Schneider ATV340 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip error causes, and step-by-step troubleshooting procedures for the Schneider Electric Altivar Machine ATV340 high-performance inverter series. Search or filter through the complete fault code directory below.

Altivar Machine Drive Power: 0.75 to 75 kW (1.0 to 100 HP) Embedded Safe Torque Off (STO SIL 3)
Power Range 0.75 – 75 kW (1 – 100 HP)
Supply Voltage 380–480V AC (3-Phase)
Control Modes Open/Closed Loop Vector & V/Hz
Operator Interface Graphic Keypad Terminal & Embedded Ethernet

Complete Schneider ATV340 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OCF, ObF, SOF, or Overheating).

Fault Code and MeaningCause and Remedy
NOA

[No Warning stored]

Cause: No warning stored.



Remedy:

  • No action required.


FRF

[Fallback Frequency]

Cause: Reaction on event: Fallback frequency.



Remedy:

  • Check fallback configuration settings.


RLS

[Speed Maintained]

Cause: Reaction on event: Speed maintained.



Remedy:

  • Check event reaction settings.


STT

[Type of stop]

Cause: Reaction on event: Stop following [Type of stop] STT without triggering an error.



Remedy:

  • Verify stop configuration and event triggers.


SRA

[Ref Frequency Warning]

Cause: Frequency reference reached.



Remedy:

  • Information only; verify system reference.


PEE

[PID error Warning]

Cause: PID error warning.



Remedy:

  • Check PID gain settings and feedback loop.


PFA

[PID Feedback Warn]

Cause: PID feedback warning.



Remedy:

  • Check feedback signal integrity.


PFAH

[PID High Fdbck Warn]

Cause: PID feedback high threshold reached.



Remedy:

  • Check for high feedback signal levels.


PFAL

[PID Low Fdbck Warn]

Cause: PID feedback low threshold reached.



Remedy:

  • Check for signal loss or low feedback levels.


LSA

[Limit Switch Reached]

Cause: Limit switch reached.



Remedy:

  • Check mechanical limit switch position.


RSDA

[Slack Rope Warning]

Cause: Slack rope warning.



Remedy:

  • Check rope tension and mechanics.


DLDA

[Dynamic Load Warning]

Cause: Dynamic load warning.



Remedy:

  • Check load stability and dynamics.


TP3A

[AI3 Th Warning]

Cause: AI3 Thermal warning.



Remedy:

  • Check temperature at Analog Input 3.


TP4A

[AI4 Th Warning]

Cause: AI4 Thermal warning.



Remedy:

  • Check temperature at Analog Input 4.


TP5A

[AI5 Th Warning]

Cause: AI5 Thermal warning.



Remedy:

  • Check temperature at Analog Input 5.


AP1

[AI1 4-20 Warning]

Cause: AI1 4-20 mA loss warning.



Remedy:

  • Verify 4-20mA signal on Analog Input 1.


AP3

[AI3 4-20 Warning]

Cause: AI3 4-20 mA loss warning.



Remedy:

  • Verify 4-20mA signal on Analog Input 3.


AP4

[AI4 4-20 Warning]

Cause: AI4 4-20 mA loss warning.



Remedy:

  • Verify 4-20mA signal on Analog Input 4.


AP5

[AI5 4-20 Warning]

Cause: AI5 4-20 mA loss warning.



Remedy:

  • Verify 4-20mA signal on Analog Input 5.


THA

[Device Therm Warn]

Cause: Drive overheating warning.



Remedy:

  • Check drive cooling fans and ambient temperature.


TJA

[IGBT Thermal Warning]

Cause: IGBT thermal state warning.



Remedy:

  • Reduce load or check drive sizing.


FCTA

[Fan Counter Warning]

Cause: Fan counter speed warning.



Remedy:

  • Check fan operation and service life.


FFDA

[Fan Feedback Warning]

Cause: Fan feedback warning.



Remedy:

  • Check fan feedback connections and obstructions.


BOA

[BR Thermal Warning]

Cause: Braking resistor thermal warning.



Remedy:

  • Check braking resistor cooling and duty cycle.


EFA

[Ext. Error Warning]

Cause: External error warning.



Remedy:

  • Investigate external device status.


USA

[Undervoltage Warning]

Cause: Undervoltage warning.



Remedy:

  • Check mains supply voltage stability.


UPA

[Preventive UnderV Active]

Cause: Controlled stop threshold is reached.



Remedy:

  • Check power supply capacity during load peaks.


FTA

[Mot Freq High Thd]

Cause: Motor frequency high threshold 1 reached.



Remedy:

  • Verify motor speed matches process requirements.


FTAL

[Mot Freq Low Thd]

Cause: Motor frequency low threshold 1 reached.



Remedy:

  • Check for mechanical stalling or low reference.


FQLA

[Pulse Warn Thd Reached]

Cause: Pulse warning threshold reached.



Remedy:

  • Check pulse input configuration.


F2AL

[Mot Freq Low Thd 2]

Cause: Motor frequency low threshold 2 reached.



Remedy:

  • Check secondary frequency thresholds.


FLA

[High Speed Reached]

Cause: High speed reached warning.



Remedy:

  • Check max speed parameters.


RTAH

[Ref Freq High Thd reached]

Cause: Reference frequency high threshold reached.



Remedy:

  • Check control system reference signals.


