Toshiba G7 drive

Home / Toshiba / Toshiba G7 drive

Toshiba G7 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba G7 True Torque Control2 adjustable speed drive series. Search or filter through the complete fault code directory below.

Heavy-Duty Industrial ASD Power: 1 to 350 HP (0.75 to 260 kW) True Torque Control² Vector Algorithm
Power Range 1 – 350 HP (0.75 – 260 kW)
Supply Voltage 200–240V / 380–480V / 520–600V
Control Modes True Torque Control² (Vector & V/f)
Operator Interface 240 x 64 Graphical LCD Keypad (EOI)

Complete Toshiba G7 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, or Overcurrent).

Fault Code and MeaningCause and Remedy
CM1
Comm1 Error

Cause:

Internal communications error.


Remedy:


  • Improperly programmed ASD.

  • Improper communications settings.

  • Improperly connected cables.


CM2
Comm2 Error

Cause:

External communications error.


Remedy:


  • Check external communication connections.

  • Verify communication settings.


EMG
Emergency Off

Cause:

Output signal from the ASD is terminated and a brake may be applied if so configured.


Remedy:


  • Stop|Reset pressed twice at the EOI.

  • EOFF command received remotely.

  • ASD reset required.


MOFF
Main Undervoltage

Cause:

Undervoltage condition at the 3-phase AC input to the ASD.


Remedy:


  • Check for low 3-phase utility voltage.


OC
Over Current

Cause:

ASD output current greater than F601 setting.


Remedy:


  • Defective IGBT (U, V, or W).

  • ASD output to the motor is connected incorrectly. Disconnect the motor and retry.

  • ASD output phase-to-phase short.

  • The ASD is starting into a spinning motor.

  • Motor/machine jammed.

  • Mechanical brake engaged while the ASD is starting or while running.

  • Accel/Decel time is too short.

  • Voltage Boost setting is too high.

  • Load fluctuations.

  • ASD operating at an elevated temperature.


OH
Overheat

Cause:

ASD ambient temperature excessive.


Remedy:


  • ASD is operating at an elevated temperature.

  • ASD is too close to heat-generating equipment.

  • Cooling fan vent is obstructed.

  • Cooling fan is inoperative.

  • Internal thermistor is disconnected.


OJ
Timer

Cause:

Run-time counter exceeded.


Remedy:


  • Type Reset required; select Clear run timer.


OLI
ASD Overload

Cause:

Load requirement in excess of the capability of the ASD.


Remedy:


  • The carrier frequency is too high.

  • An excessive load.

  • Acceleration time is too short.

  • DC damping rate is set too high.

  • The motor is starting into a spinning load after a momentary power failure.

  • The ASD is improperly matched to the application.


OLM
Motor Overload

Cause:

Load requirement in excess of the capability of the motor.


Remedy:


  • V/f parameter improperly set.

  • Motor is locked.

  • Continuous operation at low speed.

  • The load is in excess of what the motor can deliver.


OLR
Resistor Overload

Cause:

Excessive current at the Dynamic Braking Resistor.


Remedy:


  • Deceleration time is too short.

  • DBR configuration improperly set.


OP
Overvoltage

Cause:

DC bus voltage exceeds specifications.


Remedy:


  • ASD attempting to start into a spinning motor after a momentary power loss.

  • Incoming utility power is above the specified range.

  • Decel time is too short.

  • Voltage spikes at the 3-phase input; install inductive filter.

  • DBR required or DBR resistance value is too high.

  • DBR function is turned off.

  • Overvoltage Stall feature is turned off.

  • System is regenerating.

  • Load instability.

  • Disable the Ridethrough function (F302).


OT
Overtorque

Cause:

Torque requirement in excess of the setting of F616 or F617 for a time longer than the setting of F618.


Remedy:


  • ASD is not correctly matched to the application.

  • F616 or F617 setting is too low.

  • Obstructed load.


POFF
Control Undervoltage

Cause:

Undervoltage condition at the 5, 15, or the 24 VDC supply.


