Schneider ATV312 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar 312 (ATV312) compact machine drive. Search or filter through the complete fault code directory below.

Compact Machine Drive Power: 0.18 to 15 kW (0.25 to 20 HP) Integrated Modbus RTU & CANopen
Power Range 0.18 – 15 kW (0.25 – 20 HP)
Supply Voltage 200–240V / 380–500V / 600V
Control Modes Sensorless Vector & V/Hz Control
Operator Interface Integrated Display & Navigation Wheel

Complete Schneider ATV312 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCF, ObF, OHF, or Overheating).

Fault Code and MeaningCause and Remedy
bLF

[BRAKE CONTROL FAULT]

Cause:


  • Brake release current not reached.

  • Brake engage frequency threshold [Brake engage freq] (bEn) = [No] (nO) whereas the brake control [Brake assignment] (bLC) is assigned.

  • Loss of one phase at drive output.

  • Output contactor open.




Remedy:


  • Check the drive/motor connection.

  • Check the motor windings.

  • Check the [Brake release I FW] (Ibr) setting in the [APPLICATION FUNCT.] (FUn-) menu.

  • Apply the recommended settings for [Brake engage freq] (bEn).


CrF

[PRECHARGE FAULT]

Cause:

Precharge relay control or damaged precharge resistor.



Remedy:

Replace the drive.
EEF

[EEPROM FAULT]

Cause:

Internal memory issue.



Remedy:


  • Check the environment (electromagnetic compatibility).

  • Replace the drive.


IF1

[INTERNAL FAULT]

Cause:

Unknown rating.



Remedy:


  • Replace the drive.

  • Restart the drive.

  • Contact a Schneider Electric representative.


IF2

[INTERNAL FAULT]

Cause:


  • HMI card not recognized.

  • HMI card incompatible.

  • No display present.




Remedy:


  • Replace the drive.

  • Restart the drive.

  • Contact a Schneider Electric representative.


IF3

[INTERNAL FAULT]

Cause:

EEPROM issue.



Remedy:


  • Replace the drive.

  • Restart the drive.

  • Contact a Schneider Electric representative.


IF4

[INTERNAL FAULT]

Cause:

Industrial EEPROM issue.



Remedy:


  • Replace the drive.

  • Restart the drive.

  • Contact a Schneider Electric representative.


OCF / o.CF / OC.F

[OVERCURRENT]

Cause:


  • Parameters in the [SETTINGS] (SEt-) and [MOTOR CONTROL] (drC-) menus are incorrect.

  • Inertia or load too high.

  • Mechanical locking.

  • Phase/Ground Motor short-circuit.

  • Impedant short-circuit.




Remedy:


  • Check the parameters in [SETTINGS] (SEt-) and [MOTOR CONTROL] (drC-).

  • Check the size of the motor/drive/load.

  • Check the state of the mechanism.


SCF

[MOTOR SHORT CIRCUIT]

Cause:


  • Short-circuit at the drive output.

  • Significant ground leakage current at the drive output if several motors are connected in parallel.

  • Grounding at the drive output.




Remedy:


  • Check the cables connecting the drive to the motor, and the motor insulation.

  • Reduce the switching frequency.

  • Connect chokes in series with the motor.


SoF

[OVERSPEED]

Cause:


  • Instability.

  • Driving load too high.




Remedy:


  • Check the motor, gain and stability parameters.

  • Add a braking resistor.

  • Check the size of the motor/drive/load.


CnF

[NETWORK FAULT]

Cause:

Communication detected fault on the communication card.



Remedy:


  • Check the environment (electromagnetic compatibility).

  • Check the wiring.

  • Check the time out.

  • Replace the option card.

  • See the [CANopen fault mgt] (COL) parameter to define the stop mode.


CoF

[CANopen FAULT]

Cause:

Interruption in communication on the CANopen bus.



Remedy:


  • Check the communication bus.

  • Refer to the relevant product documentation.


EPF

[EXTERNAL FAULT]

Cause:

Depending on user.



Remedy:

Depending on user.
ILF

[INTERNAL LINK FAULT]

Cause:

Identification detected fault of the communication card by the drive.



Remedy:


  • Check that the option card is compatible with the drive.

  • Replace the option card.


LFF

[4-20mA LOSS]

Cause:

Loss of the 4-20 mA reference on input AI3.



Remedy:

Check the connection on input AI3.
ObF

[OVERBRAKING]

Cause:

Braking too sudden or driving load.



Remedy:


  • Increase the deceleration time.

  • Install a braking resistor if necessary.

  • Activate the [Dec ramp adapt.] (bra) function if compatible with the application.


OHF

[DRIVE OVERHEAT]

Cause:

Drive temperature too high.



Remedy:

Check the motor load, the drive ventilation and the environment. Wait for the drive to cool before restarting.
OLF

[MOTOR OVERLOAD]

Cause:


  • Triggered by excessive motor current.

  • [Cold stator resist.] (rSC) parameter value incorrect.




Remedy:


  • Check the [Mot. therm. current] (ItH) setting of the motor thermal protection, check the motor load. Wait for the drive to cool before restarting.

  • Remeasure [Cold stator resist.] (rSC).


OPF

[MOTOR PHASE LOSS]

Cause:


  • Loss of one phase at drive output.

  • Output contactor open.

  • Motor not connected or motor power too low.

  • Instantaneous instability in the motor current.




