Toshiba H7 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba H7 standard-duty industrial adjustable speed drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 – 250 kW (1 – 350 HP)
Supply Voltage
200–240V / 380–480V / 600V (3-Phase)
Control Modes
True Torque Control2 & V/f
Operator Interface
240 x 64 Graphical LCD Keypad (EOI)
Complete Toshiba H7 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| CM1 Comm1 Error (Internal) | Cause: Internal communications error.
Remedy:
|
| CM2 Comm2 Error (External) | Cause: External communications error. Remedy:
|
| EMG Emergency Off | Cause: Output signal terminated; brake may be applied.
Remedy:
|
| MOFF Main Undervoltage | Cause: Undervoltage condition at the 3-phase AC input.
|
| OC Over Current | Cause: ASD output current greater than F601 setting.
Remedy:
|
| *OH Overheat | Cause: ASD ambient temperature excessive.
Remedy:
|
| OJ Timer | Cause: Run-time counter exceeded. Remedy:
|
| *OLI ASD Overload | Cause: Load requirement in excess of ASD capability.
|
| OLM Motor Overload | Cause: Load requirement in excess of motor capability.
|
| *OLR Resistor Overload | Cause: Excessive current at the Dynamic Braking Resistor.
|
| *OP Overvoltage | Cause: DC bus voltage exceeds specifications.
Remedy:
|
| OT Overtorque | Cause: Torque requirement in excess of F616/F617 settings.
|
| *POFF Control Undervoltage | Cause: Undervoltage at 5, 15, or 24 VDC supply.
|
| PtSt Reference Point | Cause: Two speed-reference frequency setpoints are too close. Remedy:
|
| UC Undercurrent | Cause: Output current below level defined at F611 for time set at F612. Remedy:
|
| Atn Autotune active | Cause: Autotune function is active. Atn2 indicates retry. Remedy:
|
| dbOn DC Braking | Cause: DC Injection function being carried out. Remedy:
|
| ASD Overload (Trip) | Cause:
|
| Autotune Error Configuration Mismatch | Cause:
|
| Communication Error Malfunction | Cause:
|
| Control Power Undervoltage Supply Issue | Cause:
|
| CPU Fault Processor Error | Cause: CPU malfunction. Remedy:
|
| DC Bus Undervoltage Low Voltage | Cause:
Remedy:
|
| DC Fuse Open Internal Fuse | Cause: Internal DC bus fuse is open. Remedy:
|
| Dynamic Braking Resistor Overcurrent DBR Current | Cause:
|
| Dynamic Braking Resistor Overload DBR Overload | Cause:
Remedy:
|
| Earth Fault Ground Fault | Cause:
|
| EEPROM Data Fault Read Error | Cause: EEPROM read malfunction. Remedy:
|
| EEPROM Fault Write Error | Cause: EEPROM write malfunction. Remedy:
|
| Emergency Off Remote Command | Cause: Emergency Off command received via EOI or remotely. Remedy:
|
| Encoder Loss Signal Missing | Cause: Encoder signal missing while running during closed-loop operation. Remedy:
|
| Flash Memory Fault Internal Error | Cause: Flash memory malfunction. |
| Gate Array Fault Hardware Error | Cause: Defective Gate Array or Gate Array malfunction. |
| Input Phase Loss Supply Phase Missing | Cause: 3-phase input to the ASD is low or missing. |
| Load Drooping Capacity Exceeded | Cause: Load requirement is in excess of the capabilities of the motor. |
| Load End Short Circuit Wiring Issue | Cause: Improper wiring at the ASD output to the motor. |
| Low Current Detection Error | Cause: Improper Low Current detection level setting. |
| Main Board EEPROM Fault Internal Error | Cause: Internal EEPROM malfunction. |
| Motor Overload (Trip) | Cause:
Remedy:
|
| No Fault Status | Cause: No active faults. |
| Option Fault External Device | Cause:
|
| Output Current Protection Fault Limit Exceeded | Cause:
|
| Output Phase Loss Missing Phase | Cause: 3-phase output from the ASD is low or missing. |
| Overcurrent During Acceleration Accel High Current | Cause:
|
| Overcurrent During Deceleration Decel High Current | Cause:
|
| Overcurrent During Run Operating High Current | Cause:
|
| Overheat (Trip) | Cause:
|
| Over Speed Speed Limit Exceeded | Cause:
|
| Overtorque (Trip) | Cause:
|
| Overvoltage During Acceleration Restart Issue | Cause: Motor running during restart. |
| Overvoltage During Deceleration Decel Issue | Cause:
Remedy:
|
| Overvoltage During Run Instability | Cause:
|
| PG Type/Connection Error Encoder Error | Cause:
|
| Phantom Fault System Fault | Cause: In multiple ASD configuration, a faulted ASD signals remaining ASDs to shut down. |
| Position Deviation Error Position Limit | Cause: Operating in Position Control mode and position exceeds limits of F631. |
| RAM Fault Memory Error | Cause: Internal RAM malfunction. |
| ROM Fault Memory Error | Cause: Internal ROM malfunction. |
| Sink/Source Setting Error Jumper Configuration | Cause:
|
| Torque Proving Fault Adjustment Required | Cause: Lift-First Pulse Count (F743) adjustment required. |
| Typeform Error Firmware Mismatch | Cause:
|
| U/V/W Phase Short Circuit Output Short | Cause: Low impedance at the U, V, or W lead of the ASD output. |
How to Clear & Reset Toshiba H7 Drive Faults
- Keypad Reset: Press the STOP/RESET key on the Electronic Operator Interface (EOI) keypad twice when a trip occurs. The first press acknowledges the fault display, and the second clears the active trip condition.
- Control Terminal Reset (RES): Momentarily connect terminal RES to terminal CC (common) on the control terminal strip for at least 0.1 seconds, then disconnect.
- Communication Bus Reset: Send a fault reset command by toggling the reset bit in the control word via RS-232/RS-485 serial communications (or ASD-NANOCOM network protocols including Modbus RTU, Profibus-DP, and DeviceNet).
- Power Cycle: Disconnect the primary AC input power breaker. Wait until the graphical LCD display and the internal DC bus CHARGE lamp extinguish completely (approx. 10 to 15 minutes for capacitor discharge), then restore AC mains power.
- Root-Cause Inspection: Before clearing critical fault trips such as OC1/OC2/OC3 (Overcurrent), EPH1/EPH0 (Phase Loss), or EF (Ground Fault), verify motor insulation, output wiring, and load mechanics to prevent IGBT module failure.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] (and confirm the internal red CHARGE lamp has fully extinguished) before touching motor terminals U/T1, V/T2, W/T3 or performing internal wiring work on the Toshiba H7 drive.