Parker TPD-M Drive Fault Codes & Diagnostic Guide

Complete multi-axis fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Parker TPD-M modular servo drive series. Search or filter through the complete diagnostic directory below.

Multi-Axis Servo Drive System Output: Up to 20 kVA (1 to 3 Axes per Module) Common DC Bus Architecture & STO
Current / Power Up to 20 kVA (2A – 30A per Axis)
Supply Voltage 325 – 680 VDC (Common Bus)
Control Modes Multi-Axis Position, Speed & Torque
Operator Interface MotionWiz Software & 7-Segment LED

Complete Parker TPD-M Drive Fault Code Directory

Use the search box in the table below to quickly find your alarm code (e.g., type 1 for Overvoltage, 3 for Overcurrent, Feedback, or Resolver).

Fault Code and MeaningCause and Remedy
0

No alarm

Cause: Standard operation status.


Remedy:

  • If Pr24 is not 0, see the "SUB Alarms table" below.


1

DC circuit overvoltage

Cause: Voltage on DC bus is too high.


Remedy:

  • Check the three-phase power line (max 480V + 10%).

  • Check the brake circuit and the braking resistor.


2

DC circuit undervoltage

Cause: Voltage on DC bus is too low.


Remedy:

  • Check the three-phase power line.


3

Overcurrent

Cause: Current exceeds limits, potential short circuit.


Remedy:

  • If Pr24=0 (Overcurrent): Check motor connections and any phase-phase or phase-ground short-circuits.

  • Check the motor data.

  • If Pr24 is not 0: See the "SUB Alarms table" section.


4

FBK error (resolver or encoder)

Cause: Feedback device signal failure.


Remedy:

  • Check the connections of the speed loop and the connectors on both sides (drive-motor).

  • Check the feedback parameters.


5

PTC motor alarm

Cause: Motor temperature sensor issue.


Remedy:

  • Check the PTC connection cable.

  • Check parameters Pr33 (Inom) and Pr19 (Ipeak).


6

Power module overtemperature

Cause: Drive module is overheating.


Remedy:

  • Check the cooling fans and for any restrictions to air flow.

  • Check the braking cycle.

  • Check the ambient temperature in the electric cabinet and outside the cabinet.


7

External alarm

Cause: Triggered by external input.


Remedy:

  • Depends on the application (b41.7 – see Pico PLC program).


8

Auxiliary alarm

Cause: Triggered by auxiliary condition.


Remedy:

  • Depends on the application (b41.8 – see Pico PLC program).


10 (*)

Check sum pico-PLC

Cause: Parameter/Programming checksum error.


Remedy:

  • Set and save default parameters.

  • Switch off and on again the drive.

  • Repeat programming.


11 (*)

Check sum parameters

Cause: Parameter checksum error.


Remedy:

  • Set and save default parameters.

  • Switch off and on again the drive.

  • Repeat programming.


12

Signature firmware

Cause: The signature is not installed.


Remedy:

  • Internal issue; send to repair.


13

CANopen DS402 abort connection

Cause: Communication abort.


Remedy:

  • Check the connections.


15

Default parameters

Cause: Parameters reset or corrupt.


Remedy:

  • Set and save default parameters.

  • Switch off and on again the drive.

  • Repeat programming.


16

CANopen missing sync

Cause: Synchronization signal lost.


Remedy:

  • Check the connections.


17 (**)

Hardware alarm

Cause: Internal hardware damage or fault.


Remedy:

  • Internal damage, send to repair.

  • Refer to the "SUB Alarms table" below for specific code.


22

Ambient over temperature

Cause: The ambient temperature in the electric cabinet is excessive (>45°C).


Remedy:

  • Check the cooling fans.

  • Check for any restrictions to air flow.


24

PSU alarm

Cause: Power Supply Unit issue.


Remedy:

  • See the "SUB Alarms table".


25 (**)

Speed loop FBK initialization error

Cause: Issue during feedback initialization.


Remedy:

  • Check the speed FBK settings.

  • Check the speed FBK connection.

  • Ensure motor shaft is not in movement during start-up.

