Toshiba AS1 (VF-AS1) Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba TOSVERT VF-AS1 high-performance industrial inverter series. Search or filter through the complete fault code directory below.
Power Range
0.4 – 500 kW (0.5 – 700 HP)
Supply Voltage
200–240V / 380–480V (3-Phase)
Control Modes
V/f, Sensorless & Closed-Loop Vector
Operator Interface
4-Digit LED / Optional LCD Panel
Complete Toshiba AS1 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| OC1, OC1P Overcurrent during acceleration | Cause: The acceleration time (acc) is too short; V/f setting is improper; Restart signal input to rotating motor; Special motor used; Manual torque boost (vb) is large. Remedy:
|
| OC2, OC2P Overcurrent during deceleration | Cause: The deceleration time (dec) is too short. Remedy:
|
| OC3, OC3P Overcurrent during fixed speed | Cause: The load fluctuates abruptly; The load is in an abnormal condition. Remedy:
|
| OC1P, OC2P, OC3P (Note) Component Failure / Overheat | Cause: A main circuit element is defective; Overheat protection is activated. Remedy:
|
| OCA1 U-phase arm short-circuit | Cause: A main circuit element is defective (U-phase). Remedy:
|
| OCA2 V-phase arm short-circuit | Cause: A main circuit element is defective (V-phase). Remedy:
|
| OCA3 W-phase arm short-circuit | Cause: A main circuit element is defective (W-phase). Remedy:
|
| OCL Loaded side overcurrent at start time | Cause: Insulation of output main circuit or motor is defective; Motor has too small impedance; Drive circuit board damaged. Remedy:
|
| OCr Dynamic braking element overcurrent (110kW or larger) | Cause: PB-PC/+ circuit is shorted; Resistor with resistance smaller than minimum allowable is connected; Parameter Pb set to 1 or 2 without connecting brake. Remedy:
|
| OH Overheating | Cause: Cooling fan does not rotate; Ambient temperature too high; Vent blocked; Heat generating device nearby; Thermistor disconnected. Remedy:
|
| OH2 Thermal trip stop command from external device | Cause: Input signal impressed at control input terminal PTG; Thermal trip command (input function 46 or 47) issued by external device. Remedy:
|
| OL1 Inverter overload | Cause: Rapid acceleration; DC braking amount too large; V/f setting improper; Restart signal input to rotating motor; Load too large. Remedy:
|
| OL2 Motor overload | Cause: V/f parameter improperly set; Motor is locked up; Low-speed operation performed continuously; Excessive load applied. Remedy:
|
| OLr Dynamic braking resistor overload | Cause: Rapid deceleration is operated; Dynamic braking is too large. Remedy:
|
| OP1 Overvoltage during acceleration | Cause: Input voltage fluctuates abnormally (Power supply > 500kVA, capacitor opened/closed, thyrister connected); Restart signal input to rotating motor. Remedy:
|
| OP2 Overvoltage during deceleration | Cause: Deceleration time (dec) too short; Dynamic braking resistor has large resistance; Pb is OFF; Overvoltage limit F305 is OFF; Input voltage fluctuates. Remedy:
|
| OP3 Overvoltage during fixed speed operation | Cause: Input voltage fluctuates abnormally; Motor is in regenerative state (load pushes motor). Remedy:
|
| Ot Overtorque | Cause: Overtorque reaches detection level; Stall prevention performed longer than time set with F452. Remedy:
|
| UC Low current operation | Cause: Output current decreased to low-current detection level during operation. Remedy:
|
| UP1 Undervoltage (main circuit) | Cause: Input voltage too low; Momentary power failure occurs longer than detection time F628. Remedy:
|
| E Emergency stop | Cause: Inverter stopped by panel during auto/remote; Stop command (terminal function 20 or 21) issued by external device. Remedy:
|
| EEP1 EEPROM error | Cause: A data writing error occurs. Remedy:
|
| EEP2 Initial read error | Cause: Some internal data is corrupted; Power was turned off while typ was being set. Remedy:
|
| EEP3 Initial read error | Cause: Some internal data is corrupted. Remedy:
|
| EF1, EF2 Ground fault | Cause: A current leaked from an output cable or the motor to ground. Remedy:
|
| EPH0 Output phase failure | Cause: A phase failure occurred in the output line of the main circuit. Remedy:
|
| EPH1 Input phase failure | Cause: A phase failure occurred in the input line of the main circuit. Remedy:
|
| Err2 Main unit RAM fault | Cause: The control RAM is defective. Remedy:
|
