Schneider Altivar ATV12 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error codes, causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar 12 (ATV12) compact drive series. Search or filter through the complete diagnostic directory below.

Compact Machine Inverter Power: 0.18 to 4 kW (0.25 to 5 HP) Embedded Modbus RTU (RJ45)
Power Range 0.18 – 4 kW (0.25 – 5 HP)
Supply Voltage 100-120V 1-Ph / 200-240V 1/3-Ph
Control Modes Standard V/f, Sensorless Vector (SVC)
Operator Interface Integrated 4-Digit Display & Jog Dial

Complete Schneider ATV12 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCF, SCF1, OHF, or Overcurrent).

Fault Code and MeaningCause and Remedy
CrF1
Precharge

Cause: Charging relay control fault or charging resistor damaged.


Remedy:

  • Turn the drive off and then back on again.

  • Check the connections.

  • Check the stability of the main supply.

  • Contact your local Schneider Electric representative.


InF1
Unknown drive rating

Cause: The power card is different from the card stored.


Remedy:
  • Contact your local Schneider Electric representative.

InF2
Unknown or incompatible power board

Cause: The power card is incompatible with the control card.


Remedy:
  • Contact your local Schneider Electric representative.

InF3
Internal serial link

Cause: Communication interruption between the internal cards.


Remedy:
  • Contact your local Schneider Electric representative.

InF4
Invalid industrialization zone

Cause: Inconsistent internal data.


Remedy:
  • Contact your local Schneider Electric representative.

InF9
Current measurement circuit

Cause: Current measurement is not correct due to hardware circuit.


Remedy:
  • Contact your local Schneider Electric representative.

----
Problem of application Firmware

Cause: Invalid application firmware update using the Multi-Loader tool.


Remedy:
  • Flash again the application firmware of the product.

InFb
Internal thermal sensor detected fault

Cause:

  • The drive temperature sensor is not operating correctly.

  • The drive is in short circuit or open.




Remedy:
  • Contact your local Schneider Electric representative.

InFE
Internal CPU

Cause: Internal microprocessor.


Remedy:

  • Turn the drive off and then back on again.

  • Contact local Schneider Electric representative.


OCF
Overcurrent

Cause:

  • Parameters in the Motor control menu (drC) are not correct.

  • Inertia or load too high.

  • Mechanical locking.




Remedy:

  • Check the parameters.

  • Check the size of the motor/drive/load.

  • Check the state of the mechanism.

  • Connect line chokes.

  • Reduce the Switching frequency (SFr).

  • Check the ground connection of drive, motor cable and motor insulation.


SCF1
Motor or Ground short circuit

Cause:

  • Short-circuit or grounding at the drive output.

  • Ground fault during running status.

  • Commutation of motors during running status.

  • Significant current leakage to ground if several motors are connected in parallel.




Remedy:

  • Check the cables connecting the drive to the motor, and the motor insulation.

  • Connect motor chokes.


SCF3
Ground short circuit

Cause: See SCF1.


Remedy:
  • See SCF1 remedies.

SCF4
IGBT short circuit

Cause: Internal power component short circuit detected at power-on.


Remedy:
  • Contact your local Schneider Electric representative.

SOF
Overspeed

Cause:

  • Instability.

  • Overspeed associated with the inertia of the application.




Remedy:

  • Check the motor.

  • Overspeed is 10% more than Maximum frequency (tFr), so adjust this parameter if necessary.

  • Add a braking resistor.

  • Check the size of the motor/drive/load.

  • Check parameters of the speed loop (gain and stability).


tnF
Auto-tuning

Cause:

  • Motor not connected to the drive.

  • One motor phase loss.

  • Special motor.

  • Motor is rotating (being driven by the load, for example).




Remedy:

  • Check that the motor/drive are compatible.

  • Check that the motor is present during auto-tuning.

  • If an output contactor is being used, close it during auto-tuning.

  • Check that the motor is completely stopped.


LFF1
AI current lost fault

Cause: Detection if AI1 is current, scaling > 3 mA, and input < 2 mA.


Remedy:
  • Check the terminal connection.

ObF
Overbraking

Cause: Braking too sudden or driving load too high.


Remedy:

  • Increase the deceleration time.

  • Install a module unit with a braking resistor if necessary.

  • Check the line supply voltage.


OHF
Drive overheat

Cause: Drive temperature too high.


Remedy:

  • Check the motor load, drive ventilation, and ambient temperature.

  • Wait for the drive to cool down before restarting.


OLC
Process overload

Cause: Process overload.


Remedy:
  • Check the process and the parameters of the drive to be in phase.

OLF
Motor overload

Cause: Triggered by excessive motor current.


Remedy:
  • Check the setting of the motor thermal protection, check the motor load.

OPF1
1 output phase loss

Cause: Loss of one phase at drive output.


Remedy:

  • Check the connections from the drive to the motor.

