Toshiba Drives Fault Codes & Troubleshooting

Technical diagnostic directory for Toshiba TOSVERT low-voltage inverters, general purpose motor drives, and heavy industrial plant controllers. Select your drive model series below to access parameter checks, trip code descriptions, and physical test sequences.

13 Inverter Series TOSVERT Architecture Sensorless & Closed-Loop Vector

Toshiba TOSVERT High-Performance & Compact Series

6 Models

Toshiba Heavy Industrial & HVAC / Pump Inverters

7 Models

Most Common Toshiba Inverter Fault Codes

Diagnostic Quick Reference
Trip Code Trip Name Common Physical Trigger Recommended First Check
OC1 / OC1P Overcurrent during Acceleration Output current exceeded threshold during startup due to rapid accel ramp, motor short, or jammed load. Increase acceleration time (ACC) and uncouple motor to check for mechanical binding.
OC2 / OC3 Overcurrent (Decel / Constant) Deceleration rate set too fast or sudden load shock during steady-speed operation. Extend deceleration time (dEC) and inspect driven equipment for intermittent mechanical jams.
OP1 / OP2 / OP3 Overvoltage Trip Motor regenerative energy during deceleration charging internal DC link capacitors above trip voltage. Verify dynamic braking resistor connectivity across PA(+) and PB terminals; increase deceleration time.
OCA1 / OCA2 Startup Short Circuit / Ground Fault Phase-to-phase or output phase-to-ground short circuit detected across motor terminals at initiation of run command. Disconnect motor cables and measure insulation resistance to earth ground using a 500V Megohmmeter.
OL1 / OL2 Inverter / Motor Overload Continuous current exceeding rated operating limits of inverter semiconductors (OL1) or motor thermal rating (OL2). Verify motor rated current setting in parameter (tHr) and inspect machine mechanical duty cycle.
OH Heatsink Overheating Internal temperature sensor detected cooling fin temperature exceeding safe electronic limits. Verify internal cooling fan is operating, clear heatsink air passages, and check ambient panel cooling.
UP1 Undervoltage Main DC bus voltage fell below the minimum operating threshold due to supply line power outage or brownout. Measure AC line voltage across R/L1, S/L2, T/L3 and inspect incoming line fuses and disconnects.
EPHO / EPHI Output / Input Phase Failure Loss of one motor output conductor (EPHO) or one phase missing on the incoming three-phase AC line (EPHI). Check output motor cable terminal screws and inspect upstream three-phase supply lines.

How to Clear & Reset Toshiba Inverter Faults

  1. Keypad Reset: Press the red STOP/RESET key on the front digital keypad (press twice or hold if clearing persistent overcurrent trips).
  2. Control Terminal Reset (RES): Momentarily close the digital control terminal programmed as “Fault Reset” (Terminal input assigned to setting `8` or `10`).
  3. Parameter Clear Mode (typ): If resetting parameters to factory defaults, set parameter typ = 3 (Standard factory default) or typ = 13 to clear the internal fault trip history log.
  4. Power Cycle: Disconnect main AC input power, wait until the operation panel display turns off completely (discharge of internal high-voltage capacitors), then restore line power.
⚠️ High-Voltage Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus capacitor voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] before opening enclosure covers or servicing terminals U, V, and W on any Toshiba drive.