Fault Code and MeaningCause and Remedy
Atn
Autotune active

Cause: Atn indicates that the Autotune function is active.


Remedy:

  • Notification only; usually momentary under normal conditions.

  • Wait for function to complete.


dbOn
DC Braking

Cause: This code conveys the DC Injection function being carried out.


Remedy:

  • Display shows db when braking.

  • Display shows dbOn when the motor shaft stationary function is being carried out.


CM1
Comm1 Error

Cause: Internal communications error.


Remedy:

  • Improperly programmed ASD.

  • Improper communications settings.

  • Improperly connected cables.


CM2
Comm2 Error

Cause: External communications error.


Remedy:

  • Improperly programmed ASD.

  • Improper communications settings.

  • Improperly connected cables.


E
Emergency Off

Cause: Output signal from the ASD is terminated and a brake may be applied if so configured.


Remedy:

  • Stop|Reset pressed twice at the EOI.

  • EOFF command received remotely.

  • ASD reset required.


MOFF
Main Under-Voltage

Cause: Under-voltage condition at the 3-phase AC input to the ASD.


Remedy:

  • Low 3-phase commercial voltage.


OC
Over-Current

Cause: ASD output current greater than F601 setting.


Remedy:

  • Defective IGBT (U, V, or W).

  • ASD output to the motor is connected incorrectly.

  • ASD output phase-to-phase short.

  • The ASD is starting into a spinning motor.

  • Motor/machine jammed.

  • Mechanical brake engaged while the ASD is starting or while running.

  • Accel/Decel time is too short.

  • Voltage Boost setting is too high.

  • Load fluctuations.

  • ASD operating at an elevated temperature.


OH
Overheat

Cause: ASD ambient temperature excessive.


Remedy:

  • ASD is operating at an elevated temperature.

  • ASD is too close to heat-generating equipment.

  • Cooling fan vent is obstructed.

  • Cooling fan is inoperative.

  • Internal thermistor is disconnected.


OJ
Timer

Cause: Run-time counter exceeded.


Remedy:

  • Type Reset required; select Clear run timer.


OLI
ASD Overload

Cause: Load requirement in excess of the capability of the ASD.


Remedy:

  • The carrier frequency is too high.

  • An excessive load.

  • Acceleration time is too short.

  • DC damping rate is set too high.

  • The motor is starting into a spinning load after a momentary power failure.

  • The ASD is improperly matched to the application.


OLM
Motor Overload

Cause: Load requirement in excess of the capability of the motor.


Remedy:

  • V/f parameter improperly set.

  • Motor is locked.

  • Continuous operation at low speed.

  • The load is in excess of what the motor can deliver.


OLR
Resistor Overload

Cause: Excessive current at the Dynamic Braking Resistor.


Remedy:

  • Deceleration time is too short.

  • DBR configuration improperly set.


OP
Over-Voltage

Cause: DC bus voltage exceeds specifications.


Remedy:

  • ASD attempting to start into a spinning motor after a momentary power loss.

  • Incoming commercial power is above the specified range.

  • Decel time is too short.

  • Voltage spikes at the 3-phase input; install inductive filter.

  • DBR required.

  • DBR resistance value is too high.

  • DBR function is turned off.

  • Over-Voltage Stall feature is turned off.

  • System is regenerating.

  • Load instability.

  • Disable the Ridethrough function (F302).


OT
Over-Torque

Cause: Torque requirement is in excess of the setting of F616 or F617 for a time longer than the setting of F618.


Remedy:

  • ASD is not correctly matched to the application.

  • F616 or F617 setting is too low.

  • Obstructed load.


POFF
Control Under-Voltage

Cause: Under-voltage condition at the 5, 15, or the 24 VDC supply.


Remedy:

  • Defective Control board.

  • Excessive load on power supply.

  • Low input voltage.


PtSt
Reference Point

Cause: Two speed-reference frequency setpoint values are too close to each other.


Remedy:

  • Two speed reference frequency setpoints are too close to each other (increase the difference).


UC
Under-Current

Cause: Output current of the ASD is below the level defined at F611 and remains there for a time longer than the setting of F612.


