Parker AC650V Drive Fault Codes & Diagnostic Guide

Complete trip code directory, alarm causes, and step-by-step troubleshooting procedures for the Parker Hannifin / SSD Drives AC650V Sensorless Vector AC inverter series. Search or filter through the complete diagnostic index below.

Sensorless Vector AC Drive Power: 0.25 to 110 kW (0.3 to 150 HP) Frames 1 through F
Power Range 0.25 – 110 kW (0.3 – 150 HP)
Supply Voltage 200–240V (1/3-Ph) / 380–460V (3-Ph)
Control Modes Sensorless Vector (SLV) & V/Hz Control
Operator Interface 6511 / 6521 Keypad & DSE Lite Software

Complete Parker AC650V Drive Fault Code Directory

Use the search box in the table below to quickly find your trip code (e.g., type OC, dC, or OH).

Fault Code and MeaningCause and Remedy
1

OVERVOLTAGE

Cause: The drive internal dc link voltage is too high.



Remedy:

  • Check if the supply voltage is too high.

  • Trying to decelerate a large inertia load too quickly; DECEL TIME too short.

  • The brake resistor is open circuit.


2

UNDERVOLTAGE

Cause: DC link low trip.



Remedy:

  • Supply is too low or power down occurred.


3

OVERCURRENT

Cause: The motor current being drawn from the drive is too high.



Remedy:

  • Trying to accelerate a large inertia load too quickly; Check ACCEL TIME.

  • Trying to decelerate a large inertia load too quickly; Check DECEL TIME.

  • Application of shock load to motor.

  • Check for short circuit between motor phases.

  • Check for short circuit between motor phase and earth.

  • Motor output cables too long or too many parallel motors connected to the drive.

  • FIXED BOOST level set too high.


4

HEATSINK

Cause: Drive heatsink temperature > 100ºC.



Remedy:

  • The ambient air temperature is too high.

  • Poor ventilation or spacing between drives.


5

EXTERNAL TRIP

Cause: The external trip input is high.



Remedy:

  • Check configuration to identify the source of the signal (non-standard configuration).


6

INVERSE TIME

Cause: A prolonged overload condition, exceeding the Inverse Time allowance, has caused the trip.



Remedy:

  • Remove the overload condition.


7

CURRENT LOOP

Cause: A current of less than 1mA is present when 4-20mA setpoint is selected.



Remedy:

  • Look for a wire break.


8

MOTOR STALLED

Cause: The motor has stalled (not rotating). Drive in current limit > 200 seconds.



Remedy:

  • Motor loading too great.

  • FIXED BOOST level set too high.


9

ANIN FAULT

Cause: AIN2 overload on terminal 3.



Remedy:

  • Overcurrent applied in Current mode to terminal 3.


10

BRAKE RESISTOR

Cause: External dynamic brake resistor has been overloaded.



Remedy:

  • Trying to decelerate a large inertia too quickly or too often.


11

BRAKE SWITCH

Cause: Internal dynamic braking switch has been overloaded.



Remedy:

  • Trying to decelerate a large inertia too quickly or too often.


12

DISPLAY/KEYPAD

Cause: Keypad has been disconnected from drive whilst drive is running in Local Control.



Remedy:

  • Keypad accidentally disconnected from drive (indicated over Comms, or by second keypad).


13

LOST COMMS

Cause: Lost communications.



Remedy:

  • COMMS TIMEOUT parameter set too short.

  • Master device failed.

  • Wiring broken.

  • Incorrect Comms setup.


14

CONTACTOR FBK

Cause: Contactor feedback signal lost.



Remedy:

  • Check connection to the terminal wired to "contactor closed" parameter in Sequencing Logic.


15

SPEED FEEDBACK

Cause: Speed feedback error.



Remedy:

  • SPEED ERROR > 50.00% for 10 seconds.


16

AMBIENT TEMP

Cause: Ambient temperature issue.



Remedy:

  • The ambient temperature in the drive is too high.


17

MOTOR OVERTEMP

Cause: The motor temperature is too high.



Remedy:

  • Excessive load.

  • Motor voltage rating incorrect.

  • FIXED BOOST level set too high.

  • Prolonged operation of the motor at low speed without forced cooling.

  • Break in motor thermistor connection.


18

CURRENT LIMIT

Cause: Software overcurrent trip. Current exceeds 180% of stack rated current for 1 second.



Remedy:

  • Remove the shock load.

  • ACCEL TIME and/or FIXED BOOST set too high.

  • DECEL TIME set too low.


20

24V FAILURE

Cause: 24V failure on terminal 6.



Remedy:

  • Output overload (warning only). 150mA maximum either individually or as the sum of terminals 6 & 10.


21

LOW SPEED OVER I

Cause: The motor is drawing too much current (>100%) at zero output frequency.



Remedy:

  • FIXED BOOST level set too high.


22

10V FAULT

Cause: 10V fault.



Remedy:

  • +10V REF overload warning (terminal 4) - 10mA maximum.


