Parker AC10P Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker AC10P compact AC variable frequency drive series. Search or filter through the complete fault code directory below.
Power Range
0.2 – 180 kW (0.25 – 250 HP)
Supply Voltage
230V 1-Ph / 230V & 400V 3-Ph
Control Modes
V/Hz, Sensorless & Closed-Loop Vector
Operator Interface
Integrated LED Keypad / DSE Lite
Complete Parker AC10P Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC, OE, LU, or Err).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Err0 Prohibition modify function code | Cause: Prohibition modify the function code during running process. Remedy:
|
| Err1 Wrong password | Cause: Entered wrong password when password is valid. Do not enter password when modifying function code. Remedy:
|
| 2: O.C. 16: OC1 67: OC2 Over-current (1 & 2) | Cause: Too short acceleration time; short circuit at output side; locked rotor with motor; too heavy load; parameter tuning is not correct. Remedy:
|
| 3: O.E. DC Over-Voltage | Cause: Supply voltage too high; load inertia too big; deceleration time too short; motor inertia rise again; bad effect of dynamic braking; parameter of rotary speed loop PID is set abnormally. Remedy:
|
| 4: P.F1. Input Phase loss | Cause: Phase loss with input power. Remedy:
|
| 5: O.L1 Inverter Overload | Cause: Load too heavy. Remedy:
|
| 6: L.U. Under-Voltage Protection | Cause: Input voltage on the low side. Remedy:
|
| 7: O.H. Radiator Overheat | Cause: Environment temperature too high; radiator too dirty; install place not good for ventilation; fan damaged; Carrier wave frequency or compensation curve is too high. Remedy:
|
| 8: O.L2 Motor Overload | Cause: Load too heavy. Remedy:
|
| 11: ESP External fault | Cause: External emergency-stop terminal is valid. Remedy:
|
| 12: Err3 Current malfunction before running | Cause: Current alarm signal exists before running. Remedy:
|
| 13: Err2 Parameters tuning wrong | Cause: Do not connect motor when measuring parameters. Remedy:
|
| 15: Err4 Current zero excursion malfunction | Cause: Flat cable is loosened; Current detector is broken. Remedy:
|
| 17: PF0 Output Phase loss | Cause: Motor is broken; Motor wire is loose; Inverter is broken. Remedy:
|
| 18: AErr Line disconnected | Cause: Analog signal line disconnected; Signal source is broken. Remedy:
|
| 19: EP3 20: EP/EP2 Inverter under-load | Cause: Water pump dries up; Belt is broken; Equipment is broken. Remedy:
|
| 22: nP Pressure control | Cause: Pressure is too high when negative feedback; Pressure is too low when positive feedback; Inverter enters into the dormancy status. Remedy:
|
| 23: Err5 PID parameters are set wrong | Cause: PID parameters are set wrong. Remedy:
|
| 26: GP Earth fault protection | Cause: Motor cable is damaged, short connected to grounding; Motor isolation is damaged, short connected to grounding; Inverter fault. Remedy:
|
| 27: GP Encoder fault | Cause: Encoder installation error; Encoder fault; Encoder line number fault. Remedy:
|
| 32: PCE PMSM distuning fault | Cause: Motor parameters measurement is wrong; Load is too heavy. Remedy:
|
| 35: OH1 PTC overheat protection | Cause: External relay protection. Remedy:
|
| 44: Er44 Master loses slave’s response | Cause: Communication fault between master and slave. Remedy:
|
| 45: CE Communication timeout error | Cause: Communication fault. Remedy:
|
| 47: EEEP EEPROM read/write fault | Cause: Interference around; EEPROM is damaged. Remedy:
|
| 49: Err6 Watchdog fault | Cause: Watchdog timeout. Remedy:
|
How to Clear & Reset Parker AC10P Drive Faults
- Keypad Reset: Press the red STOP / RESET key on the front integrated LED keypad to clear the trip state once the active fault condition has been resolved.
- Digital Input Reset (DI): If programmed via multi-function digital input parameters (e.g., parameter group
F200–F209set to fault reset), apply a momentary pulse between the assigned digital input terminal (DI1–DI6) and the common terminal (CM). - Automatic Fault Auto-Restart: If enabled in parameter F214 (Fault Auto-Reset Selection), the drive can automatically clear trips and restart up to the number of attempts configured in F216 after the delay time set in F215.
- Serial / Fieldbus Command: Send a fault reset command bit via the integrated Modbus RTU communication interface over RS485 terminals (A+ and B-) or optional fieldbus modules.
- Power Cycle: Disconnect the incoming AC line power supply, allow the internal DC bus capacitors to discharge fully until the LED display is completely off (wait at least 5 minutes), then restore power.
⚠️ High-Voltage Electrical Safety Warning:
Hazardous residual voltages exist inside the drive after power removal. Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+] and [-] (or P and B/N) before inspecting wiring, checking the dynamic braking resistor, or servicing motor terminals U, V, and W.