Toshiba Q9 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba Q9 HVAC and pump inverter series. Search or filter through the complete fault code directory below.

HVAC & Pump Dedicated Inverter Power: 0.75 to 315 kW (1 to 400 HP) Embedded BACnet, Modbus & Metasys N2
Power Range 0.75 – 315 kW (1 – 400 HP)
Supply Voltage 200–240V / 380–480V / 600V (3-Phase)
Control Modes Variable Torque V/f & Sensorless Vector
Operator Interface Multi-Line English LCD Keypad (EOI)

Complete Toshiba Q9 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, or Overcurrent).

Fault Code and MeaningCause and Remedy
Atn
Autotune active.

Cause:

  • Autotune function is currently running.




Remedy:

  • Indication only; no action required.


ETN
Autotuning error.

Cause:

  • Autotune readings significantly inconsistent with configuration.

  • A non-3-phase motor is being used.

  • Improper settings at F400 or F410 to F413.

  • Motor rating significantly smaller than ASD rating.

  • Output cabling too small, too long, or EMF interference.

  • Motor is running during Autotune.




Remedy:

  • Verify motor wiring and type.

  • Check and adjust parameters F400 and F410-F413.

  • Ensure motor is stopped before tuning.


ETN1
Autotuning error — Torque boost error.

Cause:

  • Improper setting at F410.




Remedy:

  • Correct setting F410.


ETN2
Autotuning error — Leak inductance error.

Cause:

  • Improper setting at F412.




Remedy:

  • Correct setting F412.


ETN3
Autotuning error — Motor rating error.

Cause:

  • Improper setting at F405, F406, or F407.




Remedy:

  • Correct settings F405, F406, or F407.


ETYP
Typeform error.

Cause:

  • Firmware information inconsistent between Application Board and Motor Control board.

  • Application Board or Motor Control board is defective.




Remedy:

  • Perform a Typeform Reset.

  • Replace defective board if reset fails.


4-20 mA
4-20 Signal Loss.

Cause:

  • Misconnection, poor connection, or broken wire.

  • Improper programming at F201 and associated parameters.




Remedy:

  • Check wiring continuity.

  • Verify parameter F201.


CM1
Internal communications error.

Cause:

  • Improperly programmed ASD.

  • Improper communications settings.




Remedy:

  • Check communications programming.


CM2
External communications error.

Cause:

  • Improperly connected cables.




Remedy:

  • Secure and check external cable connections.


COFF
Under-voltage condition at optional Control power supply.

Cause:

  • Misconnection, poor connection, or broken wire.

  • Defective power supply.




Remedy:

  • Check wiring.

  • Replace power supply if defective.


DAMP
Damper closed.

Cause:

  • Improper configuration/programming for Damper Control at discrete input terminals.




Remedy:

  • Check discrete input terminal configuration.


Emergency Off
Output signal terminated/Brake applied.

Cause:

  • Stop-Reset pressed twice at the EOI.

  • EOFF command received remotely.




Remedy:

  • ASD reset required.


HLD
Heavy load — motor/ASD overloaded.

Cause:

  • Accel setting is too short.

  • ASD/Motor not right-sized for application.

  • Excessively fluctuating load.




Remedy:

  • Increase Accel time.

  • Verify motor/drive sizing.


LLD
Light load.

Cause:

  • ASD/Motor should be right-sized for application.




Remedy:

  • Verify load matches drive capacity.


LLT
Lower-limit time.

Cause:

  • Parameter F256 adjustment required.




Remedy:

  • Adjust parameter F256.


LTA
Part replacement alarm.

Cause:

  • Part Replacement Alarm activation as set at F634.




Remedy:

  • Perform scheduled maintenance/replacement.


MOFF
Main under-voltage condition.

Cause:

  • Low 3-phase commercial power voltage level.




Remedy:

  • Check input power supply voltage.


OC
Over-Current — ASD output > F601.

Cause:

  • Phase-to-phase short (U, V, or W).

  • Defective IGBT.

  • Output cabling connected incorrectly.

  • Restarting into a spinning motor (no catch-spin).

  • Motor/machine jammed or brake engaged.

  • Accel/Decel too short or Voltage Boost too high.

  • Load fluctuations or high temp.




Remedy:

  • Check cabling and motor for shorts.

  • Check for mechanical jams.

  • Adjust Accel/Decel or V/f settings.


OH
Overheat — ASD ambient temp excessive.

Cause:

  • ASD operating at elevated temperature.

  • Cooling fan obstructed or inoperative.

  • Internal thermistor disconnected.




Remedy:

  • Clean vents and check fans.

  • Reduce ambient temperature.


OJ
User-set run-time counter exceeded.

Cause:

  • Run-timer limit reached.




