Toshiba NC3 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba NC3 (TOSVERT VF-nC3) compact micro drive series. Search or filter through the complete fault code directory below.
Power Range
0.1 – 4.0 kW (0.12 – 5 HP)
Supply Voltage
1-Ph 120V/240V & 3-Ph 240V/400V
Control Modes
V/f Control & Sensorless Vector
Operator Interface
Turn-and-Push Dial & 4-Digit Display
Complete Toshiba NC3 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, OL1, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| E (0011) Emergency stop | Cause: During automatic operation or remote operation, an emergency stop command is entered from the operation panel or an external (terminal or communication). Remedy:
|
| E-13 (0045) Over speed fault | Cause: The input voltage fluctuates abnormally. Over speed fault due to the overvoltage limit operation. Remedy:
|
| E-18 (0032) Break in analog signal cable | Cause: The input signal from VI is equal to or less than the F633 setting. Remedy:
|
| E-19 (0033) CPU communications error | Cause: A communications error occurs between control CPUs. Remedy:
|
| E-20 (0034) Excessive torque boosted | Cause: The automatic torque boost parameter F402 setting is too high. The motor has too small impedance. Remedy:
|
| E-21 (0035) CPU fault 2 | Cause: The control CPU is defective. Remedy:
|
| E-26 (003A) CPU fault 3 | Cause: Internal CPU error. Remedy:
|
| EEP1 (0012) EEPROM fault 1 | Cause: The EEPROM is writing error. Remedy:
|
| EEP2 (0013) EEPROM fault 2 | Cause: TYP operation was aborted by power supply off etc. The EEPROM is reading error. Remedy:
|
| EEP3 (0014) EEPROM fault 3 | Cause: The EEPROM is defective. Remedy:
|
| EF2 (0022) Ground fault trip | Cause: A ground fault occurs in the output cable or the motor. Remedy:
|
| EPH1 (0008) Input phase failure | Cause: A phase failure occurred in the input line of the main circuit. The capacitor in the main circuit lacks capacitance. Remedy:
|
| EPH0 (0009) Output phase failure | Cause: A phase failure occurred in the output line of the main circuit. The motor has too big impedance. Remedy:
|
| ERR2 (0015) Main unit RAM fault | Cause: The control RAM is defective. Remedy:
|
| ERR3 (0016) Main unit ROM fault | Cause: The control ROM is defective. Remedy:
|
| ERR4 (0017) CPU fault 1 | Cause: The control CPU is defective. Remedy:
|
| ERR5 (0018) Remote control error | Cause: The communication with external devices was broken off. Remedy:
|
| ETN (0028/0054/0055/0056) Auto-tuning error | Cause: The motor parameters (uL, uLu, F405, F415, F417) are not set correctly. The motor capacity is 2 classes or less than the inverter. Output cable is too thin. Motor is not connected. Motor is rotating. Remedy:
|
| ETYP (0029) Inverter type error | Cause: It may be a breakdown failure. Remedy:
|
| OC1 (0001) Overcurrent during acceleration | Cause: The acceleration time ACC is too short. The V/F setting is improper. A restart signal is input to the rotating motor after a momentary stop. Special motor (small impedance) is used. Cable length to motor is long. Remedy:
|
| OC2 (0002) Overcurrent during deceleration | Cause: The deceleration time dEC is too short. The cable length to a motor is long. Remedy:
|
| OC3 (0003) Overcurrent during constant speed operation | Cause: The load fluctuates abruptly. The load is in an abnormal condition. The cable length to a motor is long. Remedy:
|
| OCA (0005) Arm overcurrent at start-up | Cause: A main circuit element is defective. Remedy:
|
| OCL (0004) Overcurrent (load side at start-up) | Cause: The insulation of the output main circuit or motor is defective. The motor has too small impedance. Remedy:
|
| OH (0010) Overheat | Cause: The cooling fan is life or fault. The ambient temperature is high or low outside a specified ambient temperature. Remedy:
|
| OL1 (000D) Inverter overload | Cause: Acceleration time ACC too short. DC braking amount too large. V/F setting improper. Restart signal input to rotating motor. Load is too large. Remedy:
|
| OL2 (000E) Motor overload | Cause: V/F setting improper. Motor is locked up. Low-speed operation performed continuously. Excessive load applied. Remedy:
|
| OL3 (003E) Main module overload | Cause: Carrier frequency is high and load current increased at low speeds (mainly 15Hz or less). Remedy:
|
| OP1 (000A) Overvoltage during acceleration | Cause: Input voltage fluctuates abnormally (Power supply >200kVA, Capacitor open/close, Thyristor connected). Restart signal input to rotating motor. Remedy:
|
| OP2 (000B) Overvoltage during deceleration | Cause: Deceleration time dEC is too short (Regenerative energy too large). Overvoltage limit operation F305 is disabled. Input voltage fluctuates abnormally. Remedy:
