Parker AC10P Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker AC10P compact AC variable frequency drive series. Search or filter through the complete fault code directory below.

Compact General Purpose Drive Power: 0.2 to 180 kW (0.25 to 250 HP) Sensorless Vector & Closed-Loop Control
Power Range 0.2 – 180 kW (0.25 – 250 HP)
Supply Voltage 230V 1-Ph / 230V & 400V 3-Ph
Control Modes V/Hz, Sensorless & Closed-Loop Vector
Operator Interface Integrated LED Keypad / DSE Lite

Complete Parker AC10P Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC, OE, LU, or Err).

Fault Code and MeaningCause and Remedy
Err0
Prohibition modify function code

Cause: Prohibition modify the function code during running process.



Remedy:

  • Please modify the function code in stopped status.


Err1
Wrong password

Cause: Entered wrong password when password is valid. Do not enter password when modifying function code.



Remedy:

  • Please enter the correct password.


2: O.C.
16: OC1
67: OC2
Over-current (1 & 2)

Cause:
Too short acceleration time; short circuit at output side; locked rotor with motor; too heavy load; parameter tuning is not correct.



Remedy:

  • Prolong acceleration time.

  • Check whether motor cable is broken.

  • Check if motor overloads.

  • Reduce V/F compensation value.

  • Measure parameter correctly.


3: O.E.
DC Over-Voltage

Cause:
Supply voltage too high; load inertia too big; deceleration time too short; motor inertia rise again; bad effect of dynamic braking; parameter of rotary speed loop PID is set abnormally.



Remedy:

  • Check if rated voltage is input.

  • Add braking resistance (optional).

  • Increase deceleration time.

  • Enhancing the dynamic braking effect.

  • Set the parameter of rotary speed loop PID correctly.

  • Change to VF control for centrifugal fan.


4: P.F1.
Input Phase loss

Cause: Phase loss with input power.



Remedy:

  • Check if power input is normal.

  • Check if parameter setting is correct.


5: O.L1
Inverter Overload

Cause: Load too heavy.



Remedy:

  • Reduce load.

  • Check drive ratio.

  • Increase inverter’s capacity.


6: L.U.
Under-Voltage Protection

Cause: Input voltage on the low side.



Remedy:

  • Check if supply voltage is normal.

  • Check if parameter setting is correct.


7: O.H.
Radiator Overheat

Cause:
Environment temperature too high; radiator too dirty; install place not good for ventilation; fan damaged; Carrier wave frequency or compensation curve is too high.



Remedy:

  • Improve ventilation.

  • Clean air inlet, outlet, and radiator.

  • Install as required.

  • Change fan.

  • Decrease carrier wave frequency or compensation curve.


8: O.L2
Motor Overload

Cause: Load too heavy.



Remedy:

  • Reduce load.

  • Check drive ratio.

  • Increase motor’s capacity.


11: ESP
External fault

Cause: External emergency-stop terminal is valid.



Remedy:

  • Check external fault.


12: Err3
Current malfunction before running

Cause: Current alarm signal exists before running.



Remedy:

  • Check if control board is connected with power board well.

  • Ask for help from manufacturer.


13: Err2
Parameters tuning wrong

Cause: Do not connect motor when measuring parameters.



Remedy:

  • Please connect motor correctly.


15: Err4
Current zero excursion malfunction

Cause: Flat cable is loosened; Current detector is broken.



Remedy:

  • Check the flat cable.

  • Ask for help from manufacturer.


17: PF0
Output Phase loss

Cause: Motor is broken; Motor wire is loose; Inverter is broken.



Remedy:

  • Check if wire of motor is loose.

  • Check if motor is broken.


18: AErr
Line disconnected

Cause: Analog signal line disconnected; Signal source is broken.



Remedy:

  • Change the signal line.

  • Change the signal source.


19: EP3
20: EP/EP2
Inverter under-load

Cause: Water pump dries up; Belt is broken; Equipment is broken.



Remedy:

  • Supply water for pump.

  • Change the belt.

  • Repair the equipment.


22: nP
Pressure control

Cause: Pressure is too high when negative feedback; Pressure is too low when positive feedback; Inverter enters into the dormancy status.



Remedy:

  • Decrease the min frequency of PID.

  • Reset inverter to normal status.


23: Err5
PID parameters are set wrong

Cause: PID parameters are set wrong.



Remedy:

  • Set the parameters correctly.


26: GP
Earth fault protection

Cause: Motor cable is damaged, short connected to grounding; Motor isolation is damaged, short connected to grounding; Inverter fault.



Remedy:

  • Change a new cable.

  • Repair the motor.

  • Contact manufacturer.


27: GP
Encoder fault

Cause: Encoder installation error; Encoder fault; Encoder line number fault.



Remedy:

  • Check the installation and connection.

  • Check encoder.

  • Set F851 correctly.


32: PCE
PMSM distuning fault

Cause: Motor parameters measurement is wrong; Load is too heavy.



Remedy:

  • Measure motor parameters correctly.

  • Decrease the load.


35: OH1
PTC overheat protection

Cause: External relay protection.



Remedy:

  • Check external heat protection equipment.


44: Er44
Master loses slave’s response

Cause: Communication fault between master and slave.



Remedy:

  • Check wiring.

  • Check baud rate.

  • Check communication parameters setting.


45: CE
Communication timeout error

Cause: Communication fault.



Remedy:

  • Check if PC/PLC sends command at fixed time.

  • Check whether the communication line is connected reliably.


47: EEEP
EEPROM read/write fault

Cause: Interference around; EEPROM is damaged.



Remedy:

  • Remove interferences.

  • Contact manufacturer.


49: Err6
Watchdog fault

Cause: Watchdog timeout.



Remedy:

  • Please check watchdog signal.


How to Clear & Reset Parker AC10P Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the front integrated LED keypad to clear the trip state once the active fault condition has been resolved.
  2. Digital Input Reset (DI): If programmed via multi-function digital input parameters (e.g., parameter group F200–F209 set to fault reset), apply a momentary pulse between the assigned digital input terminal (DI1–DI6) and the common terminal (CM).
  3. Automatic Fault Auto-Restart: If enabled in parameter F214 (Fault Auto-Reset Selection), the drive can automatically clear trips and restart up to the number of attempts configured in F216 after the delay time set in F215.
  4. Serial / Fieldbus Command: Send a fault reset command bit via the integrated Modbus RTU communication interface over RS485 terminals (A+ and B-) or optional fieldbus modules.
  5. Power Cycle: Disconnect the incoming AC line power supply, allow the internal DC bus capacitors to discharge fully until the LED display is completely off (wait at least 5 minutes), then restore power.
⚠️ High-Voltage Electrical Safety Warning: Hazardous residual voltages exist inside the drive after power removal. Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+] and [-] (or P and B/N) before inspecting wiring, checking the dynamic braking resistor, or servicing motor terminals U, V, and W.