RTAL

[Ref Freq Low Thd reached]

Cause: Reference frequency low threshold reached.



Remedy:

  • Check control system reference signals.


F2A

[2nd Freq Thd Reached]

Cause: Motor frequency high threshold 2 reached.



Remedy:

  • Check secondary frequency limits.


CTA

[Current Thd Reached]

Cause: Motor current high threshold reached.



Remedy:

  • Check for mechanical overload or jamming.


CTAL

[Low Current Reached]

Cause: Motor current low threshold reached.



Remedy:

  • Check for belt breakage or dry running.


TTHA

[High Torque Warning]

Cause: High torque threshold reached.



Remedy:

  • Check process load and mechanical coupling.


TTLA

[Low Torque Warning]

Cause: Low torque threshold reached.



Remedy:

  • Check for load decoupling or fluid loss.


ULA

[Process Undld Warning]

Cause: Process underload warning.



Remedy:

  • Inspect system for underload conditions.


OLA

[Process Overload Warning]

Cause: Overload warning.



Remedy:

  • Inspect system for overload conditions.


SSA

[Torque Limit Reached]

Cause: Torque limit reached.



Remedy:

  • Check torque limit parameters and load.


RTA

[Torque Control Warning]

Cause: Torque control warning.



Remedy:

  • Verify torque control mode settings.


TAD

[Dev Thermal reached]

Cause: Drive thermal threshold reached.



Remedy:

  • Clean heatsink and check fans.


TSA

[Motor Therm Thd reached]

Cause: Motor thermal threshold reached.



Remedy:

  • Check motor cooling and duty cycle.


TS2

[Mot2 Therm Thd reached]

Cause: Motor 2 thermal threshold reached.



Remedy:

  • Check Motor 2 cooling.


TS3

[Mot3 Therm Thd reached]

Cause: Motor 3 thermal threshold reached.



Remedy:

  • Check Motor 3 cooling.


TS4

[Mot4 Therm Thd reached]

Cause: Motor 4 thermal threshold reached.



Remedy:

  • Check Motor 4 cooling.


PTHA

[Power High Threshold]

Cause: Power high threshold reached.



Remedy:

  • Monitor system power consumption.


PTHL

[Power Low Threshold]

Cause: Power low threshold reached.



Remedy:

  • Monitor system power consumption.


CAS1

[Cust Warning 1]

Cause: Customer warning 1 active.



Remedy:

  • Check user-defined logic or inputs.


CAS2

[Cust Warning 2]

Cause: Customer warning 2 active.



Remedy:

  • Check user-defined logic or inputs.


CAS3

[Cust Warning 3]

Cause: Customer warning 3 active.



Remedy:

  • Check user-defined logic or inputs.


CAS4

[Cust Warning 4]

Cause: Customer warning 4 active.



Remedy:

  • Check user-defined logic or inputs.


CAS5

[Cust Warning 5]

Cause: Customer warning 5 active.



Remedy:

  • Check user-defined logic or inputs.


POWD

[Power Cons Warning]

Cause: Power consumption warning.



Remedy:

  • Inspect efficiency and power usage.


ANA

[Slipping warn]

Cause: Slipping warning.



Remedy:

  • Check belts and mechanical coupling.


BSA

[Load Mvt Warn]

Cause: Load movement warning.



Remedy:

  • Check load movement mechanics.


BCA

[Brake Cont Warn]

Cause: Brake contact warning.



Remedy:

  • Check brake contactor state.


TP1A

[AI1 Th Warning]

Cause: AI1 Thermal warning.



Remedy:

  • Check temperature at Analog Input 1.


TLOW

[Current Reduc Warn]

Cause: Current reduction warning.



Remedy:

  • Check load or current limit settings.


MSDA

[M/S Device Warn]

Cause: Master/Slave device warning.



Remedy:

  • Verify Master/Slave communications.


BSQA

[Backlash Warn]

Cause: Backlash warning.



Remedy:

  • Check mechanical gears/coupling for backlash.


TPEA

[Encoder Thermal Warn]

Cause: Encoder module thermal warning.



Remedy:

  • Check encoder temperature and cooling.


TS1A

[Temp Sens AI1 Warn]

Cause: Temperature sensor AI1 warning (open circuit).



Remedy:

  • Check AI1 sensor wiring for breaks.


TS3A

[Temp Sens AI3 Warn]

Cause: Temperature sensor AI3 warning (open circuit).



Remedy:

  • Check AI3 sensor wiring for breaks.


TS4A

[Temp Sens AI4 Warn]

Cause: Temperature sensor AI4 warning (open circuit).



Remedy:

  • Check AI4 sensor wiring for breaks.


TS5A

[Temp Sens AI5 Warn]

Cause: Temperature sensor AI5 warning (open circuit).



Remedy:

  • Check AI5 sensor wiring for breaks.


DCRW

[DC Bus Ripple Warn]

Cause: DC Bus Ripple Warning.



Remedy:

  • Check for phase imbalance or loss.


AFFL

[Fallback Channel]

Cause: Automatic fallback behavior activated after a fieldbus communication interruption.



Remedy:

  • Check fieldbus network cables.


IWA

[MonitorCircuit A Warn]

Cause: Monitoring circuit A warning.



Remedy:

  • Check internal monitoring circuit A.


IWB

[MonitorCircuit B Warn]

Cause: Monitoring circuit B warning.



