Input current > 30 mA (Overload detected only in Current Mode). Remedy:
|
| 17 Contactor | Cause: DC Link failed to reach undervoltage trip level within contactor feedback time.
Remedy:
|
| 18 Phase Fail | Cause: Indicates a missing input phase. Remedy:
|
| 19 Output Phase | Cause: Motor Output Phase is missing.
Remedy:
|
| 20 Vdc Ripple | Cause: The DC link ripple voltage is too high.
Remedy:
|
| 21 Pwr Loss Stop | Cause: A Power Loss Ride Through sequence occurred and limits were exceeded.
Remedy:
|
| 22 Overspeed | Cause: Motor Speed >150% base speed when in Sensorless Vector mode. Remedy:
|
| 23 PMAC Speed | Cause: (PMAC Motor) Start feature in Sensorless Vector Control failed.
Remedy:
|
| 24 Speed Sensor | Cause: Switchover Enable P0256 = TRUE.
Remedy:
|
| 25 Speed Error | Cause: Difference between actual motor speed and speed setpoint is too large.
Remedy:
|
| 26 Feedback Err | Cause: Configuration error for Closed Loop Vector control.
Remedy:
|
| 27 Command Loss | Cause: Communication lost.
Remedy:
|
| 28 Comms Break | Cause: Lost option communications.
Remedy:
|
| 29 Base Modbus | Cause: Lost Base Modbus communications. Remedy:
|
| 30 Fieldbus | Cause: Loss of connection to fieldbus master.
Remedy:
|
| 31 STO Active | Cause: Attempt to run the motor with Safe Torque Off active.
Remedy:
|
| 32 External Trip | Cause: The external (application) trip input is high. Remedy:
|
| 33 - 36 Application Trip (A1 - A4) | Cause: Controlled by Application_Trips block in configuration. Remedy:
|
| 37 CPU Loading | Cause: Combination of high switching frequency, network traffic, and complicated configuration. Remedy:
|
| 38 Track Error p | Cause: Difference between actual pressure and demand is too high. Remedy:
|
| 39 Track Error q | Cause: Difference between actual volume flow and demand is too high. Remedy:
|
| 40 Comp Protect | Cause: Actual motor speed lower than minimal pump/motor speed for protection time. Remedy:
|
| 41 p max | Cause: The actual pressure is greater than the maximal pressure value. Remedy:
|
| 42 Track Error Vel | Cause: (PMAC with feedback) Speed deviation > 500 rpm for > 1 second. Remedy:
|
| 25 (Autotune) ALL_TESTS_DISABLED | Cause: Parameter 0038 ATN TEST DISABLE set to 31. Remedy:
|
| 27 (Autotune) LEAKAGE_L_TIMEOUT | Cause: Required current cannot be reached. Remedy:
|
| 28 (Autotune) MOTOR_STALLED_ERROR | Cause: Motor stall during autotune (not rotating). Remedy:
|
| 34 (Autotune) SUPPLY_VOLTS_LOW | Cause: Available voltage supply is less than 70% of the rated motor volts. Remedy:
|
How to Clear & Reset Parker AC20F Drive Faults
- Keypad Reset: Press the red STOP / RESET key directly on the front operator keypad. If running under remote terminal or fieldbus sequencing, clear the active run command prior to resetting.
- Digital Input Reset (Terminal Control): If programmed via function block input logic, pulse the assigned 24V DC digital input terminal configured for Trip Reset (e.g., DIN1–DIN8).
- DSE Lite PC Software: Connect your PC via the onboard Ethernet port or USB interface, launch Parker DSE (Drive System Explorer) Lite software, and trigger “Trip Reset” in the online diagnostic screen.
- Industrial Ethernet / Fieldbus: Send a `0` to `1` transition on the Trip Reset bit of the Command Word over PROFINET, EtherCAT, Ethernet/IP, or Modbus TCP.
- Power Cycle: Disconnect main AC supply line power, wait at least 5 minutes until the display and power LEDs completely turn off (confirming internal DC bus capacitors have discharged below 50VDC), then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that the intermediate DC bus voltage measures strictly below 50VDC across terminals [DC+] and [DC-] before opening terminal covers, inspecting busbars, or touching motor output terminals U, V, and W on the Parker AC20F drive.