Remedy:


  • Defective Control board.

  • Excessive load on power supply.

  • Low input voltage.


PtSt
Reference Point

Cause:

Two speed-reference frequency setpoint values are too close to each other.


Remedy:


  • Two speed reference frequency setpoints are too close to each other (increase the difference).


UC
Undercurrent

Cause:

Output current of the ASD is below the level defined at F611 and remains there for the time set at F612.


Remedy:


  • Check load coupling (load loss).

  • Check F611 and F612 settings.


Autotune Error
Autotune Malfunction

Cause:

Autotune readings that are significantly inconsistent with the configuration information.


Remedy:


  • A non-3-phase motor is being used.

  • Incorrect settings at F400, F413, or F414.

  • Using a motor that has a significantly smaller rating than the ASD.

  • ASD output cabling is too small, too long, or is being housed in a cable tray with other cables that are producing an interfering EMF.

  • Motor is running during the Autotune function.


Communication Error
Comms Malfunction

Cause:

System communication failure.


Remedy:


  • Communication malfunction.

  • Improper or loose connection.

  • Improper system settings.


CPU Fault
Processor Error

Cause:

Internal processor error.


Remedy:


  • CPU malfunction.

  • Contact Toshiba support.


DC Bus Undervoltage
Bus Voltage Low

Cause:

DC Bus voltage dropped below limit.


Remedy:


  • 3-phase input voltage low.

  • Defective control board.

  • Excessive load on the power supply.

  • Undervoltage/Ridethrough settings require adjustment.


DC Fuse Open
Internal Fuse Blown

Cause:

Internal DC bus fuse is open.


Remedy:


  • Check internal fuses.

  • Check for shorts.


Dynamic Braking Resistor Overcurrent
DBR Overcurrent

Cause:

ASD inability to discharge the bus voltage during regeneration.


Remedy:


  • No dynamic braking resistor (DBR) installed.

  • Deceleration time is too short.

  • Improper DBR setup information.

  • Defective IGBT7 (or IGBT7 ckt.).

  • 3-phase input voltage is above specification.


Earth Fault
Ground Fault

Cause:

Current leakage to Earth Ground detected.


Remedy:


  • Ground fault at the motor.

  • Ground fault at the output of the ASD.

  • Current leakage to Earth Ground.


EEPROM Data Fault
Memory Error

Cause:

Internal EEPROM malfunction.


Remedy:


  • Cycle power. If fault persists, replace control board.


Encoder Loss
Signal Missing

Cause:

Encoder signal missing while running during closed-loop operation.


Remedy:


  • Check encoder connections.

  • Check encoder power supply.


Gate Array Fault
Hardware Failure

Cause:

Defective Gate Array or Gate Array malfunction.


Remedy:


  • Contact service representative.


Input Phase Loss
Phase Missing

Cause:

3-phase input to the ASD is low or missing.


Remedy:


  • Check incoming power fuses and connections.


Load Drooping
Load Error

Cause:

Load requirement is in excess of the capabilities of the motor.


Remedy:


  • Check load mechanics.

  • Verify motor sizing.


Load End Short Circuit
Output Short

Cause:

Improper wiring at the ASD output to the motor.


Remedy:


  • Check motor wiring for shorts.


Low Current
Current Low

Cause:

Improper Low Current detection level setting.


Remedy:


  • Adjust low current detection parameters.


Option Fault
Card Error

Cause:

Optional device malfunction.


Remedy:


  • Improper system settings (at ASD or optional device).

  • Loose or improper connection.


Output Phase Loss
Motor Phase Lost

Cause:

3-phase output from the ASD is low or missing.


Remedy:


  • Output current is not within specified limits.

  • Loose or improper ASD-to-motor connection.


Overcurrent During Acceleration
Accel OC

Cause:

Overcurrent detected while ramping up speed.


Remedy:


  • V/f setting needs to be adjusted.

  • Restart from a momentary power outage.

