Toshiba AS1 (VF-AS1) Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba TOSVERT VF-AS1 high-performance industrial inverter series. Search or filter through the complete fault code directory below.

High-Performance Industrial Inverter Power: 0.4 to 500 kW (0.5 to 700 HP) Sensorless & Closed-Loop Vector
Power Range 0.4 – 500 kW (0.5 – 700 HP)
Supply Voltage 200–240V / 380–480V (3-Phase)
Control Modes V/f, Sensorless & Closed-Loop Vector
Operator Interface 4-Digit LED / Optional LCD Panel

Complete Toshiba AS1 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, or Overcurrent).

Fault Code and MeaningCause and Remedy
OC1, OC1P
Overcurrent during acceleration

Cause:
The acceleration time (acc) is too short; V/f setting is improper; Restart signal input to rotating motor; Special motor used; Manual torque boost (vb) is large.



Remedy:

  • Increase the acceleration time (acc).

  • Check the V/f parameter setting.

  • Use UuS (Auto-restart) and UuC (Regenerative power ride-through control).

  • Increase the carrier frequency (CF).

  • Decrease torque boost (vb) setting value.

  • Decrease F601 (stall prevention level) to 130 as a guide.

  • Increase CF (carrier frequency) setting value if it is set at lower value (2kHz or less).


OC2, OC2P
Overcurrent during deceleration

Cause:
The deceleration time (dec) is too short.



Remedy:

  • Increase the deceleration time (dec).


OC3, OC3P
Overcurrent during fixed speed

Cause:
The load fluctuates abruptly; The load is in an abnormal condition.



Remedy:

  • Reduce the load fluctuation.

  • Check the load (operated machine).


OC1P, OC2P, OC3P (Note)
Component Failure / Overheat

Cause:
A main circuit element is defective; Overheat protection is activated.



Remedy:

  • Make a service call.

  • Check operation of cooling fan.

  • Check cooling fan control mode parameter F620.


OCA1
U-phase arm short-circuit

Cause:
A main circuit element is defective (U-phase).



Remedy:

  • Make a service call.


OCA2
V-phase arm short-circuit

Cause:
A main circuit element is defective (V-phase).



Remedy:

  • Make a service call.


OCA3
W-phase arm short-circuit

Cause:
A main circuit element is defective (W-phase).



Remedy:

  • Make a service call.


OCL
Loaded side overcurrent at start time

Cause:
Insulation of output main circuit or motor is defective; Motor has too small impedance; Drive circuit board damaged.



Remedy:

  • Check the cables and wires for defective insulation.

  • Selection of short circuit detection at starting parameter F613.

  • If this error appears when motor is not connected, the inverter may be faulty; make a service call.


OCr
Dynamic braking element overcurrent (110kW or larger)

Cause:
PB-PC/+ circuit is shorted; Resistor with resistance smaller than minimum allowable is connected; Parameter Pb set to 1 or 2 without connecting brake.



Remedy:

  • Check the impedance wiring for the resistor, etc.

  • Make a service call.

  • Check if regenerative brake is connected.

  • If regenerative brake is not necessary, set parameter Pb to 0.


OH
Overheating

Cause:
Cooling fan does not rotate; Ambient temperature too high; Vent blocked; Heat generating device nearby; Thermistor disconnected.



Remedy:

  • Restart operation by resetting inverter after it has cooled down.

  • The fan requires replacement if it does not rotate.

  • Secure sufficient space around the inverter.

  • Do not place any heat generating device near the inverter.

  • Make a service call.


OH2
Thermal trip stop command from external device

Cause:
Input signal impressed at control input terminal PTG; Thermal trip command (input function 46 or 47) issued by external device.



Remedy:

  • The motor is overheated, check whether the current flowing into the motor exceeds the rated current.


OL1
Inverter overload

Cause:
Rapid acceleration; DC braking amount too large; V/f setting improper; Restart signal input to rotating motor; Load too large.



Remedy:

  • Increase the acceleration time (acc).

  • Reduce the DC braking amount F251 and the DC braking time F252.

  • Check the V/f parameter setting.

  • Use UuS (Auto-restart) and UuC (Regenerative power ride-through control).