Remedy:

  • Output current too low.


E-10
Sink/Source Setting Error

Cause: Sink/Source configuration is incorrect.


Remedy:

  • Improperly positioned Sink/Source jumper on the Terminal board or on an option device (see J100).

  • Check Sink/Source configuration.


E-11
Brake Sequence Response Error

Cause: Braking sequence error.


Remedy:

  • F630 is set to a non-zero value.

  • Braking sequence discrete input and output terminals are not setup properly.


E-12
Encoder Signal-Loss Error

Cause: ASD is configured to receive a signal from a shaft-mounted encoder and no signal is being received while running.


Remedy:

  • Disconnection at the Encoder circuit.

  • Motor is stopped and is generating torque via torque limit control.

  • ASD is not configured properly.


E-13
Speed Error

Cause: Result of a motor speed that is greater than the commanded speed when using an encoder for speed control.


Remedy:

  • Improper encoder connection or setup information.

  • Defective encoder.


E-17
Key Failure

Cause: Key failure detected.


Remedy:

  • Same key input for 20 seconds or more.


E-18
Analog (Terminal) Input Loss

Cause: V/I signal loss.


Remedy:

  • Terminal Board failure.

  • P24 over-current condition.

  • F633 setting is too high.


E-19
CPU Communication Error

Cause: CPU data Transmit/Receive error.


Remedy:

  • Check CPU communications.


E-20
V/f Control Error

Cause: Torque processing error.


Remedy:

  • Make service call.


E-21
CPU Processing Error

Cause: Software processed incorrectly.


Remedy:

  • Make service call.


E-22
Logic Input Voltage Error

Cause: Incorrect voltage applied to the discrete input terminals.


Remedy:

  • Check input terminal voltages.


E-23
Optional Expansion Input Terminal Board 1 Error

Cause: Optional Expansion Input Terminal Board 1 is defective.


Remedy:

  • Replace board.


E-24
Optional Expansion Input Terminal Board 2 Error

Cause: Optional Expansion Input Terminal Board 2 is defective.


Remedy:

  • Replace board.


E-25
Stop Positioning Retention Error

Cause: Load movement while stopped.


Remedy:

  • F381 setting is too low.

  • Encoder malfunction.

  • Creep speed is too high.


E-26
CPU2 Fault

Cause: CPU malfunction.


Remedy:

  • Control board malfunction.


E-50 / E-51
Sink/Source Setting Error

Cause: Sink/Source configuration is incorrect.


Remedy:

  • Improperly positioned Sink/Source jumper on the Terminal board or on an option device (see J100).


EEP1
EEPROM Fault

Cause: EEPROM write malfunction.


Remedy:

  • Make a service call.


EEP2 / EEP3
EEPROM Read Error

Cause: EEPROM read malfunction.


Remedy:

  • Make a service call.


EF1 / EF2
(Earth) Ground Fault

Cause: Ground fault at output.


Remedy:

  • Ground fault at the motor.

  • Ground fault at the output of the ASD.

  • Current leakage to Earth Ground.


EPHI
Input Phase Failure

Cause: 3-phase input to the ASD is low or missing at the R, S, or T input terminals.


Remedy:

  • Check input power wiring.


EPHO
Output Phase Failure

Cause: 3-phase output from the ASD is low or missing at the U, V, or W output terminals or at the input to the motor.


Remedy:

  • Check output wiring and motor.


ERR2
RAM Fault

Cause: Internal RAM malfunction.


Remedy:

  • Make a service call.


ERR3
ROM Fault

Cause: Internal ROM malfunction.


Remedy:

  • Make a service call.


ERR4
CPU Fault

Cause: CPU malfunction.


Remedy:

  • Control board malfunction.

  • Make a service call.


ERR5
Communication Error

Cause: Communication time out error or malfunction.


Remedy:

  • Improper or loose connection.

  • Improper system settings.


ERR6
Gate Array Fault

Cause: Main Gate Array is defective.


Remedy:

  • Make a service call.


ERR7
Low-Current

Cause: Improper Low-Current detection level settings.


Remedy:

  • Check settings at F609 – F612.