Remedy:

  • Check internal monitoring circuit B.


IWC

[MonitorCircuit C Warn]

Cause: Monitoring circuit C warning.



Remedy:

  • Check internal monitoring circuit C.


IWD

[MonitorCircuit D Warn]

Cause: Monitoring circuit D warning.



Remedy:

  • Check internal monitoring circuit D.


LKON

[ON Lock Warning]

Cause: ON lock warning resulting from an external device not ready.



Remedy:

  • Ensure external device is ready.


INFM

[Internal Error 22]

Cause: Internal error 22 (Embedded Ethernet).



Remedy:

  • Restart device or contact support if persists.


RFTA

[Pwr Backup Warn]

Cause: Power backup mode warning.



Remedy:

  • Check status of backup power supply.


SLF1

[Modbus Com Inter.]

Cause: Modbus communication interruption warning.



Remedy:

  • Check Modbus wiring and termination.


AnF

[Load slipping]

Cause: Not following the ramp. The difference between the output frequency and the speed feedback is not correct.



Remedy:

  • Confirm the drive rating according to the application (motor, load, etc).

  • Verify the motor, gain, and stability parameters.

  • Add a braking resistor.

  • Verify the mechanical coupling and wiring of the encoder.

  • If torque control is used with encoder speed feedback:

    • Set [Load slip detection] Sdd = [No].

    • Set [Positive deadband] dbP and [Negative deadband] dbn to a value less than 10% of nominal motor frequency.




ASF

[Angle error]

Cause: This error is triggered during the phase-shift angle measurement if the motor phase is disconnected or if the motor inductance is too high.



Remedy:

  • Verify the motor phases and the maximum current allowed by the drive.


bLF

[Brake Control]

Cause:

  • Brake release current not reached.

  • The torque set point is not reached.

  • The fluxing current is not stable.





Remedy:

  • Verify the drive/motor connection.

  • Verify the motor windings.

  • Verify the [Brk Release Current] Ibr and [Brake release I Rev] Ird settings.

  • (Note: This error requires a power reset).


bOF

[Brake Resistor ovld]

Cause: The braking resistor is overloaded.



Remedy:

  • Wait for the braking resistor to cool down.

  • Verify the nominal power of the braking resistor.

  • Verify the [Braking Resistor Power] brP and [Braking Resistor Value] brv parameters.


brF

[Brake Feedback]

Cause:

  • Brake feedback contact status incorrect compared to logic control.

  • Brake does not stop motor quickly enough.





Remedy:

  • Verify the brake feedback circuit.

  • Verify the brake logic control circuit.

  • Verify the brake behavior.

  • Verify settings for [Brake Release Time] brt, [Brake Engage Time] bEt, [Brake Fdbk Filter] FbC, etc.


bSqF

[Backlash Error]

Cause: The torque threshold used for backlash function cannot be reached after [BL Monit Delay] bqt.



Remedy:

  • Verify the settings.

  • Verify the coupling.


bUF

[DB unit sh. circuit]

Cause:

  • Short-circuit from braking unit.

  • Braking unit not connected (not applicable for drive system braking unit option).





Remedy:

  • Verify the wiring of the braking unit.

  • Verify that the braking unit value is not too low.

  • (Note: This error requires a power reset).


bUFo

[DB unit op. circuit]

Cause:

  • Open circuit from braking circuit and/or braking resistor.

  • Braking resistor not connected/detected.





Remedy:

  • Verify the wiring of the braking resistor.

  • Verify by measurement that the resistance of the braking resistor is not too high.

  • Verify the parameter br1.

  • (Note: This error requires a power reset).


CbF

[Circuit Breaker Error]

Cause: The DC bus voltage level is not correct compared to the circuit breaker logic control after the configured timeout.



Remedy:

  • Verify the circuit breaker logic control (pulse time for start and stop).

  • Verify the mechanical state of the circuit breaker.

  • (Note: This error requires a power reset).


CFF

[Incorrect Configuration]

Cause:

  • Option module changed or removed.

  • Control board replaced by a board configured with a different rating.

  • Current configuration is inconsistent.





Remedy:

  • Verify that there is no detected error on the option module.

  • Return to factory settings or retrieve the backup configuration if it is valid.


CFi

[Invalid Configuration]

Cause: Invalid configuration. The configuration loaded via tool or fieldbus is inconsistent.



Remedy:

  • Verify the loaded configuration.

  • Load a valid configuration.


CFi2

[Conf Transfer Error]

Cause:

  • The configuration transfer to the drive was not successful or interrupted.

  • The configuration loaded is not compatible with the drive.





Remedy:

  • Verify the configuration loaded previously.

  • Load a compatible configuration.

  • Perform a factory setting.


CFi3

[Pre-settings Transfer Error]

Cause: The configuration transfer to the drive was not successful or interrupted.



Remedy:

  • Contact your local Schneider Electric representative.


CFi4

[Empty Configuration]

Cause: The selected configuration for the [Multimotors config] has not been created previously.



Remedy:

  • Verify the configurations saved.

  • Switch to a compatible configuration.


CnF

[Fieldbus Com Interrupt]

Cause: Communication interruption on fieldbus module.



Remedy:

  • Verify the environment (electromagnetic compatibility).

  • Verify the wiring and timeout.

  • Replace the option module.


CoF

[CANopen Com Interrupt]

Cause: Communication interruption on the CANopen® fieldbus.



