Parker DC590+ Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker SSD DC590+ (590 Plus) Integrator Series 2 digital DC drive. Search or filter through the complete fault code directory below.

Digital DC Motor Drive Current: 15 to 2700 A (1 to 2000 HP) Integrator Series 2 Architecture
Current Range 15 – 2700 A (1 – 2000 HP)
Supply Voltage 110–690V AC (3-Phase)
Feedback Modes Armature, Tach & Encoder
Operator Interface 6901 Keypad & DSE Lite PC Tool

Complete Parker DC590+ Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OVERSPEED, FIELD FAIL, or 3 PHASE FAIL).

Fault Code and MeaningCause and Remedy
OVERSPEED

Motor overspeed - the speed feedback signal has exceeded 125% of rated speed.

Cause:

Badly adjusted speed loop (alarm only operates with encoder or armature volts feedback selected).



Remedy:

  • Check speed loop tuning.

  • Note: Alarm time delay is 50 milliseconds.


MISSING PULSE

A missing pulse from the 6-pulse armature current waveform.

Cause:

Firing plug failure or Connection failure.

Note: This trip is only enabled when motor loading exceeds 1.5 times the DISCONTINUOUS parameter value.



Remedy:

  • Check firing circuit connector problems.

  • We recommend fusing the armature circuit if regenerative operation is intended.

  • Note: Alarm time delay is 60 seconds.


FIELD OVER I

The motor field current has exceeded 120% of the calibrated value.

Cause:

External field has incorrect supply phases applied.



Remedy:

  • Check external field supply phases.

  • Note: Alarm only operates with field current control mode selected.


HEATSINK TRIP

The Drive heatsink temperature is too high.

Cause:

The ambient air temperature is too high; Poor ventilation or spacing between Drives; Blocked ventilation slots; Clogged air filters; Excessive armature current.



Remedy:

  • Check for fan failure or wrong rotation.

  • Check fuse on power board.

  • Clean air filters and ventilation slots.

  • Check nominal armature current against calibration.

  • Allow the stack to cool in order to re-start the Drive.


THERMISTOR

The motor temperature is too high.

Cause:

Inadequate ventilation; Blower failure; Excessive armature current.



Remedy:

  • Check blower direction and air filters.

  • Check nominal armature current on nameplate against current calibration.

  • Allow the motor to cool in order to re-start the Drive.


OVER VOLTS (VA)

Motor armature voltage has exceeded 120% of rated volts.

Cause:

Loose armature connection; Badly adjusted field voltage setting; Badly adjusted field current loop; Badly adjusted field-weakening bemf loop; Badly adjusted speed loop.



Remedy:

  • Check armature connections.

  • Adjust relevant loops (field voltage, field current, bemf, speed).


SPEED FEEDBACK

Difference between speed feedback and armature voltage feedback is greater than SPDFBK ALM LEVEL.

Cause:

Analog tacho feedback polarity incorrect; ENCODER SIGN parameter polarity incorrect; Disconnection of wiring (including fibre optics); Tachogenerator failure/coupling failure.



Remedy:

  • Check wiring and polarity (terminals G3 and G4).

  • Check fibre optic cables.

  • Check tachogenerator and coupling.

  • Ensure armature voltage calibration is reduced when running at reduced field currents.


ENCODER FAILED

No speed feedback signal.

Cause:

SPEED FBK SELECT parameter is set to ENCODER but an optional Encoder board is not fitted; Damaged fibre optic cable.



Remedy:

  • Check fibre optic cable for damage, bend radius, operating length.

  • Check cable and connections on wire-ended encoder.


FIELD FAIL

Field current is less than 6% (Current Control) or 50mA (Voltage Control).

Cause:

Open circuit motor field; Faulty operation of field controller; Missing 3-phase supply for synchronization.



Remedy:

  • Check connection and measure field resistance.

  • Check connections FL1 & FL2 for line-to-line voltage.

  • For permanent magnet motors, set FIELD ENABLE parameter to DISABLED.


3-PHASE FAILED

3-phase supply failure.

Cause:

Total failure of supply or missing phase; Blown fuses (thyristor stack or power chassis).



Remedy:

  • Check supply to the controller.

  • Check high-speed thyristor stack protection fuses.

  • Check mains voltage of the Drive (wrong unit/controller voltage).


PHASE LOCK

Supply frequency is outside limits 45 - 65Hz.

Cause:

Supply frequency fault; Synchronization errors caused by distorted supply.



Remedy:

  • Check supply frequency.


5703 RCV ERROR

Invalid data received via P3 port from another Drive.

Cause:

Communication error.



Remedy:

  • Note: Alarm only operates when MODE parameter is set to 5703 SLAVE.


STALL TRIP

Motor stationary, current exceeded STALL THRESHOLD for longer than STALL TRIP DELAY.

Cause:

Mechanical stall or load issue.



Remedy:

  • Check motor load.

  • Note: Alarm only operates when the STALL TRIP parameter is enabled.


OVER I TRIP

Current feedback value has exceeded 280% of rated current.

