Schneider ATV61 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar 61 (ATV61) HVAC and pump drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 630 kW (1 – 900 HP)
Supply Voltage
200–240V / 380–480V / 690V AC
Control Modes
Variable Torque V/f & Energy Saving
Operator Interface
Graphic Terminal / 7-Segment
Complete Schneider ATV61 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OCF, OHF, OLF, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| AI2F [AI2 input] | Cause: Non-conforming signal on analog input AI2. Remedy:
|
| bOF [DBR overload] | Cause: The braking resistor is under excessive stress. Remedy:
|
| bUF [DB unit sh. Circuit] | Cause:
Remedy:
|
| CrF1 [Precharge] | Cause: Load relay control fault or charging resistor damaged. Remedy:
|
| CrF2 [Thyr. soft charge] | Cause: DC bus charging fault (thyristors). Remedy:
|
| dCF [Differential curent Fault] | Cause: Current difference between power block A and B (ATV61EC60 ... M14N4 or ATVEM15...M24Y only). Remedy:
|
| EEF1 [Control Eeprom] | Cause: Internal memory fault, control card. Remedy:
|
| EEF2 [Power Eeprom] | Cause: Internal memory fault, power card. Remedy:
|
| EnF [Encoder] | Cause: Encoder feedback fault. Remedy:
|
| FCF1 [Out. contact. stuck] | Cause: The output contactor remains closed although the opening conditions have been met. Remedy:
|
| Fd2 [Damper open] | Cause: The damper remains open although the closing conditions have been met. Remedy:
|
| HdF [IGBT desaturation] | Cause: Short-circuit or grounding at the drive output. Remedy:
|
| ILF [internal com. link] | Cause: Communication fault between option card and drive. Remedy:
|
| InF1 [Rating error] | Cause: The power card is different from the card stored. Remedy:
|
| InF2 [Incompatible PB] | Cause: The power card is incompatible with the control card. Remedy:
|
| InF3 [Internal serial link] | Cause: Communication fault between the internal cards. Remedy:
|
| InF4 [Internal MFG area] | Cause: Internal data inconsistent. Remedy:
|
| InF6 [Internal-option] | Cause: The option installed in the drive is not recognized. Remedy:
|
| InF7 [Internal-hard init.] | Cause: Initialization of the drive is incomplete. Remedy:
|
| InF8 [Internal-ctrl supply] | Cause: The control power supply is incorrect. Remedy:
|
| InF9 [Internal- I measure] | Cause: The current measurements are incorrect. Remedy:
|
| InFA [Internal-mains circuit] | Cause: The input stage is not operating correctly. Remedy:
|
| InFb [Internal- th. sensor] | Cause:
Remedy:
|
| InFC [Internal-time meas.] | Cause: Fault on the electronic time measurement component. Remedy:
|
| InFE [internal- CPU] | Cause: Internal microprocessor fault. Remedy:
|
| OCF [Overcurrent] | Cause:
Remedy:
|
| PrF [Power removal] | Cause: Fault with the drive’s “Power removal” safety function. Remedy:
|
| SCF1 [Motor short circuit] | Cause: Short-circuit or grounding at the drive output. Remedy:
|
| SCF2 [Impedant sh. circuit] | Cause: Impedant short circuit. Remedy:
|
| SCF3 [Ground short circuit] | Cause: Significant earth leakage current at the drive output if several motors are connected in parallel. Remedy:
|
| SOF [Overspeed] | Cause: Instability or driving load too high. Remedy:
|
| SPF [Speed fdback loss] | Cause:
Remedy:
|
| tnF [Auto-tuning] | Cause:
Remedy:
|
APF [Application fault] | Cause: Controller Inside card fault. Remedy:
|
CnF [Com. network] | Cause: Communication fault on communication card. Remedy:
|
COF [CAN com.] | Cause: Interruption in communication on the CANopen bus. Remedy:
|
EPF1 [External flt-LI/Bit] | Cause: Fault triggered by an external device, depending on user. Remedy:
|
EPF2 [External fault com.] | Cause: Fault triggered by a communication network. Remedy:
|
FCF2 [Out. contact. open.] | Cause: The output contactor remains open although the closing conditions have been met. Remedy:
|
Fd1 [Damper stuck] | Cause: The damper remains closed although the opening conditions have been met. Remedy:
|
LCF [input contactor] | Cause: The drive is not turned on even though [Mains V. time out] (LCt) has elapsed. Remedy:
|
LFF2 LFF3 LFF4 [AI2 4-20mA loss] [AI3 4-20mA loss] [AI4 4-20mA loss] | Cause: Loss of the 4-20 mA reference on analog input AI2, AI3 or AI4. Remedy:
|
nFF [No Flow Fault] | Cause: Zero fluid. Remedy:
|
ObF [Overbraking] | Cause: Braking too sudden or driving load. Remedy:
|
OHF [Drive overheat] | Cause: Power board -PCB over temperature. Braking unit over temperature. Phase module over temperature. Rectifier over temperature. Remedy:
|
OLC [Proc. Overload Flt] | Cause: Process overload. Remedy:
|
