Schneider ATV32 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar 32 (ATV32) book-format machine drive. Search or filter through the complete fault code directory below.

Book-Format Machine Drive Power: 0.18 to 15 kW (0.25 to 20 HP) Embedded Safety Functions (STO SIL 3)
Power Range 0.18 – 15 kW (0.25 – 20 HP)
Supply Voltage 200–240V (1-Ph) / 380–500V (3-Ph)
Control Modes Vector, V/Hz & Synchronous Motor
Operator Interface Integrated Display & Navigation Wheel

Complete Schneider ATV32 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCF, ObF, SOF, or Overheating).

Fault Code and MeaningCause and Remedy
AnF
[Load slipping]

Cause: The difference between the output frequency and the speed feedback is not correct.



Remedy:

  • Check the motor, gain and stability parameters.

  • Add a braking resistor.

  • Check the size of the motor/drive/load.

  • Check the encoder's mechanical coupling and its wiring.

  • Check the setting of parameters.


ASF
[Angle Error]

Cause: This occurs during the phase-shift angle measurement, if the motor phase is disconnected or if the motor inductance is too high.



Remedy:

  • Check the motor phases and the maximum current allowed by the drive.


brF
[Brake feedback]

Cause:

  • The brake feedback contact does not match the brake logic control.

  • The brake does not stop the motor quickly enough (detected by measuring the speed on the "Pulse input" input).




Remedy:

  • Check the feedback circuit and the brake logic control circuit.

  • Check the mechanical state of the brake.

  • Check the brake linings.


CrF1
[Precharge]

Cause: Charging relay control detected fault or charging resistor damaged.



Remedy:

  • Turn the drive off and then turn on again.

  • Check the internal connections.

  • Contact Schneider Electric Product Support.


EEF1
[Control Eeprom]

Cause: Internal memory detected fault, control block.



Remedy:

  • Check the environment (electromagnetic compatibility).

  • Turn off, reset, return to factory settings.

  • Contact Schneider Electric Product Support.


EEF2
[Power Eeprom]

Cause: Internal memory detected fault, power card.



Remedy:

  • Contact Schneider Electric Product Support.


FCF1
[Out. contact. stuck]

Cause: The output contactor remains closed although the opening conditions have been met.



Remedy:

  • Check the contactor and its wiring.

  • Check the feedback circuit.


HdF
[IGBT desaturation]

Cause: Short-circuit or grounding at the drive output.



Remedy:

  • Check the cables connecting the drive to the motor, and the motor insulation.


ILF
[internal com. link]

Cause: Communication interruption between option card and drive.



Remedy:

  • Check the environment (electromagnetic compatibility).

  • Check the connections.

  • Replace the option card.

  • Contact Schneider Electric Product Support.


InF1
[Rating error]

Cause: The power card is different from the card stored.



Remedy:

  • Check the reference of the power card.


InF2
[Incompatible PB]

Cause: The power card is incompatible with the control block.



Remedy:

  • Check the reference of the power card and its compatibility.


InF3
[Internal serial link]

Cause: Communication interruption between the internal cards.



Remedy:

  • Check the internal connections.

  • Contact Schneider Electric Product Support.


InF4
[Internal-mftg zone]

Cause: Internal data inconsistent.



Remedy:

  • Recalibrate the drive (performed by Schneider Electric Product Support).


InF6
[Internal - fault option]

Cause: The option installed in the drive is not recognized.



Remedy:

  • Check the reference and compatibility of the option.

  • Check that the option is well inserted into the ATV32.


InF9
[Internal- I measure]

Cause: The current measurements are incorrect.



Remedy:

  • Replace the current sensors or the power card.

  • Contact Schneider Electric Product Support.


InFA
[Internal-mains circuit]

Cause: The input stage is not operating correctly.



Remedy:

  • Contact Schneider Electric Product Support.


InFb
[Internal- th. sensor]

Cause: The drive temperature sensor is not operating correctly.



Remedy:

  • Replace the drive temperature sensor.

  • Contact Schneider Electric Product Support.


InFE
[internal- CPU]

Cause: Internal microprocessor detected fault.



Remedy:

  • Turn off and reset.

  • Contact Schneider Electric Product Support.


SAFF
[Safety fault]

Cause:

  • Debounce time exceeded.

  • SS1 trip threshold exceeded.

  • Wrong configuration.

