Parker AC650G Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker AC650G sensorless vector drive series. Search or filter through the complete fault code directory below.

General Purpose Vector Drive Power: 0.25 to 7.5 kW (Up to 110 kW Extended) High Torque Sensorless Vector
Power Range 0.25 – 7.5 kW (0.3 – 10 HP)
Supply Voltage 220–240V (1Ø/3Ø) & 380–460V (3Ø)
Control Modes V/Hz & Sensorless Flux Vector
Operator Interface 6511 / 6521 Keypad & DSE Lite

Complete Parker AC650G Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type dCHI, OC, or OVERCURRENT).

Fault Code and MeaningCause and Remedy
1
OVERVOLTAGE

Cause:
The drive internal dc link voltage is too high.



Remedy:

  • The supply voltage is too high.

  • Trying to decelerate a large inertia load too quickly; DECEL TIME too short.

  • The brake resistor is open circuit.


2
UNDERVOLTAGE

Cause:
DC link low trip.



Remedy:

  • Supply is too low/power down.


3
OVERCURRENT

Cause:
The motor current being drawn from the drive is too high.



Remedy:

  • Trying to accelerate a large inertia load too quickly; ACCEL TIME too short.

  • Trying to decelerate a large inertia load too quickly; DECEL TIME too short.

  • Application of shock load to motor.

  • Short circuit between motor phases.

  • Short circuit between motor phase and earth.

  • Motor output cables too long or too many parallel motors connected to the drive.

  • FIXED BOOST level set too high.


4
HEATSINK

Cause:
Drive heatsink temperature > 100ºC.



Remedy:

  • The ambient air temperature is too high.

  • Poor ventilation or spacing between drives.


5
EXTERNAL TRIP

Cause:
The external trip input is high.



Remedy:

  • Check configuration to identify the source of the signal (non-standard configuration).


6
INVERSE TIME

Cause:
A prolonged overload condition, exceeding the Inverse Time allowance, has caused the trip.



Remedy:

  • Remove the overload condition.


7
CURRENT LOOP

Cause:
A current of less than 1mA is present when 4-20mA setpoint is selected.



Remedy:

  • Look for a wire break.


8
MOTOR STALLED

Cause:
The motor has stalled (not rotating). Drive in current limit >200 seconds.



Remedy:

  • Motor loading too great.

  • FIXED BOOST level set too high.


9
ANIN FAULT

Cause:
AIN2 overload on terminal 3.



Remedy:

  • Overcurrent applied in Current mode to terminal 3.


10
BRAKE RESISTOR

Cause:
External dynamic brake resistor has been overloaded.



Remedy:

  • Trying to decelerate a large inertia too quickly or too often.


11
BRAKE SWITCH

Cause:
Internal dynamic braking switch has been overloaded.



Remedy:

  • Trying to decelerate a large inertia too quickly or too often.


12
DISPLAY/KEYPAD

Cause:
Keypad has been disconnected from drive whilst drive is running in Local Control.



Remedy:

  • Check if keypad was accidentally disconnected from drive (indicated over Comms, or by second keypad).


13
LOST COMMS

Cause:
Lost communications.



Remedy:

  • COMMS TIMEOUT parameter set too short.

  • Master device failed.

  • Wiring broken.

  • Incorrect Comms setup.


14
CONTACTOR FBK

Cause:
Contactor feedback signal lost.



Remedy:

  • Check connection to the terminal wired to "contactor closed" parameter in Sequencing Logic.


15
SPEED FEEDBACK

Cause:
Speed feedback error.



Remedy:

  • SPEED ERROR > 50.00% for 10 seconds.


16
AMBIENT TEMP

Cause:
Ambient temperature issue.



Remedy:

  • The ambient temperature in the drive is too high.


17
MOTOR OVERTEMP

Cause:
The motor temperature is too high.



Remedy:

  • Excessive load.

  • Motor voltage rating incorrect.

  • FIXED BOOST level set too high.

  • Prolonged operation of the motor at low speed without forced cooling.

  • Break in motor thermistor connection.


18
CURRENT LIMIT

Cause:
Software overcurrent trip. If the current exceeds 180% of stack rated current for 1 second, the drive will trip.



Remedy:

  • Caused by shock loads: Remove the shock load.

  • ACCEL TIME and/or FIXED BOOST set too high.

  • DECEL TIME set too low.


21
LOW SPEED OVER I

Cause:
The motor is drawing too much current (>100%) at zero output frequency.



Remedy:

  • FIXED BOOST level set too high.


22
10V FAULT

Cause:
10V fault detected.



Remedy:

  • +10V REF overload warning (terminal 4) - 10mA maximum.