  • The encoder is not phased. See the procedure.


27

Overloads digital outputs

Cause: Excessive load on outputs.


Remedy:

  • Check the load of the digital outputs.


31

Communication error

Cause: Field-bus issue.


Remedy:

  • Check the field-bus connection.


TripP.x

Hardware broken

Cause: Hardware failure (x is a number).


Remedy:

  • Internal damage, send to repair.


I²T

Current limit (I²T)

Cause: Drive entered I²T mode due to overload (current required > current supplied).


Remedy:

  • Check wiring between drive and motor (ensure no inverted phases).

  • Take special care with motors where the connector is replaced by a terminal block (easy to mistake).

  • Adhere strictly to wiring diagrams.

  • Check mechanical dimensioning.


Pr23: 0 / Pr24: 4

Serial line error

Cause: Connection issue.


Remedy:

  • Insert the terminal plug-in.


Pr23: 0 / Pr24: 5

Power supply not 3-phases

Cause: Phase loss.


Remedy:

  • Check the main supply.


Pr23: 3 / Pr24: 1

Hardware from FPGA

Cause: Internal hardware signal.


Remedy:

  • (Contact technical support / Check hardware).


Pr23: 3 / Pr24: 2

I2t maximum reached

Cause: Overload threshold reached.


Remedy:

  • Check load and cooling.


Pr23: 3 / Pr24: 3

Stall status of V/F

Cause: Motor stalled in V/F mode.


Remedy:

  • Check motor load and mechanics.


Pr23: 17 / Pr24: 1

Different number of axes

Cause: Configuration mismatch.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 2

Number of axes configuration

Cause: Configuration error.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 3

Feedback configuration

Cause: Configuration error.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 4

ADC on FPGA error

Cause: Conversion error on FPGA.


Remedy:

  • Switch off the drive.

  • Wait one minute before restarting the drive.


Pr23: 17 / Pr24: 5

EEprom error

Cause: Memory failure.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 6

FPGA fault

Cause: Processor fault.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 7

EEprom checksum error

Cause: Memory data corruption.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 8

NIOS SDRAM checksum error

Cause: RAM data corruption.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 9

NIOS RAM checksum error

Cause: RAM data corruption.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 10

FPGA blocked

Cause: Processor freeze.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 11

FPGA watchdog alarm

Cause: Watchdog timer expiration.


Remedy:

  • Internal damage, send to repair.


Pr23: 17 / Pr24: 12

NIOS watchdog alarm

Cause: Watchdog timer expiration.


Remedy:

  • Internal damage, send to repair.


How to Clear & Reset Parker TPD-M Drive Faults

  1. MotionWiz PC Software: Connect your PC via the USB or front diagnostic serial port, launch the Parker MotionWiz configuration utility, navigate to the tripped axis diagnostic page, and execute the “Fault Reset” command.
  2. Fieldbus Network Reset: Toggle Bit 7 (Fault Reset) in the standard CiA 402 / DS402 Control Word from logic `0` to logic `1` across your EtherCAT (CoE), CANopen, or PROFINET network interface.
  3. Digital Input Reset: If programmed via parameter configuration or internal PLC logic on the digital I/O connector (X12/X13), pulse the assigned digital input terminal from 0V to 24V DC to clear latched faults.
  4. Internal PLC Bit: If using internal motion code, toggle the system reset command bit (e.g., bit b99.12) within the application script to acknowledge active axis alarms.
  5. Common DC Bus Power Cycle: Power down the main AC supply feeding the common DC bus power supply module. Wait at least 5 to 10 minutes for all shared DC bus discharge lamps to extinguish completely before restoring mains power.
⚠️ High-Voltage Electrical Safety Warning: The Parker TPD-M operates on a centralized high-voltage DC bus system (325–680 VDC). Extremely lethal electrical energy remains stored across shared capacitor banks after switching off AC line power. Always measure with a calibrated multimeter to verify DC voltage is strictly below 50VDC across the DC bus bars (+BUS and -BUS) before inspecting motor power leads, feedback connectors, or replacing axis modules.