ERR8
Option Device Fault

Cause: Option device error.


Remedy:

  • Check installation, connections, and option device manual.


ERR9
Flash Memory Fault

Cause: Flash memory malfunction.


Remedy:

  • Make a service call.


ETN
Autotune Error

Cause: Autotune readings that are significantly inconsistent with the configuration information.


Remedy:

  • A non-3-phase motor is being used.

  • Incorrect settings at F400 or F413.

  • Using a motor that has a significantly smaller rating than the ASD.

  • ASD output cabling is too small, too long, or is being housed in a cable tray with other cables that are producing an interfering EMF.

  • Motor is running during the Autotune function.


ETN1
Autotune Error 1

Cause: Autotune adjustment required.


Remedy:

  • F402 adjustment required (Motor temperature is too high).

  • F410 adjustment required (Motor Constant 1 improperly set).


ETN2
Autotune Error 2

Cause: Autotune adjustment required.


Remedy:

  • F412 adjustment required (Motor Constant 3 improperly set).


ETN3
Autotune Error 3

Cause: Problem with Motor Constant readings.


Remedy:

  • Autotune setting F400 is set to Auto Calculation.


ETYP
Typeform Error

Cause: Firmware information (typeform) loaded into the Gate Driver board is inconsistent with the device.


Remedy:

  • The Gate Driver board has been replaced.

  • The Gate Driver board is defective.


None
No Errors

Cause: No active faults.


Remedy:

  • System Normal.


OC1
Over-Current During Acceleration

Cause: Over-Current condition during startup/acceleration.


Remedy:

  • Improper V/f setting.

  • Restart from a momentary power outage.

  • The ASD is starting into a rotating motor.

  • ASD/Motor not properly matched.

  • Phase-to-phase short (U, V, or W).

  • Accel time too short.

  • Voltage Boost setting is too high.

  • Motor/machine jammed.

  • Mechanical brake engaged while the ASD is running.

  • ASD current exceeds 340% of the rated FLA (or 320% for >100HP).


OC1P
Overheat During Acceleration

Cause: Overheating detected during acceleration.


Remedy:

  • Cooling fan inoperative.

  • Ventilation openings are obstructed.

  • Internal thermistor is disconnected.

  • Acceleration time is too short.

  • Improper V/f setting.

  • ASD or the motor is improperly matched to the application.


OC2
Over-Current During Deceleration

Cause: Over-Current condition during deceleration.


Remedy:

  • Phase-to-phase short (U, V, or W).

  • Deceleration time is too short.

  • Motor/machine jammed.

  • Mechanical brake engaged while the ASD is running.

  • ASD current exceeds thresholds (340% or 320%).


OC2P
Overheat During Deceleration

Cause: Overheating detected during deceleration.


Remedy:

  • Cooling fan inoperative.

  • Ventilation openings are obstructed.

  • Internal thermistor is disconnected.

  • Deceleration time is too short.

  • DC Injection current is too high.

  • ASD or the motor is improperly matched to the application.


OC3
Over-Current During Run

Cause: Over-Current condition during constant speed run.


Remedy:

  • Load fluctuations.

  • ASD is operating at an elevated temperature.

  • ASD current exceeds thresholds (340% or 320%).


OC3P
Overheat During Run

Cause: Overheating detected during run.


Remedy:

  • Cooling fan inoperative.

  • Ventilation openings are obstructed.

  • Internal thermistor is disconnected.

  • Improper V/f setting.

  • ASD or the motor is improperly matched to the application.


OCA1 / OCL
U-Phase Over-Current

Cause: Low impedance at the U lead of the ASD output.


Remedy:

  • Check output cabling and motor.


OCA2 / OCL
V-Phase Over-Current

Cause: Low impedance at the V lead of the ASD output.


Remedy:

  • Check output cabling and motor.


OCA3 / OCL
W-Phase Over-Current

Cause: Low impedance at the W lead of the ASD output.


Remedy:

  • Check output cabling and motor.


OCR
Dynamic Braking Resistor Over-Current

Cause: ASD inability to discharge the bus voltage during regeneration.


