Toshiba Q7 Drive Fault Codes & Diagnostic Guide

Complete fault code directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba Q7 HVAC and pump adjustable speed drive series. Search or filter through the complete fault code directory below.

Dedicated HVAC & Pump ASD Power: 1 to 400 HP (0.75 to 300 kW) Built-in BACnet & Metasys N2
Power Range 1 – 400 HP (0.75 – 300 kW)
Supply Voltage 200–240V / 380–480V (3-Phase)
Control Modes Variable Torque V/f & Vector
Operator Interface Plain-English LCD & HOA Keypad

Complete Toshiba Q7 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OP3, OL2, or Overcurrent).

Fault Code and MeaningCause and Remedy
CM1

Comm1 Error (Internal communications error)

Cause:

  • Improperly programmed ASD.

  • Improper communications settings.

  • Improperly connected cables.




Remedy:

  • Check internal communication settings and cabling.


CM2

Comm2 Error (External communications error)

Cause:

  • Improper communications settings.

  • Improperly connected cables.




Remedy:

  • Verify external communication device settings and wiring.


EMG

Emergency Off

Cause:

  • Stop|Reset pressed twice at the keypad.

  • EOFF command received remotely.




Remedy:

  • ASD reset required.


MOFF

Main Undervoltage

Cause:

  • Low 3-phase utility voltage.

  • Undervoltage condition at the 3-phase AC input.




Remedy:

  • Check input power supply.


OC

Over Current

Cause:

  • Defective IGBT (U, V, or W).

  • ASD output phase-to-phase short.

  • The ASD is starting into a spinning motor.

  • Motor/machine jammed.

  • Mechanical brake engaged while the ASD is starting/running.

  • Accel/Decel time is too short.

  • Voltage Boost setting is too high.

  • Load fluctuations.




Remedy:

  • ASD output to the motor is connected incorrectly. Disconnect the motor and retry.

  • Check for jammed motor/machine.

  • Adjust Accel/Decel time.


*OH

Overheat

Cause:

  • ASD is operating at an elevated temperature.

  • ASD is too close to heat-generating equipment.

  • Cooling fan vent is obstructed.

  • Cooling fan is inoperative.

  • Internal thermistor is disconnected.




Remedy:

  • Check clearance and ventilation (see Mounting instructions).

  • Replace cooling fan if inoperative.


OJ

Timer (Run-time counter exceeded)

Cause:

  • Run-time counter limit reached.




Remedy:

  • Type Reset required; select Clear run timer.


*OLI

ASD Overload

Cause:

  • The carrier frequency is too high.

  • An excessive load.

  • Acceleration time is too short.

  • DC damping rate is set too high.

  • The motor is starting into a spinning load after a momentary power failure.

  • The ASD is improperly matched to the application.




Remedy:

  • Reduce carrier frequency.

  • Increase acceleration time.

  • Verify ASD sizing for the application.


OLM

Motor Overload

Cause:

  • V/f parameter improperly set.

  • Motor is locked.

  • Continuous operation at low speed.

  • The load is in excess of what the motor can deliver.




Remedy:

  • Adjust V/f parameters.

  • Check for locked motor.


*OLR

Resistor Overload

Cause:

  • Excessive current at the Dynamic Braking Resistor.

  • Deceleration time is too short.

  • DBR configuration improperly set.




Remedy:

  • Increase deceleration time.

  • Check DBR settings.


*OP

Overvoltage

Cause:

  • ASD attempting to start into a spinning motor after momentary power loss.

  • Incoming utility power is above the specified range.

  • Decel time is too short.

  • DBR resistance value is too high or DBR function turned off.

  • Overvoltage Stall feature is turned off.

  • System is regenerating.

  • Load instability.




Remedy:

  • Install inductive filter for voltage spikes.

  • DBR required.

  • Disable the Ridethrough function (F302).


OT

Overtorque

Cause:

  • ASD is not correctly matched to the application.

  • Parameter F616 or F617 setting is too low.

  • Obstructed load.




Remedy:

  • Adjust torque parameters.

  • Clear load obstruction.


*POFF

Control Undervoltage

Cause:

  • Defective Control board.

  • Excessive load on power supply.

  • Low input voltage.

  • Undervoltage condition at the 5, 15, or the 24 VDC supply.




Remedy:

  • Check control board and power supply load.


PtSt

Reference Point

Cause:

  • Two speed-reference frequency setpoints are too close to each other.




Remedy:

  • Increase the difference between the setpoints.


UC

Undercurrent

Cause:

  • Output current is below level defined at F611 for time set at F612.




Remedy:

  • Check load connection and parameters F611/F612.


Atn

Autotune Active

Cause:

  • Indicates that the Autotune function is active.




Remedy:

  • Wait for Autotune to complete.


db / dbOn

DC Braking Active

Cause:

  • DC Injection function being carried out.

  • dbOn appears when Shaft Stationary function is active.




Remedy:

  • Notification only. No action required unless unexpected.


Inverter (ASD) OL

Inverter Overload Trip

Cause:

  • Acceleration time is too short.

  • DC Injection current is too high.

  • V/f setting needs to be adjusted.

  • Motor running during restart.

  • ASD or the motor is improperly matched to the application.