  • SLS type trip overspeed detected.




Remedy:

  • Check the safety functions configuration.

  • Check the ATV32 Integrated safety Functions Manual (S1A45606).

  • Contact Schneider Electric Product Support.


SOF
[Overspeed]

Cause: Instability or driving load too high.



Remedy:

  • Check the motor, gain and stability parameters.

  • Add a braking resistor.

  • Check the size of the motor/drive/load.

  • Check the parameters settings for the [FREQUENCY METER] (FqF-) function.


SPF
[Speed fdback loss]

Cause:

  • Signal on "Pulse input" missing, if the input is used for speed measurement.

  • Encoder feedback signal missing.




Remedy:

  • Check the wiring of the input cable and the detector used.

  • Check the configuration parameters of the encoder.

  • Check the wiring between the encoder and the drive.

  • Check the encoder.


bLF
[Brake control]

Cause:

  • Brake release current not reached.

  • Brake engage frequency threshold [Brake engage freq] (bEn) only regulated when brake logic control is assigned.




Remedy:

  • Check the drive/motor connection.

  • Check the motor windings.

  • Check the [Brake release I FW] (Ibr) and [Brake release I Rev] (Ird) settings.

  • Apply the recommended settings for [Brake engage freq] (bEn).


CnF
[Com. network]

Cause: Communication interruption on communication card.



Remedy:

  • Check the environment (electromagnetic compatibility).

  • Check the wiring.

  • Check the time-out.

  • Replace the option card.

  • Contact Schneider Electric Product Support.


COF
[CANopen com.]

Cause: Communication interruption on the CANopen® bus.



Remedy:

  • Check the communication bus.

  • Check the time-out.

  • Refer to the CANopen® User's manual.


EPF1
[External flt-LI/Bit]

Cause: Event triggered by an external device, depending on user.



Remedy:

  • Check the device which caused the trip and reset.


EPF2
[External fault com.]

Cause: Event triggered by a communication network.



Remedy:

  • Check for the cause of the trip and reset.


FbES
[FB stop flt.]

Cause: Function blocks have been stopped while motor was running.



Remedy:

  • Check [Stop FB Stop motor] (FbSM) configuration.


FCF2
[Out. contact. open.]

Cause: The output contactor remains open although the closing conditions have been met.



Remedy:

  • Check the contactor and its wiring.

  • Check the feedback circuit.


LCF
[input contactor]

Cause: The drive is not turned on even though [Mains V. time out ] (LCt) has elapsed.



Remedy:

  • Check the contactor and its wiring.

  • Check the time-out.

  • Check the line/contactor/drive connection.


LFF3
[AI3 4-20mA loss]

Cause: Loss of the 4-20 mA reference on analog input AI3.



Remedy:

  • Check the connection on the analog inputs.


ObF
[Overbraking]

Cause:

  • Braking too sudden or driving load.

  • Line voltage too high.




Remedy:

  • Increase the deceleration time.

  • Install a braking resistor if necessary.

  • Activate the [Dec ramp adapt.] (brA) function if it is compatible with the application.

  • Check the line voltage.


OCF
[Overcurrent]

Cause:

  • Parameters in the [SETTINGS] and [MOTOR CONTROL] menus are not correct.

  • Inertia or load too high.

  • Mechanical locking.




Remedy:

  • Check the parameters.

  • Check the size of the motor/drive/load.

  • Check the state of the mechanism.

  • Decrease [Current limitation] (CLI).

  • Increase the switching frequency.


OHF
[Drive overheat]

Cause: Drive temperature too high.



Remedy:

  • Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting.


OLC
[Proc. overload flt]

Cause: Process overload.



Remedy:

  • Check and remove the cause of the overload.

  • Check the parameters of the [PROCESS OVERLOAD] (OLd-) function.


OLF
[Motor overload]

Cause: Triggered by excessive motor current.



Remedy:

  • Check the setting of the motor thermal protection, check the motor load. Wait for the motor to cool down before restarting.


OPF1
[1 output phase loss]

Cause: Loss of one phase at drive output.



Remedy:

  • Check the connections from the drive to the motor.



OPF2



[3 motor phase loss]

Cause:

Motor not connected or motor power too low.

Output contactor open.

Instantaneous instability in the motor current.



Remedy:

  • Check the connections from the drive to the motor.

