Parker DC590PR Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker DC590PR 4-quadrant regenerative digital DC drive series. Search or filter through the complete fault code directory below.
Current Rating
15 – 165 A (Frames 1 & 2)
Supply Voltage
110–220V / 220–500V AC (3-Ph)
Control Modes
4Q Regenerative Speed & Torque
Operator Interface
6901 Keypad / DSE Lite PC Tool
Complete Parker DC590PR Drive Fault Code Directory
Use the search box in the table below to quickly find your trip code (e.g., type OVER I TRIP, 3-PHASE FAILED, FIELD FAIL, or MISSING PULSE).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OVERSPEED Motor overspeed - the speed feedback signal has exceeded 125% of rated speed. | Cause:
Remedy:
|
| MISSING PULSE A missing pulse from the 6-pulse armature current waveform. (Only enabled when motor loading exceeds 1.5 times the DISCONTINUOUS parameter). | Cause:
Remedy:
|
| FIELD OVER I The motor field current has exceeded 120% of the calibrated value. | Cause:
Remedy:
|
| HEATSINK TRIP The Drive heatsink temperature is too high. | Cause:
Remedy:
|
| THERMISTOR The motor temperature is too high. | Cause:
Remedy:
|
| OVER VOLTS (VA) Motor armature voltage has exceeded 120% of rated volts. | Cause:
Remedy:
|
| SPEED FEEDBACK Difference between speed feedback and armature voltage feedback is greater than SPDFBK ALM LEVEL. | Cause:
Remedy:
|
| ENCODER FAILED No speed feedback signal. | Cause:
Remedy:
|
| FIELD FAIL Field current is less than 6% (Current Control mode) or 50mA (Voltage Control mode). | Cause:
Remedy:
|
| 3-PHASE FAILED 3-phase supply failure. | Cause:
Remedy:
|
| PHASE LOCK Supply frequency is outside the frequency band limits 45 - 65Hz. | Cause:
Remedy:
|
| 5703 RCV ERROR Invalid data received via P3 port from another Drive. | Cause:
Remedy:
|
| STALL TRIP Motor stationary with current exceeding STALL THRESHOLD for longer than delay. | Cause:
Remedy:
|
| OVER I TRIP Current feedback value has exceeded 280% of rated current. | Cause:
Remedy:
|
| ACCTS FAILED AC current transformer plug connection to Drive power board missing. | Cause:
Remedy:
|
| AUTOTUNE ERROR Error encountered during Autotune process (Speed > 20% or Field > 6%). | Cause:
Remedy:
|
| AUTOTUNE ABORT The Autotune sequence has been aborted. | Cause:
Remedy:
|
| SEQ PRE READY Coding not present. | Cause:
Remedy:
|
| CONTACTOR DELAY The internal auxiliary 3-phase contactor failed to close. | Cause:
Remedy:
|
| EXTERNAL TRIP Customer alarm! (Trip operates if input open or high impedance). | Cause:
Remedy:
|
| REMOTE TRIP Remote trip activated. | Cause:
Remedy:
|
| ENABLE LOW Enable input is low. | Cause:
Remedy:
|
| SEQUENCING Internal sequencing error. | Cause:
Remedy:
|
| COMMS TIMEOUT Remote comms timeout. | Cause:
Remedy:
|
| CONFIG ENABLED Drive requested to start whilst in Configuration mode. | Cause:
Remedy:
|
| CALIBRATION FAIL Signal calibration fault. | Cause:
Remedy:
|
| NO OP STATION Keypad disconnected during local control. | Cause:
Remedy:
|
| AUX SUPPLY Auxiliary supply failure. | Cause:
Remedy:
|
| COMMS FAULT CODE x Communication hardware fault. | Cause:
Remedy:
|
| CRITICAL ERROR xxxx::xxxxxxxx | Cause:
Remedy:
|
| (EEPROM) CHECKSUM FAIL Parameters not saved, or are corrupted. | Cause:
Remedy:
|
| LANGUAGE CHECKSUM FAIL Incorrect language selected, or corrupted. | Cause:
Remedy:
|
How to Clear & Reset Parker DC590PR Drive Faults
- Keypad Reset: Press the red STOP / RESET key on the front 6901 alpha-numeric operator station to acknowledge and clear latched trips once the active fault condition has resolved.
- Digital Input Reset (Terminal C4): Apply a momentary 24V DC pulse to the assigned Remote Trip Reset digital input terminal (default terminal C4 or configured via
SEQ & REFERENCING :: REMOTE TRIP RESET). - DSE Lite PC Software: Connect a PC via the front P3 serial diagnostic port or USB adapter, open Parker DSE Lite, navigate to the active drive diagnostics window, and click “Trip Reset”.
- Fieldbus Control Word: Write Bit 7 (Trip Reset) from logic `0` to logic `1` in the Control Word via Profibus, DeviceNet, CANopen, Ethernet, or Modbus TechBox options.
- Power Cycle: Disconnect both the auxiliary control supply and main incoming 3-phase AC line power, wait 5 minutes for internal filter circuits and suppressors to de-energize completely, then restore power.
⚠️ High-Voltage Electrical Safety Warning:
The Parker DC590PR controls high DC voltages and inductive stored energy. Always disconnect and lock out incoming 3-phase AC power (L1, L2, L3) and auxiliary supplies. Verify with a calibrated digital multimeter that 0V DC is present across armature terminals [A+] and [A-], as well as field terminals [F+] and [F-], before touching thyristor modules, motor brushgear, or power wiring.