24

DESAT (OVER I)

Cause: Desaturation (Instantaneous overcurrent).



Remedy:

  • Refer to OVERCURRENT entry in this table.


25

DC LINK RIPPLE

Cause: The dc link ripple voltage is too high.



Remedy:

  • Check for a missing input phase.


26

BRAKE SHORT CCT

Cause: Brake resistor overcurrent.



Remedy:

  • Check brake resistor value is greater than minimum allowed.


27

OVERSPEED

Cause: Overspeed detected.



Remedy:

  • >150% base speed when in Sensorless Vector mode.


28

ANOUT FAULT

Cause: AOUT overload on terminal 5.



Remedy:

  • Current exceeded 10mA maximum.


29

DIGIO 1 (T9) FAULT

Cause: DIN3 overload on terminal 9.



Remedy:

  • Current exceeded 20mA maximum.


30

DIGIO 2 (T10) FAULT

Cause: DOUT2 overload on terminal 10.



Remedy:

  • 150mA maximum either individually or as the sum of terminals 6 & 10.


31

UNKNOWN

Cause: Unknown trip.



Remedy:

  • Consult technical support.


32

OTHER

Cause: "OTHER" trip is active.



Remedy:

  • Refer to Trip ID 34 to 44 inclusive.


34

MAX SPEED LOW

Cause: During Autotune, MAX SPEED RPM limits speed to less than nameplate speed.



Remedy:

  • Increase the value of MAX SPEED RPM up to the nameplate rpm of the motor (as a minimum).

  • It may be reduced, if required, after the Autotune is complete.


35

MAIN VOLTS LOW

Cause: The mains input voltage is not sufficient to carry out the Autotune.



Remedy:

  • Re-try when the mains has recovered.


36

NOT AT SPEED

Cause: The motor was unable to reach the required speed to carry out the Autotune.



Remedy:

  • Check if motor shaft is free to turn.

  • Check if the motor data is correct.


37

MAG CURRENT FAIL

Cause: Not possible to find a suitable value of magnetising current.



Remedy:

  • Check the motor data is correct (nameplate rpm and motor volts).

  • Check that the motor is correctly rated for the drive.


38

NEGATIVE SLIP F

Cause: Autotune calculated a negative slip frequency (invalid).



Remedy:

  • Check nameplate rpm, base frequency, and pole pairs are correct.

  • Ensure Nameplate rpm is not set higher than base speed.


39

TR TOO LARGE

Cause: The calculated value of rotor time constant is too large.



Remedy:

  • Check the value of nameplate rpm.


40

TR TOO SMALL

Cause: The calculated value of rotor time constant is too small.



Remedy:

  • Check the value of nameplate rpm.


41

MAX RPM DATA ERR

Cause: MAX SPEED RPM is set outside the Autotune data range (30% beyond previous max).



Remedy:

  • Re-autotune with MAX SPEED RPM set to a higher value.


42

LEAKGE L TIMEOUT

Cause: The motor must be stationary when starting the Autotune.



Remedy:

  • Ensure motor is stopped before starting Autotune.


43

MOTOR TURNING ERR

Cause: The motor must be able to rotate during Autotune.



Remedy:

  • Uncouple load or unlock brake if preventing rotation.


44

MOTOR STALL ERR

Cause: Leakage inductance measurement failed; required current level not achieved.



Remedy:

  • Check that the motor is wired correctly.


-

Product Code Error

Cause: Product identification failure.



Remedy:

  • Switch unit off/on.

  • If persistent, return unit to factory.


-

Calibration Data Error

Cause: Calibration data corruption.



Remedy:

  • Switch unit off/on.

  • If persistent, return unit to factory.


-

Configuration Data Error

Cause: Configuration data corruption.



Remedy:

  • Press the E key to accept the default configuration.

  • If persistent, return unit to factory.


How to Clear & Reset Parker AC650V Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the 6511 (LED) or 6521 (LCD) keypad to acknowledge and clear the trip display after correcting the fault cause.
  2. Digital Input Reset (Control Terminals): Provide a momentary 24V DC pulse to the digital input configured for TRIP RESET in the SEQUENCING function block (typically assigned to terminal DIN3 or DIN4).
  3. DSE Lite PC Software: Connect your PC to the front P3 RS232 programming port using the Parker programming cable (6513), open DSE Lite, and select “Acknowledge Trip” within the live diagnostics view.
  4. TechBox Communication Option: Send a reset pulse by setting the Trip Reset bit from `0` to `1` in the Control Word over RS485 / Modbus RTU or Profibus DP option modules.
  5. Mains Power Cycle: Switch off the incoming AC supply power, wait at least 5 minutes for the internal DC bus capacitor bank to fully discharge until the display goes completely off, and restore power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated CAT III or CAT IV multimeter (rated up to 1000V) that intermediate DC bus voltage measures strictly below 50VDC across terminals [DC+] and [DC-] (or braking resistor terminals DB+ and DB-) as well as motor output terminals (M1/U, M2/V, M3/W relative to PE) before removing covers or handling wiring on the Parker AC650V drive.