  • In case of using downstream contactor, check the right connection, cable and contactor.


OPF2
3 output phase loss

Cause: Motor not connected, low power, contactor open, or instability.


Remedy:

  • Check connections.

  • Test on a low-power motor (set OPL = YES).

  • To check without motor, deactivate OPL (= no).

  • Check parameters: UFr, UnS, nCr, and perform Auto-tuning.


OSF
Main overvoltage

Cause: Line voltage too high or disturbed line supply.


Remedy:

  • Check and adjust the line voltage.

  • If intermittent, set Relay R1 to FLt and connect to upstream protection.


PHF
Input phase loss

Cause: Incorrect supply, blown fuse, phase failure, or unbalanced load.


Remedy:

  • Check the power connection and the fuses.

  • Use a 3-phase line supply.

  • Disable the fault by setting IPL = no.


SCF5
Load short circuit

Cause: Short-circuit at drive output or during run/DC injection.


Remedy:
  • Check the cables connecting the drive to the motor, and the motor's insulation.

SLF1
Modbus communication

Cause: Interruption in communication on the Modbus network.


Remedy:

  • Check connections of communication bus.

  • Check time-out (ttO).

  • Refer to the Modbus user manual.


SLF2
SoMove communication

Cause: Communication interruption with SoMove.


Remedy:

  • Check the SoMove connecting cable.

  • Check the time-out.


SLF3
HMI communication

Cause: Communication interruption with the external display terminal.


Remedy:
  • Check the terminal connection.

SPIF
PI Feedback detected fault

Cause: PID feedback below lower limit.


Remedy:

  • Check the PID function feedback.

  • Check supervision threshold (LPI) and time delay (tPI).


ULF
Process underload fault

Cause: Process underload or motor current below threshold (LUL) for time (ULt).


Remedy:
  • Check the process and the parameters of the drive to be in phase.

tJF
IGBT overheat

Cause: Drive overheated (IGBT temp too high).


Remedy:

  • Check load size.

  • Reduce Switching frequency (SFr).

  • Wait for the drive to cool.


EPF1
External detected fault

Cause: Event triggered by an external device.


Remedy:
  • Check the device which caused the trip and reset.

CFF
Incorrect configuration

Cause: HMI block replaced with different rating or inconsistent parameters.


Remedy:

  • Return to factory settings or retrieve valid backup.

  • Contact Schneider Electric if fault remains.


CFI
Invalid configuration

Cause: Configuration loaded is inconsistent or upload interrupted.


Remedy:

  • Check configuration loaded previously.

  • Load a compatible configuration.


CFI2
Download invalid configuration

Cause: Interruption of download operation (Loader/SoMove).


Remedy:

  • Check connection.

  • Restart download or restore factory setting.


USF
Undervoltage

Cause: Line supply too low or transient dip.


Remedy:
  • Check voltage and Undervoltage Phase Loss Menu (USb) parameters.

InIt
On initializing itself

Description:

  • Micro controller initializing.

  • Communication configuration search.


Com.E
Communication error (Flashing)

Description:

  • 50ms time-out error.

  • Shown after 220 retry attempts.


A-17
Key alarm (Flashing)

Description:

  • Key pressed > 10s.

  • Membrane switch disconnected.

  • Keypad woken up while key pressed.


cLr
Confirm Fault reset (Flashing)

Description:
  • Appears if STOP key is pressed when there is a keypad fault.

dEU.E
Drive mismatch (Flashing)

Description:
  • Drive type (brand) did not match with keypad type.

rOM.E
ROM abnormality (Flashing)

Description:
  • Keypad ROM abnormality detected by checksum.

rAM.E
RAM abnormality (Flashing)

Description:
  • Keypad RAM abnormality detected.

CPU.E
The other defect (Flashing)

Description:
  • The other detected fault.

How to Clear & Reset Schneider ATV12 Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the integrated front keypad once the cause of the fault has been removed (applicable for reset-clearing faults).
  2. Digital Input Reset (LI): In the Fault Management menu [FLt-], assign parameter rSF (Fault Reset assignment) to an available logic input terminal (e.g., LI1 to LI4). Transitioning the terminal high resets the drive.
  3. Automatic Restart: Set parameter Atr (Automatic restart) to YES in the [FLt-] menu to permit automatic reset following transient faults such as supply undervoltage (USF) or momentary mains loss.
  4. Modbus Serial Network: Pulse Bit 7 (Fault Reset) from `0` to `1` in the Command Register (CMD / 8501) over the embedded Modbus serial communication link (RJ45 port).
  5. Power Cycle: Disconnect the incoming line AC power, wait until the front 4-digit 7-segment display turns completely dark (approx. 5 minutes for bus capacitors to discharge), and reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated DC voltmeter that the intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] before removing terminal covers, handling wiring, or touching motor terminals U, V, and W on the Schneider ATV12 drive.