Parker AC650V Drive Fault Codes & Diagnostic Guide
Complete trip code directory, alarm causes, and step-by-step troubleshooting procedures for the Parker Hannifin / SSD Drives AC650V Sensorless Vector AC inverter series. Search or filter through the complete diagnostic index below.
Power Range
0.25 – 110 kW (0.3 – 150 HP)
Supply Voltage
200–240V (1/3-Ph) / 380–460V (3-Ph)
Control Modes
Sensorless Vector (SLV) & V/Hz Control
Operator Interface
6511 / 6521 Keypad & DSE Lite Software
Complete Parker AC650V Drive Fault Code Directory
Use the search box in the table below to quickly find your trip code (e.g., type OC, dC, or OH).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 1 OVERVOLTAGE | Cause: The drive internal dc link voltage is too high. Remedy:
|
| 2 UNDERVOLTAGE | Cause: DC link low trip. Remedy:
|
| 3 OVERCURRENT | Cause: The motor current being drawn from the drive is too high. Remedy:
|
| 4 HEATSINK | Cause: Drive heatsink temperature > 100ºC. Remedy:
|
| 5 EXTERNAL TRIP | Cause: The external trip input is high. Remedy:
|
| 6 INVERSE TIME | Cause: A prolonged overload condition, exceeding the Inverse Time allowance, has caused the trip. Remedy:
|
| 7 CURRENT LOOP | Cause: A current of less than 1mA is present when 4-20mA setpoint is selected. Remedy:
|
| 8 MOTOR STALLED | Cause: The motor has stalled (not rotating). Drive in current limit > 200 seconds. Remedy:
|
| 9 ANIN FAULT | Cause: AIN2 overload on terminal 3. Remedy:
|
| 10 BRAKE RESISTOR | Cause: External dynamic brake resistor has been overloaded. Remedy:
|
| 11 BRAKE SWITCH | Cause: Internal dynamic braking switch has been overloaded. Remedy:
|
| 12 DISPLAY/KEYPAD | Cause: Keypad has been disconnected from drive whilst drive is running in Local Control. Remedy:
|
| 13 LOST COMMS | Cause: Lost communications. Remedy:
|
| 14 CONTACTOR FBK | Cause: Contactor feedback signal lost. Remedy:
|
| 15 SPEED FEEDBACK | Cause: Speed feedback error. Remedy:
|
| 16 AMBIENT TEMP | Cause: Ambient temperature issue. Remedy:
|
| 17 MOTOR OVERTEMP | Cause: The motor temperature is too high. Remedy:
|
| 18 CURRENT LIMIT | Cause: Software overcurrent trip. Current exceeds 180% of stack rated current for 1 second. Remedy:
|
| 20 24V FAILURE | Cause: 24V failure on terminal 6. Remedy:
|
| 21 LOW SPEED OVER I | Cause: The motor is drawing too much current (>100%) at zero output frequency. Remedy:
|
| 22 10V FAULT | Cause: 10V fault. Remedy:
|
| 24 DESAT (OVER I) | Cause: Desaturation (Instantaneous overcurrent). Remedy:
|
| 25 DC LINK RIPPLE | Cause: The dc link ripple voltage is too high. Remedy:
|
| 26 BRAKE SHORT CCT | Cause: Brake resistor overcurrent. Remedy:
|
| 27 OVERSPEED | Cause: Overspeed detected. Remedy:
|
| 28 ANOUT FAULT | Cause: AOUT overload on terminal 5. Remedy:
|
| 29 DIGIO 1 (T9) FAULT | Cause: DIN3 overload on terminal 9. Remedy:
|
| 30 DIGIO 2 (T10) FAULT | Cause: DOUT2 overload on terminal 10. Remedy:
|
| 31 UNKNOWN | Cause: Unknown trip. Remedy:
|
| 32 OTHER | Cause: "OTHER" trip is active. Remedy:
|
| 34 MAX SPEED LOW | Cause: During Autotune, MAX SPEED RPM limits speed to less than nameplate speed. Remedy:
|
| 35 MAIN VOLTS LOW | Cause: The mains input voltage is not sufficient to carry out the Autotune. Remedy:
|
| 36 NOT AT SPEED | Cause: The motor was unable to reach the required speed to carry out the Autotune. Remedy:
|
| 37 MAG CURRENT FAIL | Cause: Not possible to find a suitable value of magnetising current. Remedy:
|
| 38 NEGATIVE SLIP F | Cause: Autotune calculated a negative slip frequency (invalid). Remedy:
|
| 39 TR TOO LARGE | Cause: The calculated value of rotor time constant is too large. Remedy:
|
| 40 TR TOO SMALL | Cause: The calculated value of rotor time constant is too small. Remedy:
|
| 41 MAX RPM DATA ERR | Cause: MAX SPEED RPM is set outside the Autotune data range (30% beyond previous max). Remedy:
|
| 42 LEAKGE L TIMEOUT | Cause: The motor must be stationary when starting the Autotune. Remedy:
|
| 43 MOTOR TURNING ERR | Cause: The motor must be able to rotate during Autotune. Remedy:
|
| 44 MOTOR STALL ERR | Cause: Leakage inductance measurement failed; required current level not achieved. Remedy:
|
| - Product Code Error | Cause: Product identification failure. Remedy:
|
| - Calibration Data Error | Cause: Calibration data corruption. Remedy:
|
| - Configuration Data Error | Cause: Configuration data corruption. Remedy:
|
How to Clear & Reset Parker AC650V Drive Faults
- Keypad Reset: Press the red STOP / RESET key on the 6511 (LED) or 6521 (LCD) keypad to acknowledge and clear the trip display after correcting the fault cause.
- Digital Input Reset (Control Terminals): Provide a momentary 24V DC pulse to the digital input configured for TRIP RESET in the SEQUENCING function block (typically assigned to terminal DIN3 or DIN4).
- DSE Lite PC Software: Connect your PC to the front P3 RS232 programming port using the Parker programming cable (6513), open DSE Lite, and select “Acknowledge Trip” within the live diagnostics view.
- TechBox Communication Option: Send a reset pulse by setting the Trip Reset bit from `0` to `1` in the Control Word over RS485 / Modbus RTU or Profibus DP option modules.
- Mains Power Cycle: Switch off the incoming AC supply power, wait at least 5 minutes for the internal DC bus capacitor bank to fully discharge until the display goes completely off, and restore power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated CAT III or CAT IV multimeter (rated up to 1000V) that intermediate DC bus voltage measures strictly below 50VDC across terminals [DC+] and [DC-] (or braking resistor terminals DB+ and DB-) as well as motor output terminals (M1/U, M2/V, M3/W relative to PE) before removing covers or handling wiring on the Parker AC650V drive.