Parker AC690+ Drive Fault Codes & Diagnostic Guide

Complete trip code directory, alarm diagnostics, and step-by-step troubleshooting guide for the Parker Hannifin / SSD Drives AC690+ Integrator Series AC inverter. Search or filter through the complete diagnostic index below.

Integrator Series AC Drive Power: 0.75 to 1000 kW (1.0 to 1400 HP) Frames B through K
Power Range 0.75 – 1000 kW (1 – 1400 HP)
Supply Voltage 220–240V / 380–500V / 575–690V AC
Control Modes V/Hz, Sensorless Vector & Closed-Loop Vector
Operator Interface 6901 Keypad (MMI) / DSE Lite Software

Complete Parker AC690+ Drive Fault Code Directory

Use the search box in the table below to quickly find your trip code (e.g., type OVERVOLTAGE, DESAT, or DCHI).

Fault Code and MeaningCause and Remedy
OVERVOLTAGE

The drive internal dc link voltage is too high

Cause: High voltage conditions detected.


Remedy:

  • The supply voltage is too high.

  • Trying to decelerate a large inertia load too quickly.

  • The brake resistor is open circuit.


UNDERVOLTAGE

The drive internal dc link voltage is too low

Cause: Low voltage conditions detected.


Remedy:

  • Check if the supply voltage is too low.

  • Check if the supply has been lost.

  • Check if a supply phase is missing.


OVERCURRENT

The motor current being drawn from the drive is too high

Cause: Current limits exceeded due to load or wiring issues.


Remedy:

  • Trying to accelerate a large inertia load too quickly.

  • Trying to decelerate a large inertia load too quickly.

  • Application of shock load to motor.

  • Short circuit between motor phases.

  • Short circuit between motor phase and earth.

  • Motor output cables too long or too many parallel motors connected to the drive.

  • Fixed or auto boost levels are set too high.


HEATSINK

The drive heatsink temperature is too high

Cause: Thermal overload of the drive unit.


Remedy:

  • The ambient air temperature is too high.

  • Poor ventilation or spacing between drives.


EXTERNAL TRIP

User trip caused via control terminals

Cause: External signal missing.


Remedy:

  • +24V not present on external trip (e.g. terminal 19, Macro 1).


INPUT 1 BREAK

A signal break has been detected on analog input 1 (terminal 1)

Cause: 4-20mA signal loss detected.


Remedy:

  • Analog input is incorrectly configured for 4-20mA operation.

  • Break in external control wiring.


INPUT 2 BREAK

A signal break has been detected on analog input 2 (terminal 2)

Cause: 4-20mA signal loss detected.


Remedy:

  • Analog input is incorrectly configured for 4-20mA operation.

  • Break in external control wiring.


MOTOR STALLED

The motor has stalled (not rotating)

Cause: Motor unable to turn under load.


Remedy:

  • Motor loading too great.

  • Current limit level is set too low.

  • Stall trip duration is set too low.

  • Fixed or auto boost levels are set too high.


INVERSE TIME

The inverse time current limit is active

Cause: Prolonged overcurrent condition.


Remedy:

  • Motor loading is too great:

    • Motor current >150% for 60s in Constant duty.

    • Motor current >110% for 60s in Quadratic duty.



  • Fixed or autoboost levels are too high.


BRAKE RESISTOR

External dynamic braking resistor has been overloaded

Cause: Excessive energy dumped to resistor.


Remedy:

  • Trying to decelerate a large inertia load too quickly or too often.


BRAKE SWITCH

Internal dynamic braking switch has been overloaded

Cause: Excessive energy dumped to brake circuit.


Remedy:

  • Trying to decelerate a large inertia load too quickly or too often.


OP STATION

Keypad has been disconnected from drive whilst drive is running in local control

Cause: Communication loss with HMI.


Remedy:

  • Keypad accidentally disconnected from drive.


LOST COMMS

Communications Failure

Cause: Timeout detected.


Remedy:

  • COMMS TIMEOUT parameter set too short (refer to COMMS CONTROL menu at level 3).


CONTACTOR FBK

Contactor Feedback Error

Cause: Logic mismatch.


Remedy:

  • The CONTACTOR CLOSED input in the SEQUENCING LOGIC function block remained FALSE after a run command was issued.


SPEED FEEDBACK

Speed deviation detected

Cause: Control loop error.


Remedy:

  • SPEED ERROR > 50.00% for 10 seconds.


AMBIENT TEMP

The ambient temperature in the drive is too high

Cause: Environment too hot.


Remedy:

  • Check cooling and ventilation.

  • The ambient temperature in the drive is too high.


MOTOR OVERTEMP

The motor temperature is too high

Cause: Thermal overload of the motor.


Remedy:

  • Excessive load.

  • Motor voltage rating incorrect.

  • FIXED BOOST and/or AUTO BOOST set too high.

  • Prolonged operation of the motor at low speed without forced cooling.

  • Check setting of INVERT THERMIST parameter in I/O TRIPS menu at level 3.

  • Break in motor thermistor connection.


CURRENT LIMIT

Current exceeds 180% of stack rated current for 1 second

Cause: Shock loads.


Remedy:

  • Remove the cause of the shock load.


24V FAILURE

The 24V customer output has fallen below 17V

Cause: Overload on auxiliary supply.


Remedy:

  • 24V customer output is short circuited.

  • Excessive loading.


TRIP 19

Reserved

Cause: Reserved.


Remedy:

  • Reserved.


LOW SPEED OVER I

The motor is drawing too much current (>100%) at zero output frequency

Cause: Excessive magnetizing current.


Remedy:

  • FIXED BOOST and/or AUTO BOOST set too high (refer to FLUXING menu at level 4).