| Err3 Main unit ROM fault | Cause: The control ROM is defective. Remedy:
|
| Err4 CPU fault | Cause: The control CPU is defective. Remedy:
|
| Err5 Communication time-out error | Cause: Normal communication was not possible for the time set by F803. Remedy:
|
| Err6 Gate array fault | Cause: Main gate array is defective. Remedy:
|
| Err7 Output current detector error | Cause: The main output current detector is defective. Remedy:
|
| Err8 Optional unit fault | Cause: An optional device has failed (such as a communication device). Remedy:
|
| Etn Tuning error | Cause: Motor capacity connected is 2 notches or more smaller than inverter; Motor is not 3-phase inductive; Tuning performed while motor running. Remedy:
|
| Etn1 Tuning detection error | Cause: Some parameters (F410-F413) not detected; Motor capacity too small; Motor not 3-phase inductive; No motor connected; Cables too long (>30m); Motor running. Remedy:
|
| Etn2 Motor constant value error | Cause: Some detection values (F410-F413) beyond limits; Motor capacity too small; Motor not 3-phase inductive; Cables too long (>30m); Motor running. Remedy:
|
| Etn3 Motor constant setting error | Cause: Some items indicated on the motor nameplate are not entered correctly. • Base frequency (uL) • Base frequency voltage 1 (uLu) • Motor rated capacity (F405) • Motor rated current (F406) • Motor rated speed (F407) Remedy:
|
| Etyp Inverter type error | Cause: Is circuit board (or main circuit/drive circuit board) replaced? Remedy:
|
| E-10 Analog input terminal overvoltage | Cause: Overrated voltage is applied to analog input. Remedy:
|
| E-11 Sequence error | Cause: The signal from system is not inputted into input terminals. The input terminal function (130, 131) is not set up. A value other than 0.0 is specified for F630, although the brake answer function is not used. Remedy:
|
| E-12 Encoder error | Cause: Disconnection of encoder circuit. The encoder is not connected correctly. Remedy:
|
| E-13 Speed error (Over speed) | Cause: Encoder error (inverter error). Remedy:
|
| E-17 Key failure alarm | Cause: The same key is input continuously more than 20 seconds. Remedy:
|
| E-18 Terminal input error | Cause: Braking down of a wire for VI/II input signal. Terminal circuit board comes off and falls. P24 overcurrent. Remedy:
|
| E-19 Abnormal CPU2 communication | Cause: An error arises during CPU2 communication. Remedy:
|
| E-20 V/f control error | Cause: An internal control error occurs. Remedy:
|
| E-21 CPU1 fault | Cause: A software error occurs in the control CPU. Remedy:
|
| E-22 Abnormal logic input voltage | Cause: An abnormal voltage is applied to the control logic input terminal. Remedy:
|
| E-23 Option 1 error | Cause: Expansion I/O card 1 is defective. Remedy:
|
| E-24 Option 2 error | Cause: Expansion I/O card 2 is defective. Remedy:
|
| E-25 Stop position retaining error | Cause: A deviation error occurs during stop position retaining control. The stop position adjustment range specified with F381 is too narrow. Creeping speed is too fast. Remedy:
|
| E-26 CPU2 fault | Cause: Motor control CPU is defective. The drive circuit board in the inverter was damaged. Remedy:
|
| E-29 Control power backup undervoltage error | Cause: The control voltage between +SU and CC terminals is too low. Control power is not supplied through +SU and CC terminals. The parameter F647 is not set correctly. Remedy:
|
| SOut Step-out (for PM motors only) | Cause: The motor shaft is locked. One output phase is open. An impact load is applied. Remedy:
|
| PrF Power removal error | Cause: Error of power removal signal. Remedy:
|
| OFF ST signal OFF | Cause: ST terminal (terminal to which the ST function is assigned) is in open-circuit. Remedy:
|
| PrA PWR signal OFF | Cause: PWR terminal is in open-circuit. Remedy:
|
| COFF Control power backup undervoltage | Cause: The control voltage between +SU and CC terminals is too low. Control power is not supplied through +SU and CC terminals. The parameter F647 is not set correctly. Remedy:
|
| MOFF Undervoltage in main circuit | Cause: The supply voltage between R, S and T is under voltage. Trouble of rush current restraint circuit or DC circuit fuse. Remedy:
|
| rtry Retry | Cause: The inverter is in the process of retry. A momentary stop occurred. Remedy:
|