Remedy:

  • Verify the communication fieldbus.

  • Verify the timeout.

  • Refer to the CANopen® manual.


CrF1

[Precharge Capacitor]

Cause: Charging circuit control detected error or charging resistor damaged. Supply mains too low.



Remedy:

  • Turn off the drive and then turn on again.

  • Verify the internal connections.

  • Verify the voltage and the parameters of [Undervoltage handling].


CSF

[Channel Switch Error]

Cause: Switch to an invalid channel.



Remedy:

  • Verify the function parameters.


dCrE

[DC Bus Ripple Error]

Cause: Persistent ripple observed on the DC bus or DC bus capacitors damaged.



Remedy:

  • Turn off the drive and then turn on again.

  • Verify correct behavior of the input filter.

  • Verify the mains wirings and internal connections.

  • (Note: This error requires a power reset).


dLF

[Dynamic Load Error]

Cause: Load variation out of range.



Remedy:

  • Verify for a mechanical cause of load instability.


ECF

[Encoder Coupling]

Cause: The mechanical coupling of the encoder is broken. Detection active when [Encoder Coupling Monit] is Yes.



Remedy:

  • Verify the mechanical coupling of the encoder.


EEF1

[EEPROM Control]

Cause: An error of the internal memory of the control block has been detected.



Remedy:

  • Verify the environment (electromagnetic compatibility).

  • Switch off the product.

  • Return to factory settings.

  • (Note: This error requires a power reset).


EEF2

[EEPROM Power]

Cause: An error of the internal memory of the power board has been detected.



Remedy:

  • Verify the environment (electromagnetic compatibility).

  • Switch off the product.

  • Return to factory settings.

  • (Note: This error requires a power reset).


EnF

[Encoder]

Cause: Encoder feedback error. Difference between measured and estimated speed is > 4%.



Remedy:

  • Verify the configuration parameters for the encoder used.

  • Verify the mechanical and electrical operation of the encoder.

  • Verify consistency between encoder signals and direction of rotation.

  • If necessary, reverse rotation direction via [Output Ph rotation] PHr.

  • Verify the encoder module and supply voltage.


EPF1

[External Error]

Cause: Event triggered by an external device (depending on user settings) or Ethernet configuration file corrupted.



Remedy:

  • Remove the cause of the external error.

  • Perform a factory setting of the Ethernet configuration or modify IP Mode.


EPF2

[Fieldbus Error]

Cause: Event triggered by an external device, depending on user.



Remedy:

  • Remove the cause of the external error.


EtHF

[Embd Eth Com Interrupt]

Cause: Communication interruption on the Ethernet IP ModbusTCP bus.



Remedy:

  • Verify the communication bus.

  • Refer to the Ethernet manual.


FCF1

[Out Contact Closed Error]

Cause: The output contactor remains closed although the opening conditions have been met.



Remedy:

  • Verify the output contactor and its wiring.

  • Verify the contactor feedback wiring.

  • (Note: This error requires a power reset).


FCF2

[Out Contact Opened Error]

Cause: The output contactor remains opened although the closing conditions have been met.



Remedy:

  • Verify the output contactor and its wiring.

  • Verify the contactor feedback wiring.


Fdr1

[FDR 1 Error]

Cause:

  • Embedded Ethernet FDR error.

  • Communication interruption between drive and PLC.

  • Drive rating not consistent with configuration file.





Remedy:

  • Verify the drive and PLC connection.

  • Verify the communication workload.

  • Restart the transfer of configuration file from drive to PLC.


Fdr2

[FDR 2 Error]

Cause:

  • Ethernet fieldbus module FDR error.

  • Configuration file incompatible, empty, or corrupted.





Remedy:

  • Verify the drive and PLC connection.

  • Verify the communication workload.

  • Restart the transfer of configuration file from drive to PLC.


FWEr

[Firmware Update Error]

Cause: Firmware update function has detected an error.



Remedy:

  • Contact your local Schneider Electric representative.


HCF

[Boards Compatibility]

Cause: Hardware configuration error. [Pairing password] enabled and option module changed.



Remedy:

  • Refit the original option module.

  • Confirm the configuration by entering the [Pairing password] PPI if the module was changed deliberately.


IFA

[MonitorCircuit A Error]

Cause: The digital input assigned to [MonitorCircuit A Assign] is active for longer than delay.



Remedy:

  • Verify the connected device and its wiring.

  • Verify the parameter assignment.


IFb

MonitorCircuit B Error

Cause:

The digital input assigned to [MonitorCircuit B Assign] IFAb is active for longer than [MonitorCircuit B Delay] IFdb.



Remedy:

  • Verify the connected device and its wiring.

  • Verify the [MonitorCircuit B Assign] IFAB parameter assignment.

  • Note: This detected error can be cleared with the [Auto Fault Reset] ATR or manually with the [Fault Reset Assign] RSF parameter.


IFC

MonitorCircuit C Error

Cause:

The digital input assigned to [MonitorCircuit C Assign] IFAC is active for longer than [MonitorCircuit C Delay] IFdC.



Remedy:

  • Verify the connected device and its wiring.

  • Verify the [MonitorCircuit C Assign] IFAC parameter assignment.

  • Note: This detected error can be cleared with the [Auto Fault Reset] ATR or manually with the [Fault Reset Assign] RSF parameter.


