Parker AC10 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker AC10 compact variable speed drive series. Search or filter through the complete fault code directory below.

Compact Variable Speed Drive Power: 0.2 to 180 kW (0.25 to 250 HP) IP20 & IP66 / NEMA 4X Protection
Power Range 0.2 – 180 kW (0.25 – 250 HP)
Supply Voltage 230V (1/3-Ph) & 400–480V (3-Ph)
Control Modes V/Hz & Sensorless Vector (SVC)
Operator Interface LED Keypad & DSE Lite PC Tool

Complete Parker AC10 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC, OE, or LU).

Fault CodeCause & Solution
AErr Line Disconnected

- Analog signal line disconnected
- Signal source is broken
- Change the signal line
- Change the signal source
CE
Communication
Timeout
Communication fault
- PC/PLC does not send command at fixed time
- Check communication line for reliable connected
Err1
Password
is Wrong
Cause: Password is Wrong.

Solution:

- When password function is enabled, password is set wrong
- Set password correctly
Err2
Tuning
Parameters
Wrong
Cause: Tuning Parameters Wrong

Solution:

- incorrect motor parameters entered
- Connect motor correctly
- Enter correct motor data
Err3
Current
Malfunction
Before
Running
Cause: Current MalfunctionBefore Running.

Solution:

- Current alarm signal exists before running
- Check if control board is properly connected to power board
Err4
Current Zero
Excursion
Malfunction
Cause: Current Zero Excursion Malfunction.

Solution:

- Flat cable is loosened
- Current detector is broken
- Check the flat cable
Err5
PID
Parameters
are set
Wrong
Cause: PID Parameters are set Wrong.

Solution:

- PID parameters are set wrong.
- Set the parameters correctly.
FL
Flycatching
Fault
Cause: FL Flycatching Fault.

Solution:

- Flycatching failure.
- Track again.
GP
Ground
fault
Cause: GP Ground fault.

Solution:

- Motor cable is broken and short- circuit to earth
- The insulation of motor is broken and short circuit to earth
- Inverter has fault
- Change motor cable
- Repair or replace motor
- SEE ALSO: OC, OC2 and ERR4
L.U. / LU
Under-Voltage
Cause: Under-Voltage Protection.

Solution:

- Low voltage on the input side
- Check if supply voltage is normal
- Check if parameter setting is correct
OC/OC2
Overcurrent
Cause: Overcurrent.

- Too short acceleration time
- Short circuit at output side
- Locked rotor with motor
- Parameter tuning is not correct
- Prolong acceleration time
- Ask if motor is cable broken
- Check if motor overloads
- Reduce VVVF compensation value
- Measure parameter correctly
OC1
Overcurrent
Cause: Overcurrent.

- Too short acceleration time
- Short circuit at output side
- Locked rotor with motor
- Parameter tuning is not correct
- Prolong acceleration time
- Ask if motor is cable broken
- Check if motor overloads
- Reduce VVVF compensation value
- Measure parameter correctly
O.E. / OE
DC
Over-Voltage
Cause: DC Over-Voltage.
- Supply voltage too high
- Load inertia too big
- Deceleration time too short
- Motor inertia rise again
- Parameter of speed loop PID is set abnormally

Solution:

- Check if rated voltage is input
- Add braking resistance(optional)
- Increase deceleration time
- Set the parameter of rotary speed loop PID correctly
O.H. / OH
Heatsink
Overheat
Cause:

- Environment temperature too high
- Poor ventilation
- Fan damaged
- Carrier wave frequency or compensation curve is too high

Solution:

- Improve ventilation
- Clean air inlet and outlet and radiator
- Install as required
- Change fan
- Decrease carrier wave frequency or compensation curve
O.L1 / OL1
Inverter
Overload
Cause & Solution:

1. Inverter Overload

- Load too heavy
- Reduce load; check drive ratio
- Increase inverter’s capacity
O.L2 / OL2
Motor
Overload
Cause & Solution:

1. Motor Overload.

- Load too heavy
- Reduce load: check drive ratio
- Increase motor’s capacity
PCE
PMSM
tuning
fault
Cause & Solution:

PMSM tuning fault

- Load is too heavy
- Motor parameters measurement is wrong
- Decrease the load
- Measure motor parameters correctly
P.F1. / PF1
Input Phase
Loss
Cause & Solution:

Input Phase Loss.
- Phase loss with input power
- Check if power input is normal
- Check if parameter setting is correct
PF0
Output
Phase Loss
Cause & Solution:

Output Phase Loss.
- Motor is broken
- Motor wire is loose
- Inverter is broken
- Check if wire of motor is loose
- Check if motor is broken

How to Clear & Reset Parker AC10 Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key (marked O) directly on the integrated front 7-segment LED keypad. If operating under terminal control, remove the Run command prior to clearing the fault.
  2. Digital Input Reset (Terminal Control): Configure a digital input (parameters F316 to F323) for function 9 (Fault Reset), then apply a momentary 24V DC pulse to the assigned terminal (e.g., DI1–DI8).
  3. DSE Lite PC Tool: Connect your PC to the drive’s RJ45 communication port via a USB-to-RS485 interface converter, launch Parker DSE (Drive System Explorer) Lite software, and issue a “Trip Reset” command from the diagnostics window.
  4. Modbus RTU Communication: Write a reset bit command (`0` to `1` transition) to the control register via the integrated RS485 serial communication port.
  5. Power Cycle: Disconnect main AC incoming power, wait at least 5 minutes until the LED display and charge indicators completely extinguish (confirming intermediate DC bus capacitors have discharged below 50VDC), then reapply mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the intermediate DC bus voltage measures strictly below 50VDC across terminals [+] and [-] (or DC bus test points) before inspecting motor leads, opening terminal covers, or touching terminals U, V, and W on the Parker AC10 drive.