Parker AC890PX Drive Fault Codes & Diagnostic Guide

Comprehensive fault code reference directory, trip alarm causes, and troubleshooting procedures for the Parker AC890PX high-power modular AC drive series. Search or filter through the complete trip directory below.

High-Power Modular Drive Power: 110 to 400 kW (150 to 600 HP) Integrated Safe Torque Off (SIL3/PLe)
Power Range 110 – 400 kW (150 – 600 HP)
Supply Voltage 380–500V / 500–690V AC
Control Modes V/Hz, Sensorless & Flux Vector
Operator Interface 6901 Keypad / DSE Lite Software

Complete Parker AC890PX Drive Fault Code Directory

Use the search box in the table below to quickly find your trip code (e.g., type OC, DCHI, DCLO, or HEATSINK).

Fault Code and MeaningCause and Remedy
OVERVOLTAGE

The drive internal dc link voltage is too high

Cause:

  • The supply voltage is too high.

  • Trying to decelerate a large inertia load too quickly.

  • The brake resistor is open circuit.




Remedy:

  • Check supply voltage.

  • Increase deceleration time or check braking resistor connection.


UNDERVOLTAGE

The drive internal dc link voltage is too low

Cause:

  • The supply voltage is too low.

  • The supply has been lost.

  • A supply phase is missing.




Remedy:

  • Check main power supply and fuses.


OVERCURRENT

The motor current being drawn from the drive is too high

Cause:

  • Trying to accelerate a large inertia load too quickly.

  • Trying to decelerate a large inertia load too quickly.

  • Application of shock load to motor.

  • Short circuit between motor phases or between motor phase and earth.

  • Motor output cables too long or too many parallel motors.

  • Fixed or auto boost levels are set too high.


HEATSINK

The drive heatsink temperature is too high

Cause:

  • The ambient air temperature is too high.

  • Poor ventilation or spacing between drives.




Remedy:

  • Check cooling fans and cabinet ventilation.


EXTERNAL TRIP

User trip caused via control terminals

Cause:

  • +24V not present on external trip (terminal X15/05).




Remedy:

  • Check setting of EXT TRIP MODE parameter.

  • Verify wiring at terminal X15/05.


INPUT 1 BREAK

I/O TRIPS:: INPUT 1 BREAK has gone True

Cause:

  • Input signal interruption detected.




Remedy:

  • Check configuration to determine source of signal.


INPUT 2 BREAK

I/O TRIPS:: INPUT 2 BREAK has gone True

Cause:

  • Input signal interruption detected.




Remedy:

  • Check configuration to determine source of signal.


MOTOR STALLED

The motor has stalled (not rotating)

Cause:

  • Motor loading too great.

  • Current limit level is set too low.

  • Stall trip duration is set too low.

  • Fixed or auto boost levels are set too high.


INVERSE TIME

The inverse time current limit is active

Cause:

  • Motor loading is too great.

  • Fixed or autoboost levels are too high (Full Load Current = 150% for 60 seconds).


BRAKE RESISTOR

External dynamic braking resistor has been overloaded

Cause:

  • Trying to decelerate a large inertia load too quickly or too often.


BRAKE SWITCH

Internal dynamic braking switch has been overloaded

Cause:

  • Trying to decelerate a large inertia load too quickly or too often.


OP STATION

Keypad has been disconnected from drive whilst drive is running in local control

Cause:

  • Keypad accidentally disconnected from drive.




Remedy:

  • Reconnect Keypad.


COMMS BREAK

Communications failure

Cause:

  • COMMS BREAK parameter set to True (refer to I/O TRIPS menu at level 3).


CONTACTOR FBK

Contactor Feedback failure

Cause:

  • The CONTACTOR CLOSED input in the SEQUENCING LOGIC function block remained FALSE after a run command was issued.


SPEED FEEDBACK

Speed deviation detected

Cause:

  • SPEED ERROR > 50.00% for 10 seconds.


AMBIENT TEMP

The ambient temperature in the drive is too high

Cause:

  • Environmental temperature exceeds rating.




Remedy:

  • Improve cooling/ventilation.


MOTOR OVERTEMP

The motor temperature is too high

Cause:

  • Excessive load.

  • Motor voltage rating incorrect.

  • FIXED BOOST and/or AUTO BOOST set too high.

  • Prolonged operation of the motor at low speed without forced cooling.

  • Break in motor thermistor connection.