IFd

MonitorCircuit D Error

Cause:

The digital input assigned to [MonitorCircuit D Assign] IFAd is active for longer than [MonitorCircuit D Delay] IFdd.



Remedy:

  • Verify the connected device and its wiring.

  • Verify the [MonitorCircuit D Assign] IFAd parameter assignment.

  • Note: This detected error can be cleared with the [Auto Fault Reset] ATR or manually with the [Fault Reset Assign] RSF parameter.


iHF

Input Overheating

Cause:

The AFE brick temperature is too high.



Remedy:

  • Verify the drive ventilation and the ambient temperature. Wait for the drive to cool down before restarting.

  • Note: This detected error can be cleared with the [Auto Fault Reset] ATR or manually with the [Fault Reset Assign] RSF parameter.


ILF

Internal Link Error

Cause:

Communication interruption between option module and the drive.



Remedy:

  • Verify the environment (electromagnetic compatibility).

  • Verify the connections.

  • Replace the option module.

  • Contact your local Schneider Electric representative.


InF0

Internal Error 0

Cause:

Communication interruption between microprocessors of the control board, or the power board rating is not valid.



Remedy:

  • Contact your local Schneider Electric representative.


InF1

Internal Error 1

Cause:

The power board rating is not valid.



Remedy:

  • Contact your local Schneider Electric representative.


InF2

Internal Error 2

Cause:

The power board is incompatible with the control block software.



Remedy:

  • Contact your local Schneider Electric representative.


InF3

Internal Error 3

Cause:

Internal communication detected error.



Remedy:

  • Verify the wiring on drive control terminals (internal 10V supply for analog inputs overloaded).

  • Contact your local Schneider Electric representative.


InF4

Internal Error 4

Cause:

Internal data inconsistent.



Remedy:

  • Contact your local Schneider Electric representative.


InF6

Internal Error 6

Cause:


  • The option module installed in the drive is not recognized.

  • The removable control terminal modules (if existing) are not present or not recognized.

  • The embedded Ethernet adapter is not recognized.




Remedy:

  • Verify the catalog number and compatibility of the option module.

  • Plug the removable control terminal modules after the drive has been switched off.

  • Contact your local Schneider Electric representative.


InF7

Internal Error 7

Cause:

Communication interruption with CPLD component of Control board.



Remedy:

  • Contact your local Schneider Electric representative.


InF8

Internal Error 8

Cause:

The internal power switching supply is not correct.



Remedy:

  • Contact your local Schneider Electric representative.


InF9

Internal Error 9

Cause:

An error on the current circuit measurement has been detected.



Remedy:

  • Contact your local Schneider Electric representative.


InFA

Internal Error 10

Cause:

The input stage is not operating correctly.



Remedy:

  • Contact your local Schneider Electric representative.


InFb

Internal Error 11

Cause:

The internal drive thermal sensor is not operating correctly.



Remedy:

  • Contact your local Schneider Electric representative.


InFC

Internal Error 12

Cause:

Internal current supply error.



Remedy:

  • Contact your local Schneider Electric representative.


InFd

Internal Error 13

Cause:

Differential current deviation.



Remedy:

  • Contact your local Schneider Electric representative.


InFE

Internal Error 14

Cause:

Internal microprocessor detected error.



Remedy:

  • Verify that the error code can be cleared.

  • Contact your local Schneider Electric representative.


InFF

Internal Error 15

Cause:

Serial memory flash format error.



Remedy:

  • Contact your local Schneider Electric representative.


InFG

Internal Error 16

Cause:

Communication interruption or internal error of output relays option module.



Remedy:

  • Verify that the option module is correctly connected to the slot.

  • Replace the option module.

  • Contact your local Schneider Electric representative.


InFH

Internal Error 17

Cause:

Communication interruption with the Extension module of digital & analog I/O or internal error of the Extension module of digital & analog I/O.



Remedy:

  • Verify that the option module is correctly connected to the slot.

  • Replace the option module.

  • Contact your local Schneider Electric representative.


InFi

Internal Error 18

Cause:

Safety Module Internal Error (Communication interruption or internal error).



Remedy:

  • Verify the Safety Module errors for additional information.

  • Verify that the option module is correctly inserted into the slot.

  • Replace the option module.

  • Contact your local Schneider Electric representative.


InFJ

Internal Error 19

Cause:

An error on the encoder module has been detected.



Remedy:

  • Verify if the encoder option module is connected correctly to the slot.

  • Verify the compatibility of the encoder.

  • Contact your local Schneider Electric representative.


InFk

Internal Error 20

Cause:

Option module interface board error.



Remedy:

  • Contact your local Schneider Electric representative.


InFL

Internal Error 21

Cause:

Internal Real Time Clock error. It could be a communication error between the keypad and the drive or a clock oscillator start error.



Remedy:

  • Contact your local Schneider Electric representative.


InFM

Internal Error 22

Cause:

An error on the embedded Ethernet adapter has been detected.



Remedy:

  • Verify the connection to the Ethernet port.

  • Contact your local Schneider Electric representative.


InFP

Internal Error 25

Cause:

Incompatibility between Control Board hardware version and firmware version.



Remedy:

  • Update the firmware package.

  • Contact your local Schneider Electric representative.


InFr

Internal Error 27

Cause:

Diagnostics in CPLD have detected an error.



Remedy:

  • Contact your local Schneider Electric representative.