  • The ASD is starting into a rotating motor.

  • ASD/Motor not properly matched.

  • Phase-to-phase short (U, V, or W).

  • Accel time too short.

  • Voltage Boost setting is too high.

  • Motor/machine jammed.

  • Mechanical brake engaged while the ASD is running.


Overcurrent During Deceleration
Decel OC

Cause:

Overcurrent detected while ramping down speed.


Remedy:


  • Phase-to-phase short (U, V, or W).

  • Deceleration time is too short.

  • Motor/machine jammed.

  • Mechanical brake engaged while the ASD is running.


Overcurrent During Run
Run OC

Cause:

Overcurrent detected at constant speed.


Remedy:


  • Load fluctuations.

  • ASD is operating at an elevated temperature.


Over Speed
Speed Limit Exceeded

Cause:

Result of a motor speed that is greater than the commanded speed when using an encoder for speed control.


Remedy:


  • Improper encoder connection or setup information.

  • Defective encoder.


PG Type/Connection Error
Encoder Error

Cause:

ASD is configured to receive a signal from a shaft-mounted encoder and no signal is being received.


Remedy:


  • Disconnection at the Encoder circuit.

  • Motor is stopped and is generating torque via torque limit control.

  • ASD is not configured properly.


Phantom Fault
System Fault

Cause:

In a multiple ASD configuration a faulted ASD signals the remaining ASDs that a fault has occurred.


Remedy:


  • Check other ASDs in the system for the primary fault.


Position Deviation Error
Position Error

Cause:

Operating in the Position Control mode and the resulting position exceeds the limits of the F631 setting.


Remedy:


  • Check position loop settings.

  • Check mechanical linkage.


Sink/Source Setting Error
Jumper Error

Cause:

Logic setting mismatch.


Remedy:


  • Improperly positioned Sink/Source jumper on the control board or on an option device.

  • Sink/Source configuration of an option device is incorrect.


Torque Proving Fault
Brake Logic Error

Cause:

Torque proving logic failed.


Remedy:


  • Lift-First Pulse Count (F743) adjustment required.


Typeform Error
Firmware Mismatch

Cause:

Firmware information loaded into the Gate Driver board is inconsistent with the device.


Remedy:


  • The Gate Driver board has been replaced.

  • The Gate Driver board is defective.


U/V/W Phase Short Circuit
Output Short

Cause:

Low impedance at the U, V, or W lead of the ASD output.


Remedy:


  • Check for short circuit in motor cable or motor windings.

  • Check IGBTs.


How to Clear & Reset Toshiba G7 Drive Faults

  1. Keypad Reset (EOI): Press the red STOP/RESET key on the front Electronic Operator Interface (EOI). When a fault occurs, the graphical LCD screen will flash the trip code and description. Pressing the STOP/RESET key after eliminating the root cause resets the fault condition.
  2. Control Terminal Reset (RES): Momentarily close a dry contact between the programmable digital input terminal configured as RES (Reset) and common control terminal CC. The contact closure must satisfy the programmed input filter delay time in parameter F143.
  3. Parameter Re-initialization (tyP): Open Program Mode on the EOI keypad, navigate to the Utility / Reset parameter group, and select parameter tyP (Reset Selection) to clear the fault log or restore standard factory defaults if memory corruption occurred.
  4. Serial Fieldbus Reset: If networked via Modbus RTU, Profibus-DP, Ethernet/IP, or DeviceNet option modules, transmit a trip clear bit command (Bit 7 of the drive command control word) from your master controller (PLC/DCS).
  5. Mains Power Cycle: Switch off the main incoming 3-phase AC supply line (terminals R/L1, S/L2, T/L3). Allow at least 10 minutes for the internal DC bus filter capacitors to discharge and the front charge lamp to extinguish completely before restoring AC power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] (or terminals PO and PC) before inspecting motor leads, opening terminal enclosures, or touching output load terminals T1/U, T2/V, and T3/W on the Toshiba G7 drive.