Remedy:

  • Check setting of INVERT THERMIST parameter in I/O TRIPS menu at level 3.


CURRENT LIMIT

V/Hz mode only: Current exceeds limit

Cause:

  • Current exceeds 180% of induction stack rated current for 1 second.

  • Caused by shock loads.




Remedy:

  • Remove the cause of the shock load.


24V FAILURE

The 24V customer output has fallen below 17V

Cause:

  • 24V customer output is short circuited.

  • Excessive loading.


LOW SPEED OVER I

Motor drawing too much current at zero speed

Cause:

  • The motor is drawing too much current (>100%) at zero output frequency.

  • FIXED BOOST and/or AUTO BOOST set too high.




Remedy:

  • Refer to FLUXING menu at level 3.


PHASE FAIL

Input phase loss

Cause:

  • One or more input phases not present.


FBK ENCODER FAIL

Encoder fault

Cause:

  • Encoder fault - this trip is not functional in software version 1.x.


DESAT (OVER I)

Instantaneous overcurrent

Cause:

  • Refer to OVERCURRENT in this table.


VDC RIPPLE

DC link ripple voltage too high

Cause:

  • High DC ripple detected.




Remedy:

  • Check for a missing input phase.


BRAKE SHORT CCT

Brake resistor overcurrent

Cause:

  • Resistance value too low or short circuit.




Remedy:

  • Check brake resistance is not less than minimum value allowed.

  • Check wiring and brake resistor for earth faults.


OVERSPEED

Speed feedback > 150% for 0.1 seconds

Cause:

  • Load overhauling the motor.

  • Control loop tuning issues.


ANALOG INPUT ERR

4-20mA analog input current > 22mA

Cause:

  • High current on input.




Remedy:

  • Check wiring and source signal (could damage the input circuit).


INT DB RESISTOR

Braking mode set to INTERNAL

Cause:

  • Incorrect configuration for required braking.




Remedy:

  • Set to EXTERNAL and connect an External Braking Resistor if braking is required.


UNKNOWN

An unknown trip

Remedy:

  • Refer to Parker SSD Drives.


OTHER

Multiple trips or high value trip

Cause:

  • One or more trips listed below have occurred with a Value greater than 32.


MAX SPEED LOW

Autotune error: Max speed limit too low

Cause:

  • MAX SPEED RPM limits the speed to less than nameplate value during Autotune.




Remedy:

  • Increase the value of MAX SPEED RPM up to the nameplate rpm of the motor (as a minimum).

  • It may be reduced, if required, after the Autotune is complete.


MAINS VOLTS LOW

Autotune error: Mains voltage insufficient

Cause:

  • The mains input voltage is not sufficient to carry out the Autotune.




Remedy:

  • Re-try when the mains has recovered.


NOT AT SPEED

Autotune error: Motor unable to reach required speed

Cause:

  • Motor shaft not free to turn.

  • The motor data is incorrect.


MAG CURRENT FAIL

Autotune error: Magnetising current failure

Cause:

  • It was not possible to find a suitable value of magnetising current.




Remedy:

  • Check the motor data is correct, especially nameplate rpm and motor volts.

  • Check that the motor is correctly rated for the drive.


NEGATIVE SLIP F

Autotune error: Negative slip frequency calculated

Cause:

  • Nameplate rpm may have been set to a value higher than the base speed of the motor.




Remedy:

  • Check nameplate rpm, base frequency, and pole pairs are correct.


TR TOO LARGE

Autotune error: Rotor time constant too large

Cause:

  • Calculated value is invalid.




Remedy:

  • Check the value of nameplate rpm.


TR TOO SMALL

Autotune error: Rotor time constant too small

Cause:

  • Calculated value is invalid.




Remedy:

  • Check the value of nameplate rpm.


MAX RPM DATA ERR

Autotune data missing for speed range

Cause:

  • MAX SPEED RPM is set to a value outside the range for which Autotune has gathered data.

  • Drive has no data for this new operating area.




Remedy:

  • Re-autotune with MAX SPEED RPM set to a higher value.


STACK TRIP

Drive hardware trip

Cause:

  • The drive was unable to distinguish between an overcurrent/desat or overvoltage trip.


LEAKGE L TIMEOUT

Leakage inductance measurement failed

Cause:

  • It has not been possible to achieve the required level of test current.




Remedy:

  • Check that the motor is wired correctly.