25
DC LINK RIPPLE

Cause:
The dc link ripple voltage is too high.



Remedy:

  • Check for a missing input phase.


27
OVERSPEED

Cause:
Overspeed detected.



Remedy:

  • >150% base speed when in Sensorless Vector mode.


28
ANOUT FAULT

Cause:
AOUT overload on terminal 5.



Remedy:

  • 10mA maximum.


29
DIGIO 1 (T9) FAULT

Cause:
DIN3 overload on terminal 9.



Remedy:

  • 20mA maximum.


30
DIGIO 2 (T10) FAULT

Cause:
DOUT2 overload on terminal 10.



Remedy:

  • 50mA maximum.


31
UNKNOWN

Cause:
Unknown trip.



Remedy:

  • Consult technical support if persistent.


32
OTHER

Cause:
"OTHER" trip is active (Trip ID 34 to 44 inclusive).



Remedy:

  • Check specific Trip ID (34-44) for details.


34
MAX SPEED LOW

Cause:
During Autotune, MAX SPEED RPM limits the speed to less than the nameplate speed of the motor.



Remedy:

  • Increase the value of MAX SPEED RPM up to the nameplate rpm of the motor (as a minimum).

  • It may be reduced, if required, after the Autotune is complete.


35
MAIN VOLTS LOW

Cause:
The mains input voltage is not sufficient to carry out the Autotune.



Remedy:

  • Re-try when the mains has recovered.


36
NOT AT SPEED

Cause:
The motor was unable to reach the required speed to carry out the Autotune.



Remedy:

  • Motor shaft not free to turn.

  • The motor data is incorrect.


37
MAG CURRENT FAIL

Cause:
It was not possible to find a suitable value of magnetising current to achieve the required operating condition for the motor.



Remedy:

  • Check the motor data is correct, especially nameplate rpm and motor volts.

  • Check that the motor is correctly rated for the drive.


38
NEGATIVE SLIP F

Cause:
Autotune has calculated a negative slip frequency, which is not valid.



Remedy:

  • Nameplate rpm may have been set to a value higher than the base speed of the motor.

  • Check nameplate rpm, base frequency, and pole pairs are correct.


39
TR TOO LARGE

Cause:
The calculated value of rotor time constant is too large.



Remedy:

  • Check the value of nameplate rpm.


40
TR TOO SMALL

Cause:
The calculated value of rotor time constant is too small.



Remedy:

  • Check the value of nameplate rpm.


41
MAX RPM DATA ERR

Cause:
MAX SPEED RPM is set to a value outside the range for which Autotune has gathered data. The drive had no data for this new operating area.



Remedy:

  • To run the motor beyond this point it is necessary to re-autotune with MAX SPEED RPM set to a higher value.


42
LEAKGE L TIMEOUT

Cause:
The motor is moving during Autotune.



Remedy:

  • The motor must be stationary when starting the Autotune.


43
MOTOR TURNING ERR

Cause:
The motor cannot rotate during Autotune.



Remedy:

  • The motor must be able to rotate during Autotune.


44
MOTOR STALL ERR

Cause:
The leakage inductance measurement requires a test current to be inserted into the motor. It has not been possible to achieve the required level of current.



Remedy:

  • Check that the motor is wired correctly.


Product Code Error
Cause:
Internal product code error detected.



Remedy:

  • Switch unit off/on. If persistent, return unit to factory.


Calibration Data Error
Cause:
Internal calibration data error detected.



Remedy:

  • Switch unit off/on. If persistent, return unit to factory.


Configuration Data Error
Cause:
Internal configuration data error detected.



Remedy:

  • Press the E key to accept the default configuration.

  • If persistent, return unit to factory.


How to Clear & Reset Parker AC650G Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the 6511 (or 6521) keypad. Ensure any active run signal on the digital terminals is removed before clearing the trip.
  2. Digital Input Reset (DIN): Assert the assigned digital terminal configured as Trip Reset via the drive’s parameter configuration.
  3. Parker DSE Lite PC Software: Connect your PC via the RS232 / P3 programming port with the configuration cable, launch DSE Lite, and click Reset in the active trip diagnostics window.
  4. Serial / Fieldbus Communications: Write a reset command bit across the installed communication module (RS485 Modbus RTU or Profibus option interface).
  5. Power Cycle: Disconnect the incoming AC power supply, wait at least 5 minutes until the internal DC bus capacitors completely discharge and the 4-digit display goes dark, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated CAT III/CAT IV multimeter that intermediate DC link bus voltage measures strictly below 50VDC across terminals [DC+] and [DC-] (or braking terminals) before inspecting motor leads, opening terminal covers, or touching terminals U, V, and W on the Parker AC650G drive.