Remedy:

  • Type Reset required; select Clear run timer.


OLI
ASD overload.

Cause:

  • Carrier frequency too high.

  • Excessive load.

  • Accel time too short.

  • DC damping rate too high.

  • Motor starting into spinning load.




Remedy:

  • Reduce carrier frequency.

  • Increase Accel time.

  • Check load conditions.


OLM
Motor overload.

Cause:

  • V/f parameter improperly set.

  • Motor locked or running low speed continuously.

  • Motor improperly matched to load.




Remedy:

  • Adjust V/f parameters.

  • Check for motor locking/jams.


OLST
Overload soft Stall active.

Cause:

  • Soft Stall Selection adjustment required (F017).




Remedy:

  • Adjust parameter F017.


OP
DC bus voltage exceeds specifications.

Cause:

  • Starting into spinning motor after momentary power loss.

  • High input voltage or spikes (install inductive filter).

  • Decel time too short.

  • Regenerative load (Over-voltage stall turned off).




Remedy:

  • Increase Decel time.

  • Install input reactor/filter.

  • Enable Ridethrough (F302) or Over-voltage stall.


OT
Over-torque.

Cause:

  • Torque requirement exceeds F616/F617 for time > F618.

  • ASD not matched to application.

  • Load obstructed.




Remedy:

  • Check load for obstructions.

  • Adjust torque parameters F616, F617, F618.


POFF
Under-voltage at 5, 15, or 24 VDC supply.

Cause:

  • Defective Control board.

  • Excessive load on power supply.

  • Low input voltage.




Remedy:

  • Check input voltage.

  • Replace Control board if defective.


POT
Pre-over-torque.

Cause:

  • Torque requirement exceeds F616 or F617.

  • Load obstructed.




Remedy:

  • Clear load obstruction.

  • Adjust F616/F617 if necessary.


PTC
Optional thermal sensor threshold exceeded.

Cause:

  • User-set thermal threshold (F646) exceeded.




Remedy:

  • Check temperature or adjust F646.


UC
Under-current.

Cause:

  • Current below level defined at F611.




Remedy:

  • Disable detection at F610 or adjust F611.


E-10
Over-voltage at analog input.

Cause:

  • Mis-wire at the ASD input terminals.




Remedy:

  • Check input terminal wiring.


E-12
Open circuit at shaft-mounted encoder.

Cause:

  • Encoder signal missing.




Remedy:

  • Check encoder connection.


E-13
Over-speed error.

Cause:

  • Motor speed > commanded speed.

  • Improper encoder connection or setup.

  • Defective encoder.




Remedy:

  • Check encoder setup and hardware.


E-18
Loss of signal at analog input.

Cause:

  • V/I input missing or low.

  • Over-current at P24.




Remedy:

  • Check analog signal source.


E-19
CPU communication error.

Cause:

  • Internal CPU communication failure.




Remedy:

  • Service call required.


E-20
Speed/torque/direction signal error.

Cause:

  • Control signal transfer error.




Remedy:

  • Service call required.


E-21
Stack overflow error.

Cause:

  • Internal processing error.




Remedy:

  • Service call required.


E-22
Improper input voltage at discrete input.

Cause:

  • Input activation voltage out of specification.




Remedy:

  • Check discrete input voltage levels.


E-23
Expansion card option 1 hardware error.

Cause:

  • Option card 1 failure.




Remedy:

  • Service call required.


E-24
Expansion card option 2 hardware error.

Cause:

  • Option card 2 failure.




Remedy:

  • Service call required.


E-26
CPU fault.

Cause:

  • Internal CPU fault.




Remedy:

  • Service call required.


EEP1
EEPROM write error.

Cause:

  • Data storage failure.




Remedy:

  • Service call required.


EEP2 / EEP3
EEPROM read error.

Cause:

  • Data retrieval failure during initialization.




Remedy:

  • Service call required.


EF1
Software-detected earth fault.

Cause:

  • Mis-wired ground.

  • Loose ground connection.

  • ASD setup improperly.




Remedy:

  • Verify ground wiring.


EF2
Hardware-detected earth fault.

Cause:

  • Mis-wired ground or loose connection.




Remedy:

  • Verify ground wiring.


Emergency Off
Emergency Off command (Trip).

Cause:

  • Stop-Reset pressed twice.

  • EOFF command received.




Remedy:

  • ASD reset required.

  • Check stopping method at F603.


EPHI
Input phase loss (R, S, or T).

Cause:

  • Mis-wired input phase.

  • Loose input phase connection.




Remedy:

  • Check input power wiring.


EPHO
Output phase loss (U, V, or W).

Cause:

  • Mis-wired output phase.

  • Loose output phase connection.