LCF

Input Contactor

Cause:

The drive is not switched on even though [Mains V. time out] LCt timeout has elapsed.



Remedy:

  • Verify the input contactor and its wiring.

  • Verify the [Mains V. time out] LCt timeout.

  • Verify the supply mains/contactor/drive wiring.


LFF1

AI1 4-20mA loss

Cause:

Loss of the 4-20 mA on analog input AI1. This error is triggered when the measured current is below 2 mA.



Remedy:

  • Verify the connection on the analog inputs.

  • Verify the setting of [AI1 4-20mA loss] LFL1 parameter.


LFF3

AI3 4-20mA loss

Cause:

Loss of the 4-20 mA on analog input AI3. This error is triggered when the measured current is below 2 mA.



Remedy:

  • Verify the connection on the analog inputs.

  • Verify the setting of [AI3 4-20mA loss] LFL3 parameter.


LFF4

AI4 4-20mA loss

Cause:

Loss of the 4-20 mA on analog input AI4. This error is triggered when the measured current is below 2 mA.



Remedy:

  • Verify the connection on the analog inputs.

  • Verify the setting of [AI4 4-20mA loss] LFL4 parameter.


LFF5

AI5 4-20mA loss

Cause:

Loss of the 4-20 mA on analog input AI5. This error is triggered when the measured current is below 2 mA.



Remedy:

  • Verify the connection on the analog inputs.

  • Verify the setting of [AI5 4-20mA loss] LFL5 parameter.


LKon

ON Lock Error

Cause:

External device not ready.



Remedy:

  • Verify external device assigned to ON lock input.


MdCF

Load Mvt Error

Cause:

Load movement for which no command has been given.



Remedy:

  • Verify the brake command circuit. Verify the brake.

  • Note: This detected error requires a power reset.


MdLF
[MultiDrive Link Error]

Cause:

  • The communication has been interrupted while running.

  • The function has detected an inconsistency in the system configuration.




Remedy:

  • Check the communication network.

  • Check the configuration of the multi-drive link function.


MSdF
[M/S Device Error]

Cause:

  • For a master, one or more slaves are not present or not ready.

  • For a slave, the master is not present.




Remedy:

  • Verify the drive status.

  • Verify the settings of the master/slave architecture.


ObF
[DC Bus Overvoltage]

Cause:

  • Deceleration time too short or driving load too high.

  • Supply mains voltage too high.




Remedy:

  • Increase the deceleration time.

  • Configure the [Dec ramp adapt.] (brA) function if it is compatible with the application.

  • Verify the supply mains voltage.


OCF
[Overcurrent]

Cause:

  • Parameters in the [Motor data] menu are not correct.

  • Inertia or load too high.

  • Mechanical locking.




Remedy:

  • Verify the motor parameters.

  • Verify the size of the motor/drive/load.

  • Verify the state of the mechanism.

  • Decrease [Current limitation] (CLI).

  • Increase the switching frequency.


OHF
[Drive Overheating]

Cause: Drive temperature too high.



Remedy:

  • Verify the motor load, the drive ventilation, and the ambient temperature. Wait for the drive to cool down before restarting.


OLC
[Process Overload]

Cause: Process overload.



Remedy:

  • Verify and remove the cause of the overload.

  • Verify the parameters of the [Process overload] (OLd) function.


OLF
[Motor Overload]

Cause: Triggered by excessive motor current.



Remedy:

  • Verify the setting of the motor thermal monitoring.

  • Verify the motor load. Wait for the motor to cool down before restarting.

  • Verify the setting of the following parameters:

    • [Motor Th Current] (ItH)

    • [Motor Thermal Mode] (tHt)

    • [Motor Therm Thd] (ttd)

    • [MotorTemp ErrorResp] (OLL)




OPF1
[Single Output Phase Loss]

Cause: Loss of one phase at drive output.



Remedy:

  • Verify the wiring from the drive to the motor.


OPF2
[Output Phase Loss]

Cause:

  • Motor not connected or motor power too low.

  • Output contactor opened.

  • Instantaneous instability in the motor current.




Remedy:

  • Verify the wiring from the drive to the motor.

  • If an output contactor is being used, set [OutPhaseLoss Assign] (OPL) to [No Error Triggered] (OAC).

  • If the drive is connected to a low-power motor or not connected to a motor: In factory settings mode, motor phase loss detection is active [Output Phase Loss] (OPL) = [OPF Error Triggered] (YES). Deactivate motor phase loss detection [Output Phase Loss] (OPL) = [Function Inactive] (nO).

  • Verify and optimize the following parameters: [IR compensation] (UFr), [Nom Motor Voltage] (UnS) and [Rated mot. current] (nCr) and perform [Autotuning] (tUn).


OSF
[Supply Mains Overvoltage]

Cause:

  • Supply mains voltage too high.

  • Disturbed supply mains.




Remedy:

  • Verify the supply mains voltage.


PGLF
[Program Loading Error]

Cause: Verify that the error code can be cleared.



Remedy:

  • Contact your local Schneider Electric representative.


PGrF
[Program Running Error]

Cause: Verify that the error code can be cleared.



Remedy:

  • Contact your local Schneider Electric representative.


PHF
[Input phase loss]

Cause:

  • Drive incorrectly supplied or a tripped fused.

  • One phase is unavailable.

  • 3-phase Drive used on a single-phase supply mains.