|
| OP3 (000C) Overvoltage during constant-speed | Cause: Input voltage fluctuates abnormally. Motor is in regenerative state (load pushes motor faster than frequency). Remedy:
|
| OT (0020) Over-torque trip | Cause: Over-torque reaches detection level during operation. Remedy:
|
| UC (001D) Low-current operation Trip | Cause: Output current decreased to low-current detection level during operation. Remedy:
|
| UP1 (001E) Under voltage trip (main circuit) | Cause: The input voltage (in the main circuit) is too low. Remedy:
|
| A-05 Output frequency upper limit | Cause: Attempt made to operate at frequency higher than 10 times the base frequency. Remedy:
|
| A-17 Operation panel key alarm | Cause: RUN or STOP key held down for >20 seconds. Key is faulty. Remedy:
|
| ATN Auto-tuning | Cause: Auto-tuning in process. Remedy:
|
| CLR Clear command acceptable | Cause: Displayed when pressing STOP key while an error code is displayed. Remedy:
|
| DB DC braking | Cause: DC braking in process. Remedy:
|
| E1 / E2 / E3 Flowing out of excess number of digits | Cause: Number of digits (e.g. frequencies) is more than 4. Remedy:
|
| E-49 External power supply logic switching check | Cause: Input terminal switched to sink logic of external power (+24V). Remedy:
|
| E-50 Source logic switching check | Cause: Input terminal switched to source logic. Remedy:
|
| E-51 Sink logic switching check | Cause: Input terminal switched to sink logic. Remedy:
|
| EASY / STD Switching display of Easy/Standard mode | Cause: EASY key was pushed. Remedy:
|
| EOFF Emergency stop command acceptable | Cause: Operation panel used to stop operation in auto/remote control mode. Remedy:
|
| ERR1 Frequency point setting error | Cause: Frequency setting signals at points 1 and 2 are too close. Remedy:
|
| HEAD / END Display of first/last data items | Cause: First or last data item in group reached. Remedy:
|
| HI / LO Setting error alarm | Cause: Error found in a setting when data is reading or writing. Remedy:
|
| INIT Parameters in initialization | Cause: Parameters are being initialized to default. Remedy:
|
| LSTP Auto-stop (continuous low limit) | Cause: Automatic stop function (F256) activated. Remedy:
|
| MOFF Undervoltage in main circuit | Cause: Supply voltage between R, S, T is under voltage. Shorting-bar between P0 and PA/+ removed (120V class). Remedy:
|
| NERR No trip of past trip | Cause: No new record of past trip. Remedy:
|
| OFF ST terminal OFF | Cause: ST-CC circuit is opened. Remedy:
|
| PASS / FAIL Password verification | Cause: Result of password input for F739. Remedy:
|
| RTRY Retry in process | Cause: Inverter in process of retry after momentary stop. Remedy:
|
| SET Input requirement of region setting | Cause: Power supplied to inverter for the first time. Remedy:
|
| STOP Deceleration stop during power failure | Cause: Decel stop during power failure (F302) activated. Remedy:
|
| C Overcurrent pre-alarm | Cause: Current flows at or higher than stall prevention level. Remedy:
|
| H Overheat pre-alarm | Cause: Overheat protection pre-alarm level reached. Remedy:
|
| L Overload pre-alarm | Cause: Cumulative overload reaches 50% or more of trip value. Remedy:
|
| P Overvoltage pre-alarm | Cause: Voltage generated at or higher than stall prevention level. Remedy:
|
| T Communication pre-alarm | Cause: Communication broken off at or higher than F803 setting. Remedy:
|
How to Clear & Reset Toshiba NC3 Drive Faults
- Keypad Reset: Press the red STOP / RESET key on the front panel twice after resolving the fault cause (the first press acknowledges and clears the trip display; the second press returns the inverter to normal output frequency display).
- Control Terminal Reset (Digital Input): Assign the Fault Reset function (Function 10) to a programmable digital input terminal (such as F, R, S1, or S2) and briefly close the circuit to control common CC.
- Setting Dial Navigation: Rotate the central turn-and-push setting dial to inspect the trip history parameter (
ALH/ Alarm History), confirm the operating conditions at the moment of the trip, and press the dial to clear if parameter-prompted. - RS-485 Communication: If operating via the bottom RJ45 serial port, send a reset control command bit over Modbus RTU or Toshiba protocol to clear the inverter trip state remotely.
- Power Cycle: Disconnect the incoming AC power supply. Wait at least 15 minutes until the 4-digit LED display and the internal CHARGE lamp turn off completely to allow the DC bus capacitors to discharge safely, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] before inspecting motor leads, opening terminal covers, or touching output terminals U/T1, V/T2, and W/T3 on the Toshiba NC3 drive.