| Err1 Point setting alarm | Cause: The frequency setting signals at points 1 and 2 are set too close to each other. Remedy:
|
| CLr Clear enabling indication | Cause: This message is displayed when pressing the STOP key while an error code is displayed. Input terminal RES signal is ON during trip display. Remedy:
|
| EOFF Emergency stop enabling indication | Cause: The operation panel is used to stop the operation in automatic control or remote control mode. Remedy:
|
| HI / LO Setting error alarm | Cause: An error is found in a setting when data is reading or writing. (Error code and data displayed alternately). Remedy:
|
| db DC braking | Cause: DC braking in process. Remedy:
|
| dbOn Shaft fixing in control | Cause: Motor shaft fixing control is in process. Remedy:
|
| E1 / E2 / E3 Panel indication overflow | Cause: The digit number of the item displayed (e.g., frequency) is in excess of the specified digit number. Remedy:
|
| init Parameters in the process of initialization | Cause: Parameters are being initialized to default values. Remedy:
|
| Atn In auto-tuning 1 | Cause: Auto-tuning 1 in process. Remedy:
|
| LStp Auto-stop because of continuous operation at lower-limit | Cause: The automatic stop function of F256 is being performed. Remedy:
|
| StOP Momentary power failure slowdown stop | Cause: The deceleration stop function of uuc (regenerative power ride-through control) is activated. Remedy:
|
| HEAd / End Display of first/last data items | Cause: First and last data in the AuH group. Remedy:
|
| tun During learning | Cause: Learning for brake sequence operation or light-load high-speed operation is currently in progress. Remedy:
|
| tun1 Brake sequence learning error | Cause: Braking operation is not performed normally. The load is too heavy. There are some operation errors. Remedy:
|
| tun2 Light-load high-speed learning operation error | Cause: There are some errors in the operation for learning for light-load high-speed operation. Remedy:
|
| tun3 Light-load high-speed learning overload error | Cause: Learning operation for light-load high-speed operation is performed while the load is lifted. Motor constants (uL, uLv, F405 to F413) are not entered correctly. Remedy:
|
| UndO Key operation permitted temporarily | Cause: This message appears if the ENTER key is pressed and held down for 5 seconds or more when key operation is prohibited by F737. Remedy:
|
| C Overcurrent pre-alarm | Cause: Same as OC (Overcurrent). Remedy:
|
| P Overvoltage pre-alarm / PBR operation level | Cause: Same as OP (Overvoltage). P blink while PBR is operating is not an error. Remedy:
|
| L Overload pre-alarm | Cause: Same as OL1 and OL2 (Overload). Remedy:
|
| H Overheat pre-alarm | Cause: Same as OH (Overheat). Remedy:
|
| t Communication error | Cause: Various transmission errors occur when computer is linked up with inverter system. Various transmission errors occur in inverter to inverter communication (slave side). Time-out or trip in master side. Remedy:
|
How to Clear & Reset Toshiba AS1 Drive Faults
- Keypad Reset: Press the STOP/RESET key on the operation panel twice when a trip code is displayed. The first press acknowledges the trip state, and the second clears the active fault.
- Control Terminal Reset (RES): Close the contact between control terminal RES and common terminal CC for at least 0.1 seconds, then reopen. (The RES terminal is factory-assigned to the fault reset function).
- Serial Communication Reset: Send an inverter reset command by setting the fault reset bit in the control word via the built-in RS-485 port (Modbus RTU / TOSHIBA protocol) or optional communication bus (DeviceNet, Profibus-DP, CC-Link).
- Power Cycle: Switch off the main AC power supply breaker. Wait until the control panel display and the internal CHARGE LED extinguish completely (approx. 10 to 15 minutes for capacitor discharge), then restore input power.
- Pre-Reset Safety Check: Always inspect motor insulation and load mechanical integrity prior to resetting high-priority trips such as overcurrent (OC1/OC2/OC3) or ground faults (EF) to prevent permanent IGBT module damage.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that the intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] (and confirm the internal red CHARGE lamp has fully extinguished) before touching motor terminals U/T1, V/T2, W/T3 or performing internal wiring work on the Toshiba AS1 drive.