Remedy:

  • Check motor wiring.


ERR2 / ERR3 / ERR4 / ERR5 / ERR6
Internal ROM/RAM/CPU/Comm/Gate Array errors.

Cause:

  • Internal hardware or communication timeouts.

  • Improper setup or connections (ERR5/ERR8).




Remedy:

  • Service call required (for most hardware errors).

  • Check cables and setup (for Comm/Net errors).


OC1 / OC1P
Over-current during acceleration.

Cause:

  • V/f setting needs adjustment.

  • Restart from momentary power outage.

  • Starting into rotating motor.

  • Phase-to-phase short.

  • Accel time too short.

  • Voltage Boost too high.

  • Motor jammed or brake engaged.




Remedy:

  • Adjust V/f or Accel settings.

  • Clear jams/brakes.

  • Check for shorts.


OC2 / OC2P
Over-current during deceleration.

Cause:

  • Phase-to-phase short.

  • Decel time too short.

  • Motor/machine jammed.




Remedy:

  • Increase Decel time.

  • Check for shorts/jams.


OC3 / OC3P
Over-current during run.

Cause:

  • ASD/Motor load not matched.

  • Load fluctuations.

  • Elevated temperature.




Remedy:

  • Verify drive sizing.

  • Check cooling.


OCA1 / OCA2 / OCA3
Over-current at U/V/W phase IGBT.

Cause:

  • Low impedance at the specific phase (U, V, or W).




Remedy:

  • Check IGBT and motor phase impedance.


OCL
Output short circuit at U-V-W.

Cause:

  • Phase-to-phase short.

  • Starting into rotating motor.

  • Short Circuit Detection adjustment required (F613).




Remedy:

  • Check wiring for shorts.

  • Adjust F613.


OH
Over temperature error.

Cause:

  • Cooling fan inoperative.

  • Ventilation obstructed.




Remedy:

  • Check fans and clear vents.


OH2
Over temperature at PTC1/PTC2.

Cause:

  • Over-temperature detected by option board.

  • See F637 and F638.




Remedy:

  • Check external device temperature.


OL1
ASD overload error.

Cause:

  • Accel time too short.

  • DC Injection current too high.

  • V/f setting needs adjustment.




Remedy:

  • Adjust Accel or V/f settings.


OL2
Motor overload error.

Cause:

  • Motor locked or continuous low speed.

  • Load exceeds motor ability.




Remedy:

  • Check for jams.

  • Review sizing.


OP1 / OP2 / OP3
Over-voltage (Accel/Decel/Run).

Cause:

  • Motor running during restart.

  • Decel time too short.

  • Stall protection disabled.

  • Input voltage out of spec.




Remedy:

  • Increase Decel time.

  • Check input voltage.

  • Install input reactance if needed.


OT
Over-torque error.

Cause:

  • Torque exceeds F616/F617 settings.

  • Load obstructed.




Remedy:

  • Clear obstruction.

  • Adjust torque parameters.


SOUT
Permanent magnet motor pull out trip.

Cause:

  • Motor sync loss.




Remedy:

  • Service call required.


UC
Low-Current error.

Cause:

  • Improper low-current detection level setting.




Remedy:

  • Adjust detection level.


UP1
Main power under-voltage.

Cause:

  • 3-phase input voltage low.

  • Defective control board.

  • Excessive load on power supply.

  • Under-Voltage/Ridethrough settings require adjustment.




Remedy:

  • Check input power.

  • Adjust Ridethrough settings.


How to Clear & Reset Toshiba Q9 Drive Faults

  1. Keypad Reset: Press the STOP/RESET key on the electronic operator interface (EOI) LCD panel twice when a trip screen is active. The first press acknowledges the alarm condition, and the second clears the fault display.
  2. Control Terminal Reset (RES): Momentarily close the contact between digital input terminal RES and common terminal CC for at least 0.1 seconds, then open the contact.
  3. Building Automation / BAS Reset: Set the remote reset command bit via embedded building automation fieldbus protocols (BACnet MS/TP, Metasys N2, Siemens FLN, or Modbus RTU).
  4. Power Cycle: Disconnect the main AC incoming power breaker. Wait until the LCD display and the internal DC bus CHARGE lamp extinguish completely (approx. 10 to 15 minutes for capacitor discharge), then restore AC mains power.
  5. Post-Fault Verification: For serious fault conditions including OC1/OC2/OC3 (Overcurrent), EF (Ground Fault), or EPH0/EPH1 (Phase Loss), ensure mechanical loads and motor windings are checked prior to issuing a reset.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] (and confirm the internal red CHARGE LED is completely unlit) before servicing motor leads U/T1, V/T2, W/T3 or opening the enclosure on the Toshiba Q9 drive.