Cause:

Motor armature windings failure; Badly tuned current loop; Faulty Drive.



Remedy:

  • Check insulation resistance.

  • Check current loop tuning.

  • Refer to Parker SSD Drives for faulty drive.


ACCTS FAILED

AC current transformer plug connection to Drive power board missing.

Cause:

Plug disconnected; Load imbalance (Frame 5).



Remedy:

  • Check armature current transformer plug for correct installation.


AUTOTUNE ERROR

Error encountered during Autotune process.

Cause:

Motor shaft rotating; Open-circuit wiring; Discontinuous current boundary too high; Large supply imbalance; Hardware fault.



Remedy:

  • Ensure motor shaft is stationary.

  • Check drive to armature wiring.

  • Check supply voltage balance.


AUTOTUNE ABORT

The Autotune sequence has been aborted.

Cause:

Coast Stop/Program Stop/Enable disabled; AUTOTUNE parameter reset; Timeout (2 mins).



Remedy:

  • Check terminal inputs during Autotune.

  • Restart Autotune sequence.


SEQ PRE READY

Coding not present.

Cause:

Hardware configuration issue.



Remedy:

  • Replace power board or chassis.


CONTACTOR DELAY

The internal auxiliary 3-phase contactor failed to close.

Cause:

Calibration issue.



Remedy:

  • Check the position of the Calibration Scaling Switch.


EXTERNAL TRIP

Customer alarm! Trip operates if input open or high impedance.

Cause:

Device not wired to drive or device open circuited.



Remedy:

  • Check C1 to C2 connections to drive.

  • Connect C1 to C2 if customer device not fitted.


REMOTE TRIP

Remote Trip flag set.

Cause:

REM. SEQUENCE parameter Remote Trip flag set to zero.



Remedy:

  • Check Remote Sequence parameters.


ENABLE LOW

Local Mode run with Enable input low.

Cause:

Enable input is low while trying to run in Local Mode.



Remedy:

  • Check Enable input signal.


SEQUENCING

Internal sequencing error.

Cause:

Internal software/hardware error.



Remedy:

  • Contact Parker SSD Drives.


COMMS TIMEOUT

Remote comms timeout.

Cause:

Communication interruption.



Remedy:

  • See COMMS TIMEOUT parameter in the SEQUENCING function block.


CONFIG ENABLED

The drive was requested to start whilst in Configuration mode.

Cause:

Drive is in Configuration mode.



Remedy:

  • Exit Configuration mode before starting.


CALIBRATION FAIL

Signal calibration fault.

Cause:

Hardware failure suspected.



Remedy:

  • Power unit off and on.

  • If problem persists, contact Parker SSD Drives.


NO OP STATION

Keypad has been disconnected from Drive whilst Drive is running in local control.

Cause:

Keypad disconnection.



Remedy:

  • Reconnect Keypad.


AUX SUPPLY

Auxiliary supply failure.

Cause:

Missing or unstable supply.



Remedy:

  • Check auxiliary supply and/or mains input.


COMMS FAULT CODE x

Keypad or remote cable fault.

Cause:

Keypad faulty; Remote cable to keypad faulty; Drive firmware not running.



Remedy:

  • Check keypad and cables.


CRITICAL ERROR

System Critical Error.

Cause:

Internal failure.



Remedy:

  • Contact Parker SSD Drives.


(EEPROM) CHECKSUM FAIL

Parameters not saved, or are corrupted.

Cause:

Corrupted UDP file loaded.



Remedy:

  • Press the E key and perform a PARAMETER SAVE.

  • The Drive will be returned to its factory default values.


LANGUAGE CHECKSUM FAIL

Incorrect language selected, or corrupted.

Cause:

Corrupted UDP file loaded.



Remedy:

  • Press the E key and reload the correct language or de-select the second language.


How to Clear & Reset Parker DC590+ Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the 6901 or 6511 operator keypad. If operating via remote terminal sequence, remove the active Start/Run permissive before attempting a reset.
  2. Digital Input Reset (Terminal Control): If mapped in the Sequencing Logic (Trip Reset) block, apply a momentary 24V DC pulse to the assigned digital input terminal (e.g., DIN4 / Terminal C6).
  3. DSE Lite PC Software: Connect your PC to the P3 serial communication port or USB converter, open Parker DSE (Drive System Explorer) Lite software, and issue a “Trip Reset” command from the diagnostics window.
  4. Fieldbus Control Word: Write a `0` to `1` transition on Bit 7 (Fault/Trip Reset) in the Command Word via Profibus, DeviceNet, CANopen, Ethernet/IP, or Modbus RTU communications.
  5. Power Cycle: Switch off the incoming 3-phase AC supply and auxiliary control power, wait at least 3 minutes until the keypad display and LED indicators are completely unlit, then re-energize the unit.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter capable of 1000V DC that line supply and armature voltage measure strictly 0V across armature terminals [A+] and [A-] as well as field terminals [F+] and [F-] before opening terminal enclosures, inspecting thyristor / SCR stacks, or touching DC motor leads on the Parker DC590+ drive.