  • Use an inverter with a larger rating.


OL2
Motor overload

Cause:
V/f parameter improperly set; Motor is locked up; Low-speed operation performed continuously; Excessive load applied.



Remedy:

  • Check the V/f parameter setting.

  • Check the load (operated machine).

  • Check the OLM setting and adjust F606 according to sustainable overload in low-speed range.

  • Reduce the DC braking amount F251 and the DC braking time F252.


OLr
Dynamic braking resistor overload

Cause:
Rapid deceleration is operated; Dynamic braking is too large.



Remedy:

  • Increase the deceleration time (dec).

  • Increase the capacity of dynamic braking resistor (wattage) and adjust PBR capacity parameter Pbr.


OP1
Overvoltage during acceleration

Cause:
Input voltage fluctuates abnormally (Power supply > 500kVA, capacitor opened/closed, thyrister connected); Restart signal input to rotating motor.



Remedy:

  • Insert a suitable input reactor.

  • Use UuS (Auto-restart) and UuC (Regenerative power ride-through control).


OP2
Overvoltage during deceleration

Cause:
Deceleration time (dec) too short; Dynamic braking resistor has large resistance; Pb is OFF; Overvoltage limit F305 is OFF; Input voltage fluctuates.



Remedy:

  • Increase the deceleration time (dec).

  • Install a dynamic braking resistor.

  • Decrease dynamic braking resistance (Also reset the Pbr).

  • Set dynamic braking mode parameter Pb properly.

  • Set overvoltage limit operation F305 properly.

  • Insert a suitable input reactor.


OP3
Overvoltage during fixed speed operation

Cause:
Input voltage fluctuates abnormally; Motor is in regenerative state (load pushes motor).



Remedy:

  • Insert a suitable input reactor.

  • Install a dynamic braking resistor.


Ot
Overtorque

Cause:
Overtorque reaches detection level; Stall prevention performed longer than time set with F452.



Remedy:

  • Check system error.

  • Check whether the motor is overloaded or the brake is engaged.


UC
Low current operation

Cause:
Output current decreased to low-current detection level during operation.



Remedy:

  • Check the suitable detection level for the system (F611).

  • Make a service call if the setting is correct.


UP1
Undervoltage (main circuit)

Cause:
Input voltage too low; Momentary power failure occurs longer than detection time F628.



Remedy:

  • Check the input voltage.

  • To cope with momentary stop, enable UuC (Regenerative ride-through), UuS (auto-restart), and F628.


E
Emergency stop

Cause:
Inverter stopped by panel during auto/remote; Stop command (terminal function 20 or 21) issued by external device.



Remedy:

  • Reset the inverter.


EEP1
EEPROM error

Cause:
A data writing error occurs.



Remedy:

  • Turn off the inverter, then turn it on again. If it does not recover, make a service call.


EEP2
Initial read error

Cause:
Some internal data is corrupted; Power was turned off while typ was being set.



Remedy:

  • Make a service call.

  • Set typ again. If error persists, make a service call.


EEP3
Initial read error

Cause:
Some internal data is corrupted.



Remedy:

  • Make a service call.


EF1, EF2
Ground fault

Cause:
A current leaked from an output cable or the motor to ground.



Remedy:

  • Check the cable and the motor for ground faults.


EPH0
Output phase failure

Cause:
A phase failure occurred in the output line of the main circuit.



Remedy:

  • Check the main circuit output line, motor, etc. for phase failure.

  • Select output phase failure detection parameter F605.


EPH1
Input phase failure

Cause:
A phase failure occurred in the input line of the main circuit.



Remedy:

  • Check the main circuit input line for phase failure.


Err2
Main unit RAM fault

Cause:
The control RAM is defective.



Remedy:

  • Make a service call.


Err3
Main unit ROM fault

Cause:
The control ROM is defective.



Remedy:

  • Make a service call.


Err4
CPU fault

Cause:
The control CPU is defective.



Remedy:

  • Make a service call.


Err5
Communication time-out error

Cause:
Normal communication was not possible for the time set by F803.



Remedy:

  • Check the remote control device, cables, etc.


Err6
Gate array fault

Cause:
Main gate array is defective.