Remedy:


  • Check the connections from the drive to the motor.

  • If an output contactor is being used, set [Output Phase Loss] (OPL) to [Output cut] (OAC).

  • Test on a low-power motor or without a motor: In factory settings mode, motor output phase loss detection is active. To check the drive in a test or maintenance environment without having to switch to a motor with the same rating as the drive, deactivate motor phase loss detection ([Output Phase Loss] (OPL) = [No] (nO)).

  • Check and optimize the [IR compensation] (UFr), [Rated motor volt.] (UnS), and [Rated mot. current] (nCr) parameters, and perform an [Auto tuning] (tUn) operation.


OSF

[MAINS OVERVOLTAGE]

Cause:


  • Line voltage is too high.

  • Disturbed line supply.




Remedy:

Check the line voltage.
PHF

[INPUT PHASE LOSS]

Cause:


  • Drive incorrectly supplied or a fuse blown.

  • Failure of one phase.

  • Three-phase ATV312 used on a single-phase line supply.

  • Unbalanced load (protection only operates with the drive on load).




Remedy:


  • Check the power connection and the fuses.

  • Reset.

  • Use a three-phase line supply.

  • Disable the detection by setting [Input phase loss] (IPL) = [No] (nO).


SLF

[MODBUS FAULT]

Cause:


  • Interruption in communication on the Modbus bus.

  • Remote display terminal enabled ([HMI command] (LCC) = [Yes]) and terminal disconnected.




Remedy:


  • Check the communication bus.

  • Refer to the relevant product documentation.

  • Check the link with the remote display terminal.


tnF

[AUTO TUNING FAULT]

Cause:


  • Special motor or motor whose power is not suitable for the drive.

  • Motor not connected to the drive.




Remedy:


  • Use the L ratio or the [Var. torque] (P) ratio (see [U/F mot 1 selected] (UFt)).

  • Check that the motor is present during auto-tuning.

  • If an output contactor is being used, close it during auto-tuning.


CFF

[INCORRECT CONFIG.]

Cause:

  • The current configuration is inconsistent.

  • Addition or removal of an option.




Remedy:



  • Return to factory settings or retrieve the backup configuration, if it is valid. See the [Restore config.] (FCS) parameter.


CFI

[INVALID CONFIG]

Cause:

  • Invalid configuration.

  • The configuration loaded in the drive via the serial link is inconsistent.




Remedy:



  • Check the configuration loaded previously.

  • Load a consistent configuration.


USF

[UNDERVOLTAGE]

Cause:

  • Insufficient line supply.

  • Transient voltage dip.

  • Damaged precharge resistor.




Remedy:



  • Check the voltage and the voltage parameter.

  • Tripping threshold in [UNDERVOLTAGE] (USF):

    ATV312....M2: 160 V

    ATV312....M3: 160 V

    ATV312....N4: 300 V

    ATV312....S6: 430 V

  • Replace the drive.


InIt

Initialization in progress

Cause:

  • The microcontroller is initializing.

  • Search underway for communication configuration.




Remedy:


Wait for initialization to complete.
COM.E (Flashing)

Communication error

Cause:

  • Time out detected fault (50 ms).

  • This message is displayed after 20 attempts at communication.




Remedy:


Check communication connections.
A-17 (Flashing)

Alarm button

Cause:

  • A button has been held down for more than 10 seconds.

  • The keypad is disconnected.

  • The "keypad" wakes up when a button is pressed.




Remedy:


Release the button or check keypad connection.
cLr (Flashing)

Confirmation of detected fault reset

Cause:


This is displayed when the STOP button is pressed once during a remote terminal detected fault.



Remedy:


None required (informational).
dEU.E (Flashing)

Drive disparity

Cause:


The drive brand does not match that of the remote terminal.



Remedy:


Use a compatible remote terminal.
rOM.E (Flashing)

ROM anomaly

Cause:


The remote terminal detects a ROM anomaly on the basis of checksum calculation.



Remedy:


Replace remote terminal.
rAM.E (Flashing)

RAM anomaly

Cause:


The remote terminal detects a RAM anomaly.



Remedy:


Replace remote terminal.
CPU.E (Flashing)

Other detected faults

Cause:


Other detected faults.



Remedy:


Check drive diagnostics.

How to Clear & Reset Schneider ATV312 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET button located on the front navigation panel after resolving the fault condition. Ensure run commands on digital input terminals LI1..LI6 are removed before pressing reset.
  2. Logic Input Reset (LI): If a logic input is configured for fault reset in menu [FAULT MANAGEMENT] (FLt-) > [FAULT RESET] (rSF-), toggle the assigned digital input terminal (e.g., LI2 to LI6) high.
  3. SoMove PC Software: Connect via the front Modbus RJ45 port using a USB-to-RS485 adapter cable, open SoMove software, and click “Fault Reset” in the monitoring dashboard.
  4. Communication Control Word: Set Bit 7 (Fault Reset) from `0` to `1` in the Command Word (CMD) via integrated Modbus RTU or CANopen network interfaces.
  5. Power Cycle: Disconnect main AC line power, wait until the 4-digit 7-segment display turns off completely, and wait at least 15 minutes for the DC bus capacitors to fully discharge before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 42VDC across terminals [PA/+] and [PC/-] before removing terminal covers, servicing motor leads, or touching output terminals U, V, and W on the Schneider Altivar 312 drive.