POWER LOSS STOP

Power Loss Stop sequence ended

Cause:

  • Power Loss Stop sequence has ramped Speed Setpoint to zero or timed out.


MOTR TURNING ERR

Autotune error: Motor moving

Cause:

  • The motor must be stationary when starting the Autotune.


MOTR STALLED ERR

Autotune error: Motor stalled

Cause:

  • The motor must be able to rotate during Autotune.


AT TORQ LIM ERR

Autotune error: Torque limit

Cause:

  • The motor is in torque limit during Autotune.


FBK ENCODR CAL

Absolute position error

Cause:

  • The drive has failed to set absolute position.




Remedy:

  • Check the encoder supports absolute position.

  • Check that the encoder is wired correctly.


OUTPUT GBX ERROR

Gearbox configuration error

Cause:

  • A non-unity output gearbox is not supported if the encoder direction is reversed.


APP HALTED

Application halted

Cause:

  • The application has been halted by the DSE Configuration Tool.


APP ERROR

Application error

Cause:

  • The application has ceased execution due to an error.


FIRMWARE ERROR

Firmware stopped

Cause:

  • The firmware in the drive has stopped executing.


RESOLVER ERROR

See function block description

Cause:

  • Motor current is too high.


I2T MOTOR TRIP

See function block description

Cause:

  • Motor is undersized.


SAFE TORQUE OFF

STO Active

Cause:

  • Safe Torque Off function activated.


REF ENCODER CAL

The drive has failed to set absolute position

Remedy:

  • Check the encoder supports absolute position.

  • Check that the encoder is wired correctly.


DRIVE CONFIG ERR

Drive configuration error

Cause:

  • The configuration defined in DRIVE CONFIG doesn't match the actual drive configuration.


CURRENT BALANCE

Poor current sharing in CD Module

Cause:

  • A CD Module hardware fault.


SYSTEM VOLTS

Control and fan supply volts low on CD Module

Cause:

  • Supply overloaded, fan shorted or low voltage supply wiring fault.


LEFT FAN

Left fan fail on CD Module

Cause:

  • Fan not rotating.


RIGHT FAN

Right fan fail on CD Module

Cause:

  • Fan not rotating.


CS PHASE LOSS

3 phase/1 phase power supply loss

Cause:

  • Complete 3 phase power supply loss, or loss of a single phase.


CS TEMPERATURE

CS/CP Module overtemperature warning

Cause:

  • Warning that the CS Module is running too hot.

  • Warning that the CP Module is running too hot.


CS BRIDGE

CS Module overcurrent/ overtemperature trip

Cause:

  • The current being drawn from the CS Module is too high.

  • The CS Module is running too hot.

  • The CP Module is running too hot.


EARTH FAULT

Current in phases U, V & W ≠ 0

Cause:

  • Currents do not sum to zero. One phase may have a short to earth.


STACK MISMATCH

U, V & W CD Modules are not the same build

Remedy:

  • Check U, V & W CD Modules are the same voltage/power rating.


CM OVERTEMP

Control Module heatsink too hot

Cause:

  • Shorted/ fan supply overloaded.


How to Clear & Reset Parker AC890PX Drive Faults

  1. Keypad Reset: Press the red Stop / Reset (E) key on the 6901 Operator Keypad to acknowledge and clear the active trip once the underlying fault condition is resolved.
  2. Digital Input Reset: If configured in the control block via DSE software (SEQ & REFERENCING :: REMOTE TRIP RESET), pulse the assigned digital input terminal (e.g., DIN4 or DIN5) to clear trips remotely.
  3. DSE Lite PC Tool: Connect your PC to the drive via serial or USB interface using Parker DSE Lite or DSE890 software, access the diagnostic monitoring window, and execute “Trip Reset”.
  4. Fieldbus Control Word: Write Bit 7 (Fault Reset) from logic 0 to logic 1 in the control word via Profibus, DeviceNet, Modbus, or Ethernet communication options.
  5. Power Cycle: Disconnect main AC line input power, wait at least 5 to 10 minutes until internal DC link capacitors discharge completely and all indicator LEDs turn off, then re-energize the drive.
⚠️ High-Voltage Electrical Safety Warning: The Parker AC890PX is a high-power modular drive system operating with lethal DC bus voltages. Always verify with an IEC 61010 CAT III/IV digital multimeter that DC bus voltage measures strictly below 50VDC across terminals [DC+] and [DC-] before inspecting power modules, touching output terminals U, V, and W, or performing maintenance.