  • Unbalanced load.




Remedy:

  • Verify the power connection and the fuses.

  • Use a 3-phase supply mains.

  • Disable the detected error by [Input phase loss] (IPL) = [No] (nO) if single phase supply mains or DC bus supply is used.


rAdF
[Rotation Angle Monit]

Cause: The monitoring of the rotation angle has detected a too high deviation.



Remedy:

  • Check for mechanical problems in the system.

  • Verify the settings of the monitoring function.


SAFF
[Safety Function Error]

Cause:

  • Debounce time exceeded.

  • Internal hardware error.

  • STOA and STOB have a different status (high/low) for more than 1 second.




Remedy:

  • Verify the wiring of the digital inputs STOA and STOB.

  • Contact your local Schneider Electric representative.


SAVF
[Safety Violation]

Cause:

  • Safety Module Violation Error.

  • Safety Module has detected a violation of defined limits.




Remedy:

  • Verify the Safety Module errors for additional information.

  • Contact your local Schneider Electric representative.


SCF1
[Motor short circuit]

Cause: Short-circuit or grounding at the drive output.



Remedy:

  • Verify the cables connecting the drive to the motor, and the motor insulation.

  • Adjust the switching frequency.

  • Connect chokes in series with the motor.

  • Verify the adjustment of speed loop and brake.

  • Increase the [Time to restart] (ttr).


SCF3
[Ground Short Circuit]

Cause: Significant ground leakage current at the drive output if several motors are connected in parallel.



Remedy:

  • Verify the cables connecting the drive to the motor, and the motor insulation.

  • Adjust the switching frequency.

  • Connect chokes in series with the motor.

  • If you have long cables, verify the setting of [Ground Fault Activation] (GrFL).


SCF4
[IGBT Short Circuit]

Cause:

  • Power component detected error.

  • At product power-on, the IGBTs are tested for short circuit. The time to check each transistor is between 1 and 10 µs.




Remedy:

  • Verify the setting of [Output Short Circuit Test] (Strt) parameter.

  • Contact your local Schneider Electric representative.


SCF5
[Motor Short Circuit]

Cause: Short-circuit at drive output.



Remedy:

  • Verify the cables connecting the drive to the motor, and the motor's insulation.

  • Contact your local Schneider Electric representative.


SCFF
[Safety Config Error]

Cause:

  • Safety Module Configuration Error.

  • Incorrect configuration linked to the Safety Module has been detected.




Remedy:

  • Verify the Safety Module errors for additional information.

  • Contact your local Schneider Electric representative.


SLF1
[Modbus Com Interruption]

Cause: Communication interruption on the Modbus port.



Remedy:

  • Verify the communication bus.

  • Verify the timeout.

  • Refer to the Modbus user manual.


SLF2
[PC Com Interruption]

Cause: Communication interruption with the commissioning software.



Remedy:

  • Verify the commissioning software connecting cable.

  • Verify the timeout.


SLF3
[HMI Com Interruption]

Cause:

  • Communication interruption with the Graphic display terminal.

  • This error is triggered when the command or reference value are given using the Graphic Display Terminal and if the communication is interrupted during more than 2 seconds.




Remedy:

  • Verify the Graphic display terminal connection.

  • Verify the timeout.


SIOF
[Safety IO Error]

Cause:

  • Safety Module IO Error.

  • Error on input / output of the Safety Module.

  • Error on encoder signal.




Remedy:

  • Verify the Safety Module errors for additional information.

  • Contact your local Schneider Electric representative.


SoF
Motor Overspeed

Cause:


Instability or driving load too high. If a downstream contactor is used, the contacts between the motor and the drive have not been closed before applying a Run command. The overspeed threshold (corresponding to 110% of [Max frequency] tFr) has been reached.



Remedy:

  • Verify the motor parameter settings.

  • Verify the size of the motor/drive/load.

  • Verify and close the contacts between the motor and the drive before applying a Run command.

  • Verify the consistency between [Max frequency] tFr and [High Speed] HSP. It is recommended to have at least [Max frequency] tFr ≥ 110% * [High Speed] HSP.


SPF
Encoder Feedback Loss

Cause:


This error is triggered if: The measured speed is lower than 2% of [Nominal Motor Freq] FrS; The difference between stator speed and measured speed is > 20% of FrS; EMC perturbations; No input signal; Encoder feedback missing; Supply voltage missing; Broken wire.



Remedy:

  • Verify the error code value [Encoder Fdbck Error] EnCE.

  • Verify the wiring between the encoder and the drive.

  • Verify the encoder.

  • Verify the encoder settings.

  • Verify the wiring of the pulse input and the sensor used.

  • Use a shielded cable and ground both ends.

  • Verify the encoder power supply. Reduce [Encoder Supply Voltage] uECV value.

  • Check the supply voltage of the encoder.


SPFC
Security Files Corrupt

Cause:


Security files corrupted or missing.



Remedy:

  • Switch off the product. At next switch-on, the security file will be created again, and the information related to cybersecurity (such as channel policy and password) are set back to the default value.


SrF
Torque timeout

Cause:


The torque control function is not able to regulate the torque within the configured dead band. The drive has switched to speed control for longer than [Torque ctrl time out] rto.



Remedy:

  • Verify the settings of the [Torque control] tor - function.

  • Verify that there are no mechanical constraints.


