Toshiba Drives Fault Codes & Troubleshooting
Technical diagnostic directory for Toshiba TOSVERT low-voltage inverters, general purpose motor drives, and heavy industrial plant controllers. Select your drive model series below to access parameter checks, trip code descriptions, and physical test sequences.
Toshiba TOSVERT High-Performance & Compact Series
6 ModelsFlagship Industrial Inverter with Dual Embedded Ethernet, Web Server & High-Torque Performance
Classic Heavy-Duty Inverter with Closed-Loop Flux Vector Control (0.75 to 500 kW)
Compact General Purpose Drive with Easy-Setting Dial & Permanent Magnet (PM) Motor Control
Classic Compact AC Inverter with Side-by-Side Installation & Built-in EMI Filter
Simple & Compact Micro Inverter for Small Conveyors, Fans & Medical Machinery
Sub-Compact Micro Drive with Integrated Rotary Frequency Setting Potentiometer
Toshiba Heavy Industrial & HVAC / Pump Inverters
7 ModelsHeavy Duty Industrial Inverter with Real Matrix Torque Vector Algorithm for Severe Industrial Loads
Classic TOSVERT-130 G7 Heavy-Duty Industrial Vector Drive
Enhanced HVAC & Pump Flow Controller with BACnet, Metasys N2 & Multi-Zone PID Regulation
Dedicated Commercial HVAC and Pumping Drive with Integrated Damper & Smoke Purge Logic
Classic Variable Torque HVAC Inverter with Clean Power Harmonics Control
High-Capacity Heavy-Duty Industrial Drive for Mining, Extruders & Large Centrifugal Compressors
Classic TOSVERT-130 H7 Industrial Drive Module for Demanding Factory Automation
Most Common Toshiba Inverter Fault Codes
Diagnostic Quick Reference| Trip Code | Trip Name | Common Physical Trigger | Recommended First Check |
|---|---|---|---|
| OC1 / OC1P | Overcurrent during Acceleration | Output current exceeded threshold during startup due to rapid accel ramp, motor short, or jammed load. | Increase acceleration time (ACC) and uncouple motor to check for mechanical binding. |
| OC2 / OC3 | Overcurrent (Decel / Constant) | Deceleration rate set too fast or sudden load shock during steady-speed operation. | Extend deceleration time (dEC) and inspect driven equipment for intermittent mechanical jams. |
| OP1 / OP2 / OP3 | Overvoltage Trip | Motor regenerative energy during deceleration charging internal DC link capacitors above trip voltage. | Verify dynamic braking resistor connectivity across PA(+) and PB terminals; increase deceleration time. |
| OCA1 / OCA2 | Startup Short Circuit / Ground Fault | Phase-to-phase or output phase-to-ground short circuit detected across motor terminals at initiation of run command. | Disconnect motor cables and measure insulation resistance to earth ground using a 500V Megohmmeter. |
| OL1 / OL2 | Inverter / Motor Overload | Continuous current exceeding rated operating limits of inverter semiconductors (OL1) or motor thermal rating (OL2). | Verify motor rated current setting in parameter (tHr) and inspect machine mechanical duty cycle. |
| OH | Heatsink Overheating | Internal temperature sensor detected cooling fin temperature exceeding safe electronic limits. | Verify internal cooling fan is operating, clear heatsink air passages, and check ambient panel cooling. |
| UP1 | Undervoltage | Main DC bus voltage fell below the minimum operating threshold due to supply line power outage or brownout. | Measure AC line voltage across R/L1, S/L2, T/L3 and inspect incoming line fuses and disconnects. |
| EPHO / EPHI | Output / Input Phase Failure | Loss of one motor output conductor (EPHO) or one phase missing on the incoming three-phase AC line (EPHI). | Check output motor cable terminal screws and inspect upstream three-phase supply lines. |
How to Clear & Reset Toshiba Inverter Faults
- Keypad Reset: Press the red STOP/RESET key on the front digital keypad (press twice or hold if clearing persistent overcurrent trips).
- Control Terminal Reset (RES): Momentarily close the digital control terminal programmed as “Fault Reset” (Terminal input assigned to setting `8` or `10`).
- Parameter Clear Mode (typ): If resetting parameters to factory defaults, set parameter typ = 3 (Standard factory default) or typ = 13 to clear the internal fault trip history log.
- Power Cycle: Disconnect main AC input power, wait until the operation panel display turns off completely (discharge of internal high-voltage capacitors), then restore line power.