Remedy:

  • Make a service call.


Err7
Output current detector error

Cause:
The main output current detector is defective.



Remedy:

  • Make a service call.


Err8
Optional unit fault

Cause:
An optional device has failed (such as a communication device).



Remedy:

  • Check the connection of optional board(s).

  • Refer to instructions of options concerned.


Etn
Tuning error

Cause:
Motor capacity connected is 2 notches or more smaller than inverter; Motor is not 3-phase inductive; Tuning performed while motor running.



Remedy:

  • Make sure that a motor is connected.

  • Make sure that the motor is at standstill.

  • Perform auto-tuning 1 again and if error persists, perform tuning manually.


Etn1
Tuning detection error

Cause:
Some parameters (F410-F413) not detected; Motor capacity too small; Motor not 3-phase inductive; No motor connected; Cables too long (>30m); Motor running.



Remedy:

  • Make sure that a motor is connected.

  • Make sure that the motor is at standstill.

  • Perform auto-tuning 1 again and if error persists, perform tuning manually.


Etn2
Motor constant value error

Cause:
Some detection values (F410-F413) beyond limits; Motor capacity too small; Motor not 3-phase inductive; Cables too long (>30m); Motor running.



Remedy:

  • Make sure that the motor is at standstill.

  • Perform auto-tuning 1 again and if error persists, perform tuning manually.


Etn3
Motor constant setting error

Cause: Some items indicated on the motor nameplate are not entered correctly.

• Base frequency (uL)

• Base frequency voltage 1 (uLu)

• Motor rated capacity (F405)

• Motor rated current (F406)

• Motor rated speed (F407)



Remedy:

  • Make sure that all items on the motor nameplate are entered correctly.


Etyp
Inverter type error

Cause: Is circuit board (or main circuit/drive circuit board) replaced?



Remedy:

  • When board has been replaced, input 6 for typ.


E-10
Analog input terminal overvoltage

Cause: Overrated voltage is applied to analog input.



Remedy:

  • Apply voltage within the rated voltage.


E-11
Sequence error

Cause: The signal from system is not inputted into input terminals.

The input terminal function (130, 131) is not set up.

A value other than 0.0 is specified for F630, although the brake answer function is not used.



Remedy:

  • Please check if the sequence is normal or not.

  • Please set 130 or 131 as the input terminal to use.

  • Please set up 0.0, when you do not use system-supporting sequence.


E-12
Encoder error

Cause: Disconnection of encoder circuit.

The encoder is not connected correctly.



Remedy:

  • Check connection of encoder.

  • Connect encoder correctly.

  • Check whether the setting of F376 matches the phase-A and phase-B connections of the encoder.


E-13
Speed error (Over speed)

Cause: Encoder error (inverter error).



Remedy:

  • Check connection of encoder.

  • Connect encoder correctly.


E-17
Key failure alarm

Cause: The same key is input continuously more than 20 seconds.



Remedy:

  • Check the operation panel.


E-18
Terminal input error

Cause: Braking down of a wire for VI/II input signal.

Terminal circuit board comes off and falls.

P24 overcurrent.



Remedy:

  • Check VI/II input signal.

  • Install the control terminal board to the inverter.

  • Check P24 terminal short circuit to CC or CCA.


E-19
Abnormal CPU2 communication

Cause: An error arises during CPU2 communication.



Remedy:

  • Make a service call.


E-20
V/f control error

Cause: An internal control error occurs.



Remedy:

  • Make a service call.


E-21
CPU1 fault

Cause: A software error occurs in the control CPU.



Remedy:

  • Make a service call.


E-22
Abnormal logic input voltage

Cause: An abnormal voltage is applied to the control logic input terminal.



Remedy:

  • Check the signal given to the logic connected with the input terminal.


E-23
Option 1 error

Cause: Expansion I/O card 1 is defective.



Remedy:

  • Make a service call.


E-24
Option 2 error

Cause: Expansion I/O card 2 is defective.



Remedy:

  • Make a service call.


E-25
Stop position retaining error

Cause: A deviation error occurs during stop position retaining control.

The stop position adjustment range specified with F381 is too narrow.

Creeping speed is too fast.



Remedy:

  • Check connection of encoder.