SSF
Torque Limitation Error

Cause:


The drive was in torque limitation or current limitation state during [Trq/I Limit Timeout] Sto.



Remedy:

  • Verify the settings of the [Torque limitation] toL - function.

  • Verify that there are no mechanical constraints.


StF
Motor Stall Error

Cause:


The stall monitoring function has detected an error. Triggered if: Output frequency is smaller than [Stall Frequency] StP3; Output current is higher than [Stall Current] StP2; Duration longer than [stall Max Time] StP1.



Remedy:

  • Search for a mechanical blocking of the motor.

  • Search for a possible cause of motor overload.

  • Verify the settings of the monitoring function.


t1CF
AI1 Thermal Sensor Error

Cause:


The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI1: Open circuit or Short circuit.



Remedy:

  • Verify the sensor and its wiring.

  • Replace the sensor.


t3CF
AI3 Thermal Sensor Error

Cause:


The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI3: Open circuit or Short circuit.



Remedy:

  • Verify the sensor and its wiring.

  • Replace the sensor.

  • Verify the setting of [AI3 Type] AI3t parameter.


t4CF
AI4 Thermal Sensor Error

Cause:


The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI4: Open circuit or Short circuit.



Remedy:

  • Verify the sensor and its wiring.

  • Replace the sensor.

  • Verify the setting of [AI4 Type] AI4t parameter.


t5CF
AI5 Thermal Sensor Error

Cause:


The thermal monitoring function has detected an error of the thermal sensor connected to the analog input AI5: Open circuit or Short circuit.



Remedy:

  • Verify the sensor and its wiring.

  • Replace the sensor.

  • Verify the setting of [AI5 Type] AI5t parameter.


tECF
Encoder Th Sensor Error

Cause:


The thermal sensor monitoring function has detected a thermal sensor on the encoder module analog input: Open circuit or Short circuit.



Remedy:

  • Verify the sensor and its wiring.

  • Replace the sensor.


tH1F
AI1 Th Level Error

Cause:


The thermal sensor monitoring function has detected a high temperature on analog input AI1.



Remedy:

  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


tH3F
AI3 Th Level Error

Cause:


The thermal sensor monitoring function has detected a high temperature on analog input AI3.



Remedy:

  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


tH4F
AI4 Th Level Error

Cause:


The thermal sensor monitoring function has detected a high temperature on analog input AI4.



Remedy:

  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


tH5F
AI5 Th Level Error

Cause:


The thermal sensor monitoring function has detected a high temperature on analog input AI5.



Remedy:

  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


tHEF
Encoder Th Detected Error

Cause:


The thermal sensor monitoring function has detected a high temperature on encoder module analog input.



Remedy:

  • Search for a possible cause of overheating.

  • Verify the settings of the monitoring function.


tJF
IGBT Overheating

Cause:


Drive power stage overheating.



Remedy:

  • Verify the size of the load/motor/drive according to environment conditions.

  • Reduce the switching frequency.

  • Increase the ramp time.

  • Decrease the current limitation.


tLoF
Drive Overload

Cause:


The [Drive overload monit] obr - function has detected an error.



Remedy:

  • Verify the size of the load/motor/drive according to environment conditions.

  • Verify the settings of the [Drive Overload Monit] tLoL parameter.


tnF
Autotuning Error

Cause:


Special motor or motor whose power is not suitable for the drive. Motor not connected to the drive. Motor not stopped.



Remedy:

  • Verify that the motor/drive are compatible.

  • Verify that the motor is connected to the drive during autotuning.

  • If an output contactor is being used, verify that it is closed during autotuning.

  • Verify that the motor is present and stopped during autotuning.

  • In case of reluctance motor, reduce [PSI Align Curr Max] MCr.


ULF
Process Underload

Cause:


Process underload.



Remedy:

  • Verify and remove the cause of the underload.

  • Verify the parameters of the [Process underload] uLd - function.


USF
Supply Mains UnderV

Cause:


Supply mains too low. Transient voltage dips.



Remedy:

  • Verify the voltage and the parameters of [Undervoltage handling] uSb.


How to Clear & Reset Schneider ATV340 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET button on the Graphic Display Terminal once the error condition is rectified. Ensure remote run commands (DI or fieldbus) are removed before resetting.
  2. Digital Input Reset (DI): If assigned in [Complete settings] > [Error/Warning handling] > [Fault reset] (parameter rSF), send a 0-to-1 transition pulse to the designated digital input terminal (e.g., DI3 or DI4).
  3. Embedded Web Server & SoMove PC Tool: Connect your PC via the onboard Ethernet RJ45 port or Modbus serial link, open SoMove or access the embedded Web server interface, and click “Fault Reset” in the monitoring status window.
  4. Fieldbus Control Word: Toggle Bit 7 (Fault Reset) from `0` to `1` in the drive Command Word (CMD) via embedded Ethernet/IP, Modbus TCP, Profinet, or CANopen networks.
  5. Mains Power Cycle: Switch off main AC supply line power. Wait until all display LEDs and indicators extinguish completely, and allow a minimum of 15 minutes for the internal DC bus capacitors to fully discharge before repowering.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the intermediate DC bus voltage measures strictly below 42VDC across terminals [PA/+] and [PC/-] before removing terminal covers, inspecting motor cabling, or touching output terminals U, V, and W on the Schneider Altivar Machine ATV340 drive.