Schneider Altivar ATV71 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar 71 (ATV71) constant torque heavy-duty drive series. Search or filter through the complete diagnostic directory below.
Power Range
0.37 – 630 kW (0.5 – 900 HP)
Supply Voltage
200–240V / 380–480V / 500–690V
Control Modes
Closed Loop (FVC), Vector (SFVC) & V/f
Operator Interface
Multilingual Graphic Display Terminal
Complete Schneider ATV71 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OCF, SCF1, SOF, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| AI2F [AI2 input] | Cause: Non-conforming signal on analog input AI2. Remedy:
|
| AnF [Load slipping] | Cause: The encoder speed feedback does not match the reference. Remedy:
|
| bOF [DBR overload] | Cause: The braking resistor is under excessive stress. Remedy:
|
| brF [Brake feedback] | Cause: The brake feedback contact does not match the brake logic control. The brake does not stop the motor quickly enough (detected by measuring the speed on the "Pulse input" input). Remedy:
|
| bUF [DB unit sh. Circuit] | Cause: Short-circuit output from braking unit or Braking unit not connected. Remedy:
|
| CrF1 [Precharge] | Cause: Charging relay control fault or charging resistor damaged. Remedy:
|
| CrF2 [Thyr. soft charge] | Cause: DC bus charging fault (thyristors). Remedy:
|
| dCF [Differential current Fault] | Cause: Current difference between power block A and B (Specific ATV71 models only). Remedy:
|
| ECF [Encoder coupling] | Cause: Break in encoder’s mechanical coupling. Remedy:
|
| EEF1 [Control Eeprom] | Cause: Internal memory fault, control card. Remedy:
|
| EEF2 [Power Eeprom] | Cause: Internal memory fault, power card. Remedy:
|
| EnF [Encoder] | Cause: Encoder feedback fault. Remedy:
|
| FCF1 [Out. contact. stuck] | Cause: The output contactor remains closed although the opening conditions have been met. Remedy:
|
| HdF [IGBT desaturation] | Cause: Short-circuit or grounding at the drive output. Remedy:
|
| ILF [Internal com. link] | Cause: Communication fault between option card and drive. Remedy:
|
| InF1 [Rating error] | Cause: The power card is different from the card stored. Remedy:
|
| InF2 [Incompatible PB] | Cause: The power card is incompatible with the control card. Remedy:
|
| InF3 [Internal serial link] | Cause: Communication fault between the internal cards. Remedy:
|
| InF4 [Internal-mftg zone] | Cause: Internal data inconsistent. Remedy:
|
| InF6 [Internal - fault option] | Cause: The option installed in the drive is not recognized. Remedy:
|
| InF7 [Internal-hard init.] | Cause: Initialization of the drive is incomplete. Remedy:
|
| InF8 [Internal-ctrl supply] | Cause: The control power supply is incorrect. Remedy:
|
| InF9 [Internal- I measure] | Cause: The current measurements are incorrect. Remedy:
|
| InFA [Internal-mains circuit] | Cause: The input stage is not operating correctly. Remedy:
|
| InFb [Internal- th. sensor] | Cause: The drive temperature sensor is not operating correctly or the braking unit's temperature sensor is not operating correctly. Remedy:
|
| InFC [Internal-time meas.] | Cause: Fault on the electronic time measurement component. Remedy:
|
| InFE [Internal- CPU] | Cause: Internal microprocessor fault. Remedy:
|
| OCF [Overcurrent] | Cause: Parameters in the [SETTINGS] (SEt-) and [1.4 MOTOR CONTROL] (drC-) menus are not correct. Inertia or load too high. Mechanical locking. Remedy:
|
| PrF [Power removal] | Cause: Fault with the drive’s "Power removal" safety function. Remedy:
|
| SCF1 [Motor short circuit] | Cause: Short-circuit or grounding at the drive output. Significant earth leakage current at the drive output if several motors are connected in parallel. Remedy:
|
| SCF2 [Impedant sh. circuit] | Cause: Short-circuit or grounding at the drive output (Impedant). Remedy:
|
| SCF3 [Ground short circuit] | Cause: Ground short circuit or significant earth leakage. Remedy:
|
| SOF [Overspeed] | Cause: Instability or driving load too high. Remedy:
|
| SPF [Speed fdback loss] | Cause:
Remedy:
|
| tnF [Auto-tuning] | Cause:
Remedy:
|
| APF [Application fault] | Cause: Controller Inside card fault Remedy: Please refer to the card documentation |
| bLF [Brake control] | Cause:
Remedy:
|
| CnF [Com. network] | Cause: Communication fault on communication card Remedy:
|
| COF [CANopen com.] | Cause: Interruption in communication on the CANopen bus Remedy:
|
| EPF1 [External flt-LI/Bit] | Cause: Fault triggered by an external device, depending on user Remedy: Check the device which caused the fault, and reset |
| EPF2 [External fault com.] | Cause: Fault triggered by a communication network Remedy: Check for the cause of the fault and reset |
| FCF2 [Out. contact. open.] | Cause: The output contactor remains open although the closing conditions have been met Remedy:
|
| LCF [input contactor] | Cause: The drive is not turned on even though [Mains V. time out] (LCt) has elapsed. Remedy:
|
| LFF2 / LFF3 / LFF4 [AI2/AI3/AI4 4-20mA loss] | Cause: Loss of the 4-20 mA reference on analog input AI2, AI3 or AI4 Remedy: Check the connection on the analog inputs |
| ObF [Overbraking] | Cause: Braking too sudden or driving load Remedy:
|
| OHF [Drive overheat] | Cause:
Remedy: Check the motor load, the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting |
| OLF [Motor overload] | Cause: Triggered by excessive motor current Remedy: Check the setting of the motor thermal protection, check the motor load. Wait for the drive to cool down before restarting. |
| OPF1 [1 output phase loss] | Cause: Loss of one phase at drive output Remedy: Check the connections from the drive to the motor |
| OPF2 [3 motor phase loss] | Cause:
Remedy:
|
| OSF [Mains overvoltage] | Cause:
Remedy:
|
| OtF1 [PTC1 overheat] | Cause: Overheating of the PTC1 probes detected. Remedy:
|
| OtF2 [PTC2 overheat] | Cause: Overheating of the PTC2 probes detected. Remedy:
|
| OtFL [LI6=PTC overheat] | Cause: Overheating of PTC probes detected on input LI6. Remedy:
|
| PtF1 [PTC1 probe] | Cause: PTC1 probes open or short-circuited. Remedy:
|
| PtF2 [PTC2 probe] | Cause: PTC2 probes open or short-circuited. Remedy:
|
| PtFL [LI6=PTC probe] | Cause: PTC probes on input LI6 open or short-circuited. Remedy:
|
| SCF4 [IGBT short circuit] | Cause: Power component fault. Remedy:
|
| SCF5 [Motor short circuit] | Cause: Short-circuit at drive output. Remedy:
|
| SLF1 [Modbus com.] | Cause: Interruption in communication on the Modbus bus. Remedy:
|
| SLF2 [PC com.] | Cause: Fault communicating with PC-Software. Remedy:
|
| SLF3 [HMI com.] | Cause: Fault communicating with the graphic display terminal. Remedy:
|
| SrF [TORQUE TIME OUT FLT] | Cause: The time-out of the torque control function is attained. Remedy:
|
| SSF [Torque/current lim] | Cause: Switch to torque limitation. Remedy:
|
| tJF [IGBT overheat] | Cause: Drive overheated. Remedy:
|
| CFF [Incorrect config.] | Cause:
Remedy:
|
| CFI [Invalid config.] | Cause:
Remedy:
|
| dLF [Dynamic load fault] | Cause: Abnormal load variation. Remedy:
|
| HCF [Cards pairing] | Cause: The [CARDS PAIRING] (PPI-) function has been configured and a drive card has been changed. Remedy:
|
| PHF [Input phase loss] | Cause:
Remedy:
|
| USF [Undervoltage] | Cause:
Remedy:
|
How to Clear & Reset Schneider ATV71 Drive Faults
- Graphic Display Terminal Reset: Press the red STOP / RESET key directly on the front graphic display terminal once the underlying fault cause has been removed.
- Digital Input Reset (LI): In menu [1.7 – FAULT MANAGEMENT] under submenu [FAULT RESET], assign parameter rSF (Fault reset assign.) to an available logic input terminal (e.g., LI1 to LI6). A positive transition on this terminal clears active faults.
- Automatic Fault Restart: Set parameter Atr (Automatic restart) to YES in menu [1.7 – FAULT MANAGEMENT] to allow the drive to automatically clear transient faults (such as momentary line undervoltage USF) when normal conditions resume.
- Communication Network Command: Write Bit 7 (Fault Reset) from `0` to `1` in the Control Word (CMD / register 8501) via embedded Modbus RTU, CANopen, or optional communication cards (Profibus DP, Ethernet/IP).
- Power Cycle: Disconnect the incoming 3-phase line AC power supply, wait until the Graphic Terminal display and internal DC bus charge LED extinguish completely (approx. 15 minutes), and reapply power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated DC voltmeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] before removing safety shrouds, modifying power wiring, or servicing motor terminals U/T1, V/T2, and W/T3 on the Schneider ATV71 drive.