  • Adjust the proportional P gain F362.

  • Increase F381.

  • Lower the creeping speed.


E-26
CPU2 fault

Cause: Motor control CPU is defective.

The drive circuit board in the inverter was damaged.



Remedy:

  • Make a service call.


E-29
Control power backup undervoltage error

Cause: The control voltage between +SU and CC terminals is too low.

Control power is not supplied through +SU and CC terminals.

The parameter F647 is not set correctly.



Remedy:

  • Check whether the voltage between +SU and CC terminals is DC20V or more.

  • Set F647 to 0 if a control power backup device is not connected to +SU and CC terminals.

  • To reset the inverter that has been tripped because of this error, turn it off and then back on.


SOut
Step-out (for PM motors only)

Cause: The motor shaft is locked.

One output phase is open.

An impact load is applied.



Remedy:

  • Unlock the motor shaft.

  • Check the interconnect cables between the inverter and the motor.


PrF
Power removal error

Cause: Error of power removal signal.



Remedy:

  • Make a service call.


OFF
ST signal OFF

Cause: ST terminal (terminal to which the ST function is assigned) is in open-circuit.



Remedy:

  • Close ST (terminal to which the ST function is assigned)-CC circuit.


PrA
PWR signal OFF

Cause: PWR terminal is in open-circuit.



Remedy:

  • Close PWR-P24/PLC circuit.


COFF
Control power backup undervoltage

Cause: The control voltage between +SU and CC terminals is too low.

Control power is not supplied through +SU and CC terminals.

The parameter F647 is not set correctly.



Remedy:

  • Check whether the voltage between +SU and CC terminals is DC20V or more.

  • Set F647 to 0 if a control power backup device is not connected to +SU and CC terminals.

  • Note: In the event of a COFF error, the inverter will not be reset automatically even if voltage returns. Turn off and back on to reset.


MOFF
Undervoltage in main circuit

Cause: The supply voltage between R, S and T is under voltage.

Trouble of rush current restraint circuit or DC circuit fuse.



Remedy:

  • Measure the main circuit supply voltage. If the voltage is at a normal level, the inverter requires repairing.

  • Make a service call.


rtry
Retry

Cause: The inverter is in the process of retry.

A momentary stop occurred.



Remedy:

  • The inverter is normal if it restarts after several tens of seconds.

  • The inverter restarts automatically. Be careful of the machine because it may suddenly restart.


Err1
Point setting alarm

Cause: The frequency setting signals at points 1 and 2 are set too close to each other.



Remedy:

  • Set the frequency setting signals at points 1 and 2 apart from each other.


CLr
Clear enabling indication

Cause: This message is displayed when pressing the STOP key while an error code is displayed.

Input terminal RES signal is ON during trip display.



Remedy:

  • Press the STOP key again to clear the trip.

  • Turn off the input terminal RES signal.


EOFF
Emergency stop enabling indication

Cause: The operation panel is used to stop the operation in automatic control or remote control mode.



Remedy:

  • Press the STOP key for an emergency stop. To cancel the emergency stop, press any other key.


HI / LO
Setting error alarm

Cause: An error is found in a setting when data is reading or writing.

(Error code and data displayed alternately).



Remedy:

  • Check whether the setting is made correctly.


db
DC braking

Cause: DC braking in process.



Remedy:

  • The message goes off in several tens of seconds if no problem occurs.


dbOn
Shaft fixing in control

Cause: Motor shaft fixing control is in process.



Remedy:

  • If the message disappears by stop command (ST-CC open), it is normal.


E1 / E2 / E3
Panel indication overflow

Cause: The digit number of the item displayed (e.g., frequency) is in excess of the specified digit number.



Remedy:

  • For indication of frequency, set multiplying rate (F702) lower. (Parameter setting that results in overflow is of course valid.)


init
Parameters in the process of initialization

Cause: Parameters are being initialized to default values.



Remedy:

  • Normal if the message disappears after a while (several seconds to several tens of seconds).


Atn
In auto-tuning 1

Cause: Auto-tuning 1 in process.



Remedy:

  • Normal if the message disappears after a few seconds (6900PL or less) or 2-3 minutes (6110KPC or larger).


