Schneider ATV310 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Schneider Electric Easy Altivar ATV310 compact inverter series. Search or filter through the complete fault code directory below.

Easy Altivar Series Power: 0.37 to 11 kW (0.5 to 15 HP) Three-Phase 380–460V Input
Power Range 0.37 – 11 kW (0.5 – 15 HP)
Supply Voltage 380–460V AC (3-Phase)
Control Modes Sensorless Vector (SVC) & V/f
Operator Interface Built-in 4-Digit Display & Dial

Complete Schneider ATV310 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F010, F011, F018, or Overcurrent).

Fault Code and MeaningCause and Remedy
----
Problem with application firmware

Cause: Invalid application firmware update using the Multi-Loader tool.



Remedy:

  • Re-download application firmware.


F001
Precharge

Cause: Charging relay control fault or charging resistor damaged.



Remedy:

  • Turn the drive off and then back on again.

  • Check the connections.

  • Check the stability of the main supply.

  • Contact local Schneider Electric representative.


F002
Unknown drive rating

Cause: Power card and stored card versions different.



Remedy:

  • Contact local Schneider Electric representative.


F003
Unknown or incompatible power board

Cause: The power card is incompatible with the control card.



Remedy:

  • Contact local Schneider Electric representative.


F004
Internal serial link fault

Cause: Communication interruption between the internal cards.



Remedy:

  • Contact local Schneider Electric representative.


F005
Invalid industrialization zone

Cause: Internal data inconsistent.



Remedy:

  • Contact local Schneider Electric representative.


F006
Current measurement circuit

Cause: Current measurement is not correct due to hardware circuit fault.



Remedy:

  • Contact local Schneider Electric representative.


F007
Internal thermal sensor detected fault

Cause:

  • The drive temperature sensor is not operating correctly.

  • The drive is in short circuit or open.




Remedy:

  • Contact local Schneider Electric representative.


F008
Internal CPU

Cause: Internal microprocessor fault.



Remedy:

  • Turn the drive off and then back on again.

  • Contact local Schneider Electric representative.


F010
Overcurrent

Cause:

  • Parameters in the Motor control menu (300) are not correct.

  • Inertia or load too high.

  • Mechanical locking.




Remedy:

  • Check the parameters.

  • Check the size of the motor/drive/load.

  • Check the state of the mechanism.

  • Connect line motor chokes.

  • Reduce the Switching frequency range (315).

  • Check the ground connection of drive, motor cable, and motor insulation.


F018
Motor short-circuit

Cause:

  • Short-circuit or grounding at the drive output.

  • Ground fault while in run state.

  • Motor switching while in run state.

  • Significant current leakage to ground while several motors are connected in parallel.




Remedy:

  • Verify the cables connecting the drive to the motor and the motor insulation.

  • Adjust the switching frequency.

  • Connect chokes in series with the motor.

  • Verify the adjustment of speed loop.


F019
Ground short-circuit

Cause:

  • Ground fault while in run state.

  • Motor switching while in run state.

  • Significant current leakage to ground.




Remedy:

  • Verify the cables connecting the drive to the motor and the motor insulation.

  • Adjust the switching frequency.

  • Connect chokes in series with the motor.

  • Verify the adjustment of speed loop.


F020
IGBT short circuit

Cause: Internal power component short circuit detected at power on.



Remedy:

  • Contact local Schneider Electric representative.


F025
Overspeed

Cause:

  • Instability.

  • Overspeed associated with the inertia of the application.




Remedy:

  • Check the motor.

  • If overspeed is 10% more than Top frequency (308), adjust this parameter if necessary.

  • Add a braking resistor.

  • Check the size of the motor/drive/load.

  • Check parameters of the speed loop (gain and stability).


F028
Autotuning fault

Cause:

  • Motor not connected to the drive.

  • Motor phase loss.

  • Special motor.

  • Motor is rotating (being driven by the load, for example).




Remedy:

  • Check that the motor/drive are compatible.

  • Check that the motor is present during autotuning.

  • If an output contactor is being used downstream, close it during auto-tuning.

  • Check that the motor is completely stopped.


F036
Angle setting fault

Cause: This occurs during the phase-shift angle measurement, if the motor phase is disconnected or if the motor inductance is too high.



Remedy:

  • Check the motor phases and the maximum current allowed by the drive.


F009
Overbraking

Cause: Sudden braking or load inertia too high.



Remedy:

  • Increase the deceleration time.

  • Install a module unit with a braking resistor if necessary.

  • Check the main supply voltage to ensure it is under the maximum acceptable limit during run status.


F011
Drive overheat

Cause: Drive temperature too high.



Remedy:

  • Check the motor load, the drive ventilation and the ambient temperature.

  • Wait for the drive to cool down before restarting.

  • See Mounting and temperature conditions in manual.


F012
Process overload fault

Cause: Process overload.



Remedy:

  • Check that drive parameters and application processes are compatible.


F013
Motor overload

Cause: Triggered by excessive motor current.



Remedy:

  • Check configuration of motor thermal protection and motor load.


F014
1 Output phase loss

Cause: Loss of one phase on drive output.



Remedy:

  • Check the connections from the drive to the motor.

  • If using a downstream contactor, make sure the connection, cable and contactor are right.


F015
3 Output phases loss

Cause:

  • Motor not connected.

  • Motor power too low, below 6% of the rated drive current.

  • Output contactor open.

  • Transient instability in the motor current.




Remedy:

  • Check the connections from the drive to the motor.

  • Test on a low power motor or without a motor.

  • In factory settings, motor phase loss detection is active (605=01). To test without a motor, set 605=00.