  • If an output contactor is being used, set [Output Phase Loss] (OPL) to [Output cut] (OAC).

  • Test on a low power motor or without a motor: In factory settings mode, motor phase loss detection is active [Output Phase Loss] (OPL) = [Yes] (YES). To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive (in particular for high power drives), deactivate motor phase loss detection [Output Phase Loss] (OPL) = [No] (nO).

  • Check and optimize the following parameters: [IR compensation] (UFr), [Rated motor volt.] (UnS) and [Rated mot. current] (nCr) and perform [Auto tuning] (tUn).



OSF



[Mains overvoltage]

Cause:

Line voltage too high.

Disturbed mains supply.



Remedy:

  • Check the line voltage.



OtFL



[LI6=PTC overheat]

Cause:

Overheating of PTC probes detected on input LI6.



Remedy:

  • Check the motor load and motor size.

  • Check the motor ventilation.

  • Wait for the motor to cool before restarting.

  • Check the type and state of the PTC probes.



PtFL



[LI6=PTC probe]

Cause:

PTC probe on input LI6 open or short-circuited.



Remedy:

  • Check the PTC probe and the wiring between it and the motor/drive.



SCF1



[Motor short circuit]

Cause:

Short-circuit or grounding at the drive output.



Remedy:

  • Check the cables connecting the drive to the motor, and the motor insulation.

  • Reduce the switching frequency.

  • Connect chokes in series with the motor.

  • Check the adjustment of speed loop and brake.

  • Increase the [Time to restart] (ttr).

  • Increase the switching frequency.



SCF3



[Ground short circuit]

Cause:

Significant earth leakage current at the drive output if several motors are connected in parallel.



Remedy:

  • Check the cables connecting the drive to the motor, and the motor insulation.

  • Reduce the switching frequency.

  • Connect chokes in series with the motor.

  • Check the adjustment of speed loop and brake.

  • Increase the [Time to restart] (ttr).

  • Reduce the switching frequency.



SCF4



[IGBT short circuit]

Cause:

Power component detected fault.



Remedy:

  • Contact Schneider Electric Product Support.



SCF5



[Motor short circuit]

Cause:

Short-circuit at drive output.



Remedy:

  • Check the cables connecting the drive to the motor, and the motor's insulation.

  • Contact Schneider Electric Product Support.



SLF1



[Modbus com.]

Cause:

Communication interruption on the Modbus bus.



Remedy:

  • Check the communication bus.

  • Check the time-out.

  • Refer to the Modbus User's manual.



SLF2



[PC com.]

Cause:

Communication interruption with PC Software.



Remedy:

  • Check the PC Software connecting cable.

  • Check the time-out.



SLF3



[HMI com.]

Cause:

Communication interruption with the graphic display terminal or remote display terminal.



Remedy:

  • Check the terminal connection.

  • Check the time-out.



SSF



[Torque/current lim]

Cause:

Switch to torque or current limitation.



Remedy:

  • Check if there are any mechanical problems.

  • Check the parameters of [TORQUE LIMITATION] (tOL-) and the parameters of the [TORQUE OR I LIM. DETECT.] (tId-).



tJF



[IGBT overheat]

Cause:

Drive overheated.



Remedy:

  • Check the size of the load/motor/drive.

  • Reduce the switching frequency.

  • Wait for the motor to cool before restarting.



tnF



[Auto-tuning]

Cause:

Special motor or motor whose power is not suitable for the drive.

Motor not connected to the drive.

Motor not stopped.



Remedy:

  • Check that the motor/drive are compatible.

  • Check that the motor is present during auto-tuning.

  • If an output contactor is being used, close it during auto-tuning.

  • Check that the motor is stopped during tune operation.



ULF



[Proc. underload Flt]

Cause:

Process underload.



Remedy:

  • Check and remove the cause of the underload.

  • Check the parameters of the [PROCESS UNDERLOAD] (Uld-) function.


CFF
[Incorrect config.]

Cause:

  • Option card changed or removed.

  • Control block replaced by a control block configured on a drive with a different rating.

  • The current configuration is inconsistent.




Remedy:

  • Check that there are no card errors.

  • In the event of the option card being changed/removed deliberately, see manual remarks.

  • Check that there are no card errors.

  • In the event of the control block being changed deliberately, see manual remarks.

  • Return to factory settings or retrieve the backup configuration, if it is valid.