LStp
Auto-stop because of continuous operation at lower-limit

Cause: The automatic stop function of F256 is being performed.



Remedy:

  • This function is deactivated when the command frequency becomes 0.2Hz or more higher than the lower-limit frequency (LL) or when a command for stopping operation is entered.


StOP
Momentary power failure slowdown stop

Cause: The deceleration stop function of uuc (regenerative power ride-through control) is activated.



Remedy:

  • To restart operation, reset the inverter or input an operation signal again.


HEAd / End
Display of first/last data items

Cause: First and last data in the AuH group.



Remedy:

  • To exit from the group, press the MODE key.


tun
During learning

Cause: Learning for brake sequence operation or light-load high-speed operation is currently in progress.



Remedy:

  • To cancel learning, suspend it and set learning parameters F329 to 0.


tun1
Brake sequence learning error

Cause: Braking operation is not performed normally.

The load is too heavy.

There are some operation errors.



Remedy:

  • Brake signal output (68, 69) is not assigned to the control output terminal.

  • The brake function mode selection parameter (F341) is not set.

  • Learning is performed while the load is lifted.


tun2
Light-load high-speed learning operation error

Cause: There are some errors in the operation for learning for light-load high-speed operation.



Remedy:

  • Check whether the learning operation for light-load high-speed operation is performed correctly. (Refer to 6.16)


tun3
Light-load high-speed learning overload error

Cause: Learning operation for light-load high-speed operation is performed while the load is lifted.

Motor constants (uL, uLv, F405 to F413) are not entered correctly.



Remedy:

  • Check the load.

  • Check the motor constant setting.


UndO
Key operation permitted temporarily

Cause: This message appears if the ENTER key is pressed and held down for 5 seconds or more when key operation is prohibited by F737.



Remedy:

  • When this message is displayed, all the keys are operational. To prohibit key operation again, turn off the inverter and then turn it back on.


C
Overcurrent pre-alarm

Cause: Same as OC (Overcurrent).



Remedy:

  • Same as OC (Overcurrent).


P
Overvoltage pre-alarm / PBR operation level

Cause: Same as OP (Overvoltage).

P blink while PBR is operating is not an error.



Remedy:

  • Same as OP (Overvoltage).

  • P blink while PBR is operating is not an error.


L
Overload pre-alarm

Cause: Same as OL1 and OL2 (Overload).



Remedy:

  • Same as OL1 and OL2 (Overload).


H
Overheat pre-alarm

Cause: Same as OH (Overheat).



Remedy:

  • Same as OH (Overheat).


t
Communication error

Cause: Various transmission errors occur when computer is linked up with inverter system.

Various transmission errors occur in inverter to inverter communication (slave side). Time-out or trip in master side.



Remedy:

  • For measures to correct various kinds of data transmission errors, refer to the instruction manual for the communications device used specified in Section 6.42.

  • Check the master inverter.


How to Clear & Reset Toshiba AS1 Drive Faults

  1. Keypad Reset: Press the STOP/RESET key on the operation panel twice when a trip code is displayed. The first press acknowledges the trip state, and the second clears the active fault.
  2. Control Terminal Reset (RES): Close the contact between control terminal RES and common terminal CC for at least 0.1 seconds, then reopen. (The RES terminal is factory-assigned to the fault reset function).
  3. Serial Communication Reset: Send an inverter reset command by setting the fault reset bit in the control word via the built-in RS-485 port (Modbus RTU / TOSHIBA protocol) or optional communication bus (DeviceNet, Profibus-DP, CC-Link).
  4. Power Cycle: Switch off the main AC power supply breaker. Wait until the control panel display and the internal CHARGE LED extinguish completely (approx. 10 to 15 minutes for capacitor discharge), then restore input power.
  5. Pre-Reset Safety Check: Always inspect motor insulation and load mechanical integrity prior to resetting high-priority trips such as overcurrent (OC1/OC2/OC3) or ground faults (EF) to prevent permanent IGBT module damage.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] (and confirm the internal red CHARGE lamp has fully extinguished) before touching motor terminals U/T1, V/T2, W/T3 or performing internal wiring work on the Toshiba AS1 drive.