PHASE FAIL

One or more phases of the 3-phase supply is missing

Cause: Input power loss.


Remedy:

  • Check supply connections.

  • Check fuses.


ENCODER 1 FAULT

Encoder Error

Cause: Encoder module signal error.


Remedy:

  • The Error input on the Encoder TB is in the Error state.


DESAT (OVER I)

Instantaneous overcurrent

Cause: Hardware protection trip.


Remedy:

  • Refer to OVERCURRENT in this table.


VDC RIPPLE

The dc link ripple voltage is too high

Cause: Supply imbalance.


Remedy:

  • Check for a missing input phase.


BRAKE SHORT CCT

Brake resistor overcurrent

Cause: Low resistance.


Remedy:

  • Check resistance brake resistor value is greater than minimum allowed.


OVERSPEED

Speed limit exceeded

Cause: Speed feedback has exceeded the THRESHOLD for a period greater than DELAY.


Remedy:

  • Check speed loop tuning.

  • Check overspeed threshold parameters.


ANALOG INPUT ERR

Analog Input Signal Error

Cause: Signal out of range.


Remedy:

  • Analog input is incorrectly configured for 4-20mA operation.

  • Short circuit in external control wiring.

  • Extreme over-range of remote sensor.


TRIP 29

Reserved

Cause: Reserved.


Remedy:

  • Reserved.


TRIP 30

Reserved

Cause: Reserved.


Remedy:

  • Reserved.


UNKNOWN

An unknown trip

Cause: Unknown system error.


Remedy:

  • Refer to Parker SSD Drives.


MAX SPEED LOW

Autotune Error: MAX SPEED RPM limits speed to less than nameplate value

Cause: Configuration error during Autotune.


Remedy:

  • Increase the value of MAX SPEED RPM up to the nameplate rpm of the motor (as a minimum).

  • It may be reduced, if required, after the Autotune is complete.


MAINS VOLTS LOW

The mains input voltage is not sufficient to carry out the Autotune

Cause: Supply sag during test.


Remedy:

  • Re-try when the mains has recovered.


NOT AT SPEED

The motor was unable to reach the required speed to carry out the Autotune

Cause: Mechanical or Data issue.


Remedy:

  • Motor shaft not free to turn.

  • The motor data is incorrect.


MAG CURRENT FAIL

Unable to find suitable magnetising current

Cause: Motor data mismatch.


Remedy:

  • Check the motor data is correct, especially nameplate rpm and motor volts.

  • Check that the motor is correctly rated for the drive.


NEGATIVE SLIP F

Autotune has calculated a negative slip frequency

Cause: Data entry error.


Remedy:

  • Nameplate rpm may have been set to a value higher than the base speed of the motor.

  • Check nameplate rpm, base frequency, and pole pairs are correct.


TR TOO LARGE

Calculated rotor time constant too large

Cause: Calculation out of bounds.


Remedy:

  • Check the value of nameplate rpm.


TR TOO SMALL

Calculated rotor time constant too small

Cause: Calculation out of bounds.


Remedy:

  • Check the value of nameplate rpm.


MAX RPM DATA ERR

MAX SPEED RPM is set outside range of Autotune data

Cause: Data unavailable for new speed range.


Remedy:

  • Autotune gathers data up to 30% beyond "max speed rpm".

  • If MAX SPEED RPM is increased later, re-autotune with MAX SPEED RPM set to a higher value.


STACK TRIP

Drive hardware trip

Cause: Critical hardware protection.


Remedy:

  • The drive was unable to distinguish between an overcurrent/Dsat or overvoltage trip.


LEAKGE L TIMEOUT

Leakage inductance measurement timeout

Cause: Unable to achieve required test current.


Remedy:

  • Check that the motor is wired correctly.


POWER LOSS STOP

Power Loss Stop sequence ended

Cause: Sequence completion.


Remedy:

  • Power Loss Stop sequence has ramped Speed Setpoint to zero or timed out.


MOTR TURNING ERR

Motor moving at start of Autotune

Cause: Motor not stationary.


Remedy:

  • The motor must be stationary when starting the Autotune.


MOTR STALLED ERR

Motor unable to rotate during Autotune

Cause: Mechanical blockage.


Remedy:

  • The motor must be able to rotate during Autotune.


How to Clear & Reset Parker AC690+ Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the 6901 MMI keypad to acknowledge and clear the active trip display. If the drive is in Remote mode, switch to Local mode or ensure the run enable command is removed before resetting.
  2. Digital Input Reset (Terminal Strip): Apply a momentary 24V DC pulse to the digital input configured for REM TRIP RESET in the SEQUENCING function block (commonly assigned to digital input DIN4 or DIN5 on terminal block X03/X04).
  3. DSE Lite PC Tool: Connect your PC to the P3 serial programming port on the front of the drive using an RS232 / USB programming lead, launch Parker DSE Lite, and select “Acknowledge Trip” within the online diagnostics panel.
  4. Fieldbus Control Word: Transition the Trip Reset bit (Bit 3 in standard Eurotherm/Parker protocols or Bit 7 in Profibus DP/DeviceNet control word) from `0` to `1` via your network PLC.
  5. Mains Power Cycle: Disconnect the incoming 3-phase AC supply, wait at least 5 minutes for the internal capacitor bank to discharge completely until the keypad LCD display turns dark, and restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a certified CAT III or CAT IV multimeter (rated up to 1000V) that the intermediate DC bus voltage measures strictly below 50VDC across terminals [DC+] and [DC-] (or dynamic brake terminals DB+ and DB-) as well as motor output terminals M1/U, M2/V, and M3/W relative to safety earth before opening enclosure covers or servicing wiring on the Parker AC690+ drive.