OLF [Motor overload] | Cause: Triggered by excessive motor current. Remedy:
|
OPF1 [1 motor phase loss] | Cause: Loss of one phase at drive output. Remedy:
|
OPF2 [3 motor phase loss] | Cause: Motor not connected or motor power too low. Output contactor open. Instantaneous instability in the motor current. Remedy:
|
OSF [Mains overvoltage] | Cause: Line voltage too high. Disturbed line supply. Remedy:
|
OtF1 [PTC1 overheat] | Cause: Overheating of the PTC1 probes detected. Remedy:
|
OtF2 [PTC2 overheat] | Cause: Overheating of the PTC2 probes detected. Remedy:
|
OtFL [LI6=PTC overheat] | Cause: Overheating of PTC probes detected on input LI6. Remedy:
|
PtF1 [PTC1 probe] | Cause: PTC1 probes open or short-circuited. Remedy:
|
PtF2 [PTC2 probe] | Cause: PTC2 probes open or short-circuited. Remedy:
|
PtFL [LI6=PTC probe] | Cause: PTC probes on input LI6 open or short-circuited. Remedy:
|
SCF4 [IGBT short circuit] | Cause: Power component fault. Remedy:
|
SCF5 [Motor short circuit] | Cause: Short-circuit at drive output. Remedy:
|
SLF1 [Modbus com.] | Cause: Interruption in communication on the Modbus bus. Remedy:
|
SLF2 [PC com.] | Cause: Fault communicating with PC Software. Remedy:
|
SLF3 [HMI com.] | Cause: Fault communicating with the graphic display terminal. Remedy:
|
SPIF [PI Feedback] | Cause: PID feedback below lower limit. Remedy:
|
SSF [Torque/current lim] | Cause: Switch to torque limitation. Remedy:
|
tJF [IGBT overheat] | Cause: Drive overheated. Remedy:
|
ULF [Proc. Underload Flt] | Cause: Process underload. Remedy:
|
CFF [Incorrect config.] | Cause: Option card changed or removed. The current configuration is inconsistent. Remedy:
|
CFI [Invalid config.] | Cause: Invalid configuration. The configuration loaded in the drive via the bus is inconsistent. [Max frequency] (tFr) has been set at a value higher than 599Hz. Remedy:
|
HCF [Cards pairing] | Cause: The [CARDS PAIRING] (PPI-) function has been configured and a drive card has been changed. Remedy:
|
PHF [Input phase loss] | Cause: Drive incorrectly supplied or a fuse blown. Failure of one phase. 3-phase ATV61 used on a single-phase line supply. Unbalanced load. (This protection only operates with the drive on load). Remedy:
|
PrtF [Power Ident] | Cause: The [Power Identification] (Prt) parameter is incorrect. Control card replaced by a control card configured on a drive with a different rating. Remedy:
|
USF [Undervoltage] | Cause: Line supply too low. Transient voltage dip. Damaged pre-charge resistor. (This protection only operates with the drive running in motor mode). Remedy:
|
| CFF [Incorrect config.] | Cause:
Remedy:
|
| CFI / CFI2 [Invalid config.] | Cause:
Remedy:
|
| CSF [Ch. Sw. fault] | Cause:
Remedy:
|
| dLF [Dynamic load fault] | Cause:
Remedy:
|
| FbE [FB fault] | Cause:
Remedy:
|
| HCF [Cards pairing] | Cause:
Remedy:
|
| PHF [Input phase loss] | Cause:
Remedy:
|
| USF [Undervoltage] | Cause:
Remedy:
|
| InIt [Initialization in progress] | Cause:
Remedy:
|
| COM.E (Flashing) [Communication error] | Cause:
Remedy:
|
| A-17 (Flashing) [Alarm button] | Cause:
Remedy:
|
| CLr (Flashing) [Confirmation of detected fault reset] | Cause:
Remedy:
|
| dEU.E (Flashing) [Drive disparity] | Cause:
Remedy:
|
| rOM.E (Flashing) [ROM anomaly] | Cause:
Remedy:
|
| rAM.E (Flashing) [RAM anomaly] | Cause:
Remedy:
|
| CPU.E (Flashing) [Other detected faults] | Cause:
Remedy:
|
How to Clear & Reset Schneider ATV61 Drive Faults
- Keypad Reset: Press the red STOP/RESET key on the graphic display terminal or integrated 7-segment display once the fault condition has been resolved and run commands are removed.
- Logic Input Reset (LI): In menu [1.8 – FAULT MANAGEMENT] (FLt-), configure parameter [Fault Reset assign.] (rSF) to an available logic input (e.g., LI2 to LI6). Apply a +24V transition to reset the drive.
- PowerSuite / SoMove Software: Connect your PC via the front RJ45 Modbus port, monitor active trips in the diagnostics window, and initiate a software fault clear command.
- Fieldbus Control Word: Write Bit 7 (Fault Reset) from 0 to 1 in the drive Control Word (CMD / register 8501) over embedded Modbus RTU, CANopen, or optional communication cards (LonWorks, BACnet, Profibus, Ethernet).
- Power Cycle: Disconnect the incoming mains line voltage at the circuit breaker. Wait at least 15 minutes until internal DC bus capacitors discharge and all indicator LEDs turn off, then restore power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 42VDC across terminals [PA/+] and [PC/-] before removing covers, inspecting motor cabling, or touching power terminals U, V, and W on the Schneider Altivar 61 drive.