Remedy:

  • No dynamic braking resistor (DBR) installed.

  • Deceleration time is too short.

  • Improper DBR setup information.

  • Defective IGBT7 (or IGBT7 ckt.).

  • 3-phase input voltage is above specification.


OH2
External Overheat

Cause: Excessive-heat signature received at the TB3 terminals.


Remedy:

  • Check TH1(+) and TH1(-) terminals.

  • See F637 for setup information.


OL1
ASD Overload

Cause: ASD Overload detected.


Remedy:

  • Acceleration time is too short.

  • DC Injection current is too high.

  • Improper V/f setting.

  • Motor running during restart.

  • ASD or the motor is improperly matched to the application.


OL2
Motor Overload

Cause: Motor Overload detected.


Remedy:

  • Improper V/f setting.

  • Motor is locked.

  • Continuous operation at low speed.

  • Load requirement exceeds ability of the motor.

  • Startup frequency setting adjustment required.


OLR
Dynamic Braking Resistor Overload

Cause: Resistor Overload detected.


Remedy:

  • Deceleration time is too short.

  • DBR setting adjustment required.

  • Over-Voltage Stall setting adjustment required.


OP1
Over-Voltage During Acceleration

Cause: Motor running during restart.


Remedy:

  • Check restart conditions.


OP2
Over-Voltage During Deceleration

Cause: Over-Voltage detected during deceleration.


Remedy:

  • Deceleration time is too short.

  • DBR value is too high.

  • DBR required (DBR setup required).

  • Stall protection is disabled.

  • 3-phase input voltage is out of specification.

  • Input reactance required.


OP3
Over-Voltage During Run

Cause: Over-Voltage detected during run.


Remedy:

  • Load fluctuations.

  • 3-Phase input voltage out of specification.

  • DBR required (DBR setup required).


OT
Over-Torque

Cause: Torque requirement by the load is in excess of the setting of F616 or F617 for a time longer than the setting of F618.


Remedy:

  • The ASD is improperly matched to the application.

  • The load is obstructed.


SOUT
Step-Out (for PM Motor Only)

Cause: Step-Out condition detected.


Remedy:

  • Motor shaft is locked.

  • Output phase is open.

  • Operating a reciprocating load.


UP1
Main Power Under-Voltage

Cause: Input 3-phase voltage is too low.


Remedy:

  • Momentary power failure longer than the time setting of F628.


UP2
Control Power Under-Voltage

Cause: Under-voltage condition at the 5, 15, or the 24 VDC supply.


Remedy:

  • 3-phase input voltage low.


How to Clear & Reset Toshiba H9 Drive Faults

  1. Keypad Reset (EOI): Press the red STOP/RESET key on the Electronic Operator Interface (EOI). When a fault occurs, the graphical LCD screen will flash the active trip code and failure description. Pressing STOP/RESET once the cause is resolved clears the fault and returns the drive to standby mode.
  2. Control Terminal Reset (RES): Momentarily close a dry contact between the programmable digital input terminal configured as RES (Reset) and control common terminal CC. The pulse must meet the debounce filter requirement programmed in terminal parameters (F111–F118).
  3. Parameter Re-initialization (tyP): Navigate to the Program ⇒ Fundamental Parameters ⇒ Standard Setting Mode or access direct access parameter tyP via the keypad dial to clear fault logs or restore factory defaults if parameter registers were corrupted.
  4. Fieldbus / Serial Network Reset: If equipped with ASD-NANOCOM or optional communication cards (Modbus RTU, Ethernet/IP, Profibus-DP, DeviceNet), transmit a trip clear bit command (Bit 7 of Command Control Word) from your master controller (PLC/DCS).
  5. Mains Power Cycle: Switch off the primary 3-phase incoming AC line disconnect (terminals R/L1, S/L2, T/L3). Allow at least 15 minutes for the internal high-capacity DC bus filter capacitors to fully discharge and verify that the red charge indicator LED is completely unlit before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] (or terminals PO and PC) before inspecting motor leads, opening terminal enclosures, or touching output load terminals T1/U, T2/V, and T3/W on the Toshiba H9 drive.