Parker TWIN-N & SPD-N Drive Fault Codes & Diagnostic Guide
Complete trip alarm reference table, numeric and Er error code directory, and step-by-step troubleshooting procedures for Parker SBC TWIN-N (dual-axis) and SPD-N (single-axis) digital servo drives. Search or filter through the complete diagnostic index below.
Power Rating
1.4 – 11.2 kVA (2A – 16A/axis)
Supply Voltage
200–240V (1/3-Ph) / 380–480V (3-Ph)
Control Modes
Position, Speed, Electronic Cam & picoPLC
Operator Interface
7-Segment Keypad & MotionWiz Software
Complete Parker TWIN-N & SPD-N Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Er 01, Overcurrent, or Resolver).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 0 No alarm | Cause: Normal operation. Remedy:
|
| 1 DC circuit overvoltage | Cause: Voltage in the DC circuit has exceeded limits. Remedy:
|
| 2 DC circuit undervoltage | Cause: Voltage in the DC circuit is too low. Remedy:
|
| 3 Overcurrent | Cause: Excessive current detected. Remedy:
|
| 4 FBK error (resolver or encoder) | Cause: Feedback loop signal failure. Remedy:
|
| 5 PTC motor alarm | Cause: Motor temperature sensor issue or overheat. Remedy:
|
| 6 Power module overtemperature | Cause: Thermal limit reached in power module. Remedy:
|
| 7 External alarm | Cause: Triggered by external input. Remedy:
|
| 8 Auxiliary alarm | Cause: Triggered by auxiliary condition. Remedy:
|
| 10 (*) PLC check sum | Cause: Data integrity error in PLC program. Remedy:
(*) Reset only after default values have been loaded and saved. |
| 11 (*) Parameter check sum | Cause: Data integrity error in parameters. Remedy:
(*) Reset only after default values have been loaded and saved. |
| 14 Overload braking resistor | Cause: Braking resistor duty cycle exceeded. Remedy:
|
| 15 Default parameters | Cause: Parameters need reset. Remedy:
|
| 17 (**) Hardware broken | Cause: Internal hardware failure. Remedy:
(**) Can be only reset at the next power on. |
| 22 Ambient over temperature | Cause: The ambient temperature in the electric cabinet is excessive (>45°C). Remedy:
|
| 24 Braking dynamic protection | Cause: Short-circuit in braking resistance. Remedy:
|
| 25 (**) Speed loop FBK initialization error | Cause: Feedback initialization failure. Remedy:
(**) Can be only reset at the next power on. |
| 30 EEPROM not recognized | Cause: Memory hardware failure. Remedy:
|
| TripP.x (where x is a number) Hardware broken | Cause: Internal hardware failure. Remedy:
|
| I²T Current limit (I²T) | Cause: The drive goes in I²T mode due to an overload (the current required is more than the current that can be supplied). (Display shows decimal points on all characters) Remedy:
|
How to Clear & Reset Parker TWIN-N & SPD-N Drive Faults
- Keypad Reset: On the front operator panel, use the key combination to navigate and write bit b99.10 to `0` or execute the reset command once the abnormal operating condition has been remedied.
- Digital Input Reset: Provide a momentary 24V DC pulse to the digital input mapped to the Alarm Reset command inside the embedded picoPLC program or MotionWiz configuration.
- MotionWiz PC Software: Connect your PC via the RS232 / RS485 serial communication port, launch Parker MotionWiz, open the online Diagnostics window, and click “Reset Faults” to clear the latch.
- Fieldbus Control Word (CANopen / EtherCAT): Set Bit 7 (Fault Reset) from `0` to `1` in the CiA 402 / DSP402 Control Word (0x6040) from the master motion controller or PLC.
- Power Cycle (24V Logic & Mains): Remove main AC supply voltage and cycle the 24V DC auxiliary power supply (terminals 24 and 48). Wait at least 5 minutes for the internal high-voltage capacitor bank to discharge completely before re-applying power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated CAT III / CAT IV multimeter (rated up to 1000V) that intermediate DC bus terminals (+ and -) as well as motor power output terminals (Motor 1: terminals 5, 6, 7; Motor 2: terminals 9, 10, 11 on TWIN-N) measure strictly below 50VDC to safety ground before opening terminal covers or touching cabling on Parker TWIN-N and SPD-N servo drives.