KEB Drives Fault Codes & Troubleshooting

Complete diagnostic database for 2 KEB drive series (COMBIVERT F5 & R6). Browse fault codes, error status, causes, and step-by-step fixes for industrial AC inverter, servo, and regenerative systems. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.

1 Inverter & Servo Series 1 Regenerative Unit Series 2 Total Series

KEB COMBIVERT Drive & Regeneration Systems

2 Models

Most Common KEB Drive Fault Codes

Diagnostic Quick Reference
Display Code Hex / Status Fault Description Common Root Cause
E.OC 0x01 Overcurrent Trip Instantaneous peak current limit exceeded; phase-to-phase short on motor terminals U, V, W, jammed mechanical gearbox, or rapid acceleration ramp.
E.OP 0x02 Overpotential (Overvoltage) Intermediate circuit DC bus exceeded maximum threshold; high regenerative energy returned during deceleration without dynamic braking resistor or active R6 unit.
E.UP 0x03 Underpotential (Undervoltage) DC link voltage dropped below allowable operating limit; mains supply failure, severe line voltage sag, or blown upstream input protection fuse.
E.OH / E.dOH 0x05 / 0x06 Heatsink / Drive Overheat Power module or internal enclosure temperature exceeded safety limit; clogged heatsink ventilation channels, internal cooling fan malfunction, or ambient >45°C.
E.OL 0x07 Drive Overload Continuous operation exceeding 100% rated capacity according to thermal model; mechanical binding or undersized drive for continuous load profile.
E.OL2 0x08 Motor Overload Motor electronic thermal protection activated (I²t calculation); sustained low-speed high-torque operation without forced ventilation cooling fan.
E.EnC 0x09 Encoder / Feedback Error Speed feedback signal missing, broken encoder cable, inverted channel connection (A/B), or resolver communication timeout.
E.buS 0x0D Fieldbus Watchdog Timeout Cyclic communication interrupted across fieldbus interface (EtherCAT, CANopen, Profinet); damaged communication patch cable or master PLC cycle stop.

How to Clear & Reset KEB Faults

  1. Keypad Reset: Press the ENTER / RESET key (or toggle the F/R key depending on operator module) on the front digital operator once the error root cause is resolved.
  2. Digital Input Terminal: Apply a 24VDC pulse to the digital input terminal configured for fault reset (e.g., configure parameter di.01–di.08 to option Reset on terminal strip X2A).
  3. COMBIVIS 5 / 6 Software: Connect via diagnostic serial/USB cable or Ethernet, open the diagnostic control panel inside KEB COMBIVIS, and click the “Error Reset” button.
  4. Main Power Disconnect Cycle: Turn off incoming 3-phase AC line power, wait until the internal DC bus voltage completely discharges below 50VDC (minimum 5 minutes), and re-energize the unit.
⚠️ High-Voltage Safety Warning: Hazardous electrical voltages up to 900 VDC remain stored in the intermediate circuit DC bus capacitors after mains supply disconnection. Wait at least 5 minutes and verify with a calibrated digital multimeter across terminals (++) and (–) that the voltage is strictly below 50VDC before inspecting internal wiring or touching motor output terminals.