CFI / CFI2
[Invalid config.]

Cause:

  • Invalid configuration.

  • The configuration loaded in the drive via the bus or communication network is inconsistent.




Remedy:

  • Check the configuration loaded previously.

  • Load a compatible configuration.


CSF
[Ch. Sw. fault]

Cause:

  • Switch to not valid channels.




Remedy:

  • Check the function parameters.


dLF
[Dynamic load fault]

Cause:

  • Abnormal load variation.




Remedy:

  • Check that the load is not blocked by an obstacle.

  • Removal of a run command causes a reset.


FbE
[FB fault]

Cause:

  • Function blocks error.




Remedy:

  • See [FB Fault] (FbFt) for more details.


HCF
[Cards pairing]

Cause:

  • The [CARDS PAIRING] (PPI-) function has been configured and a drive card has been changed.




Remedy:

  • In the event of a card error, reinsert the original card.

  • Confirm the configuration by entering the [Pairing password] (PPI) if the card was changed deliberately.


PHF
[Input phase loss]

Cause:

  • Drive incorrectly supplied or a fuse blown.

  • One phase missing.

  • 3-phase ATV32 used on a single-phase line supply.

  • Unbalanced load.

  • This protection only operates with the drive on load.




Remedy:

  • Check the power connection and the fuses.

  • Use a 3-phase line supply.

  • Disable the detected fault by [Input phase loss] (IPL) = [No] (nO).


USF
[Undervoltage]

Cause:

  • Line supply too low.

  • Transient voltage dip.




Remedy:

  • Check the voltage and the parameters of [UNDERVOLTAGE MGT] (USb-).


InIt
[Initialization in progress]

Cause:

  • The microcontroller is initializing.

  • Search underway for communication configuration.




Remedy:

  • Wait for initialization to complete.


COM.E (Flashing)
[Communication error]

Cause:

  • Time out detected fault (50 ms).

  • This message is displayed after 20 attempts at communication.




Remedy:

  • Check communication connections and parameters.


A-17 (Flashing)
[Alarm button]

Cause:

  • A key has been held down for more than 10 seconds.

  • The keypad is disconnected.

  • The keypad wakes up when a key is pressed.




Remedy:

  • Release the key.

  • Check keypad connection.


CLr (Flashing)
[Confirmation of detected fault reset]

Cause:

  • This is displayed when the STOP key is pressed once if the active command channel is the remote display terminal.




Remedy:

  • Informational message; no specific remedy required.


dEU.E (Flashing)
[Drive disparity]

Cause:

  • The drive brand does not match that of the remote display terminal.




Remedy:

  • Ensure the remote display is compatible with the drive.


rOM.E (Flashing)
[ROM anomaly]

Cause:

  • The remote display terminal detects a ROM anomaly on the basis of checksum calculation.




Remedy:

  • Replace the remote display terminal.


rAM.E (Flashing)
[RAM anomaly]

Cause:

  • The remote display terminal detects a RAM anomaly.




Remedy:

  • Replace the remote display terminal.


CPU.E (Flashing)
[Other detected faults]

Cause:

  • Other detected faults.




Remedy:

  • Check for other fault codes on the drive.


How to Clear & Reset Schneider ATV32 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET button on the front control panel once the fault condition has been resolved. Ensure any active run signals (LI1..LI6) are toggled off before resetting.
  2. Logic Input Reset (LI): If a logic input is configured for fault reset in menu [FAULT MANAGEMENT] (FLt-) > [FAULT RESET] (rSF-), apply a 0-to-1 transition pulse to the designated logic input terminal (e.g., LI2 to LI6).
  3. SoMove PC Software: Connect via the front Modbus RJ45 port or optional Bluetooth interface, open the SoMove diagnostic window, and click “Fault Reset”.
  4. Fieldbus Control Word: Write Bit 7 (Fault Reset) from `0` to `1` in the Command Word (CMD) via embedded Modbus RTU, CANopen, or optional communication cassettes (EtherNet/IP, Profibus DP, DeviceNet).
  5. Power Cycle: Disconnect main AC power, wait until the integrated 4-digit display turns off completely, and wait at least 15 minutes to allow the DC bus capacitors to discharge safely before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 42VDC across terminals [PA/+] and [PC/-] before removing terminal covers, handling wiring, or touching output terminals U, V, and W on the Schneider Altivar 32 drive.