  • Check and optimize IR compensation (310), Rated motor voltage (304), and Rated motor current (305), then perform Auto-tuning (318).


F016
Main overvoltage

Cause:

  • Line voltage too high.

  • Drive power supply >10% over max acceptable voltage.

  • Power with no run command >20% over max line supply.

  • Disturbed mains supply.




Remedy:

  • Turn Off the Drive. Check and adjust the line voltage.

  • After line comes back to nominal voltage, power On.

  • If intermittent F016 codes appear, set R1 assignment (205.0) to 01.


F017
Input phase loss

Cause:

  • Drive incorrectly supplied or a fuse blown.

  • Failure of one phase.

  • 3-phase drive used on a single-phase line supply.

  • Unbalanced load.




Remedy:

  • Check the power connection and the fuses.

  • Use a 3-phase line supply.

  • Disable reporting of this fault by setting Input Phase loss detection (606) to 00.


F021
Load short circuit

Cause:

  • Short-circuit at drive output.

  • Short circuit detection at the run command or DC injection if parameter IGBT Test (608) is set to 01.




Remedy:

  • Check the cables connecting the drive to the motor and the condition of motor insulation.


F022
Modbus interruption

Cause: Interrupted communication on the Modbus network.



Remedy:

  • Check the connections of communication bus.

  • Check the time-out (parameter Modbus time out 704).

  • Refer to the Modbus user manual.


F024
HMI communication

Cause: Communication interruption with the external display terminal.



Remedy:

  • Check the terminal connection.


F026
PI feedback fault

Cause: PID feedback below lower limit.



Remedy:

  • Verify the PID function feedback.

  • Verify the PID feedback supervision (parameter 59.25) and time delay setting (parameter 59.23).


F027
IGBT overheat

Cause:

  • Drive overheated.

  • IGBT internal temperature is too high for the ambient temperature and load.




Remedy:

  • Check the size of the load/motor/drive.

  • Reduce the Switching frequency (315).

  • Wait for the drive to cool down before restarting.


F029
Process underload fault

Cause:

  • Process underload.

  • Time that motor current is below the Process underload threshold (211) exceeds the delay (210).




Remedy:

  • Check that drive parameters and application processes are compatible.


F033
AI1 current loss

Cause:

  • Analog input AI1 is configured as current.

  • AI1 current scaling parameter (204.1) is greater than 3 mA.

  • Analog input current is lower than 2 mA.




Remedy:

  • Check the terminal connection.


F030
Undervoltage

Cause:

  • Line supply too low.

  • Transient voltage dip.




Remedy:

  • Check the voltage and parameters on the Undervoltage phase loss menu (607).


F031
Incorrect configuration

Cause:

  • HMI block replaced by an HMI block configured on a drive with a different rating.

  • The current configuration of customer parameters is inconsistent.




Remedy:

  • Return to factory settings or retrieve the backup configuration, if it is valid.

  • If the fault remains after reverting to the factory settings, contact your local Schneider Electric representative.


F032
Invalid configuration

Cause:

  • Invalid configuration.

  • The configuration loaded in the drive via the bus/communication network is inconsistent.

  • The configuration upload has been interrupted or is not fully finished.




Remedy:

  • Check the configuration loaded previously.

  • Load a compatible configuration.


F034
Download invalid configuration

Cause: When save parameter setting or restore to factory setting, the drive detects invalid configuration.



Remedy:

  • Power cycle drive.

  • Restore to factory setting.

  • If the fault remains after reverting to the factory settings, contact your local Schneider Electric representative.



InIt:



Auto-initialization on start

Cause:




  • Macro controller initialization.

  • Searching communication configuration.




Remedy:





COM.E (Flashing)



Communication error

Cause:




  • 50 ms time out error.

  • This message appears after 220 retry attempts.




Remedy:




A-17 (Flashing)



Key alarm

Cause:




  • Key pressed down for longer than 10 seconds.

  • Membrane switch disconnected.

  • Display terminal woken up while a key is being pressed.




Remedy:




cLr (Flashing)



Confirm fault reset

Cause:



This message appears if the STOP key is pressed while the display terminal is displaying a fault.



Remedy:




dEU.E (Flashing)



Drive mismatch

Cause:



Drive type (brand) does not match display terminal type (brand).



Remedy:




rOM.E (Flashing)



ROM abnormality

Cause:



ROM abnormality detected by checksum calculation.



Remedy:




rAM.E (Flashing)



RAM abnormality

Cause:



Display terminal RAM abnormality detected.



Remedy:




CPU.E (Flashing)



Other fault

Cause:



The other detected fault.



Remedy:



How to Clear & Reset Schneider ATV310 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET key on the front control panel. Ensure the cause of the fault has been removed before initiating a reset.
  2. Logic Input Reset (LI): If configured in parameter 601 (Fault reset assignment) in the [FAULT MANAGEMENT] (600-) menu, toggle the assigned digital input (e.g., LI1 to LI4) with a +24V transition.
  3. Automatic Restart: For non-critical trip conditions (e.g., supply undervoltage or transient overvoltage), enable parameter 602.0 (Automatic restart) to automatically reset the drive once line voltage stabilizes.
  4. Modbus Serial Network: Pulse Bit 7 (Fault Reset) from 0 to 1 in the drive Control Word (CMD / register 8501) via embedded RJ45 Modbus RTU communication.
  5. Power Cycle: Disconnect the incoming AC power supply, wait at least 15 minutes for internal capacitors to discharge until the 4-digit LED display goes completely dark, then reapply power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 42VDC across terminals [PA/+] and [PB] (or internal DC bus test points) before opening terminal covers or servicing output terminals U, V, and W on the Schneider Easy Altivar ATV310 drive.