Remedy:

  • Increase acceleration time.

  • Adjust V/f settings or DC injection parameters.


Autotuning Err

Autotuning Error

Cause:

  • Readings significantly inconsistent with configuration.

  • A non-3-phase motor is being used.

  • Incorrect settings at parameter F400, F413, or F414.

  • Using a motor significantly smaller than the ASD rating.

  • ASD output cabling is too small, too long, or has interfering EMF.

  • Motor is running during Autotune.




Remedy:

  • Verify motor type and parameter settings.

  • Ensure motor is stopped before Autotuning.


Comm Error

Communication Error

Cause:

  • Communication malfunction.

  • Improper or loose connection.

  • Improper system settings.




Remedy:

  • Check connections and settings.


Ctrl Undervolts

Control Undervoltage

Cause:

  • Undervoltage condition at the 5, 15, or 24 VDC supply.

  • 3-phase input voltage low.




Remedy:

  • Check input voltage levels.


CPU Error

CPU Malfunction

Cause:

  • CPU malfunction.




Remedy:

  • Contact service if power cycle does not resolve.


Main Undervolts

Main Undervoltage

Cause:

  • 3-phase input voltage low.

  • Defective control board.

  • Excessive load on the power supply.

  • Undervoltage/Ridethrough settings require adjustment.




Remedy:

  • Check mains voltage and power supply load.


Fuse

Fuse Open

Cause:

  • Internal DC bus fuse is open.




Remedy:

  • Check for short circuits; Replace fuse/ASD.


DBR Overcurrent

DBR Overcurrent

Cause:

  • ASD inability to discharge the bus voltage during regeneration.

  • No dynamic braking resistor (DBR) installed.

  • Deceleration time is too short.

  • Improper DBR setup information.

  • Defective IGBT7 (or IGBT7 ckt.).

  • 3-phase input voltage is above specification.




Remedy:

  • Install DBR or check DBR setup.

  • Increase deceleration time.


DBR Overload

DBR Overload

Cause:

  • Deceleration time is too short.

  • DBR setting adjustment required.

  • Overvoltage Stall setting adjustment required.




Remedy:

  • Adjust Decel time and Stall settings.


GND Fault

Ground Fault

Cause:

  • Ground fault at the motor.

  • Ground fault at the output of the ASD.

  • Current leakage to Earth Ground.




Remedy:

  • Check motor and output wiring for shorts to ground.


Ctrl EEPROM Err

Control EEPROM Error

Cause:

  • Internal EEPROM malfunction.




Remedy:

  • Contact service.


EEPROM Write Err

EEPROM Write Error

Cause:

  • EEPROM write malfunction.




Remedy:

  • Retry operation or contact service.


E-Off

Emergency Off

Cause:

  • Emergency Off command received via keypad or remotely.




Remedy:

  • Reset ASD.


Encoder Loss

Encoder Loss

Cause:

  • Encoder signal missing while running during closed-loop operation.




Remedy:

  • Check encoder connections.


Flash Error

Flash Memory Error

Cause:

  • Flash memory malfunction.




Remedy:

  • Contact service.


Gate Array Error

Gate Array Error

Cause:

  • Defective Gate Array or Gate Array malfunction.




Remedy:

  • Contact service; Board replacement may be required.


In(put) Phase Loss

Input Phase Loss

Cause:

  • 3-phase input to the ASD is low or missing.




Remedy:

  • Check input power phases.


Load Drooping

Load Drooping

Cause:

  • Load requirement is in excess of the capabilities of the motor.




Remedy:

  • Reduce load or resize motor.


Load End OC

Load End Overcurrent

Cause:

  • Improper wiring at the ASD output to the motor.




Remedy:

  • Check output wiring.


Under Curr(ent) Trip

Undercurrent Trip

Cause:

  • Improper Low Current detection level setting.




Remedy:

  • Adjust detection level settings.


Main EEPROM Err

Main EEPROM Error

Cause:

  • Internal EEPROM malfunction.




Remedy:

  • Contact service.


Motor Overload

Motor Overload

Cause:

  • V/f setting needs to be adjusted.

  • Motor is locked.

  • Continuous operation at low speed.

  • Load requirement exceeds ability of the motor.

  • Startup frequency setting adjustment required.




Remedy:

  • Check for locked motor.

  • Adjust V/f and startup parameters.


Option PCB Error

Option PCB Error

Cause:

  • Optional device malfunction.

  • Improper system settings (at ASD or optional device).

  • Loose or improper connection.




Remedy:

  • Check connections and settings of optional devices.


Out(put) Phase Loss

Output Phase Loss

Cause:

  • 3-phase output from the ASD is low or missing.




Remedy:

  • Check motor connections and ASD output.


Overcurrent Acc

Overcurrent during Accel

Cause:

  • V/f setting needs to be adjusted.

  • Restart from a momentary power outage.

  • The ASD is starting into a rotating motor.

  • ASD/Motor not properly matched.

  • Phase-to-phase short (U, V, or W).

  • Accel time too short.

  • Voltage Boost setting is too high.

  • Motor/machine jammed or brake engaged.

  • ASD current exceeds rated limit (340% or 320% depending on HP) during acceleration.




Remedy:

  • Adjust Accel time and Voltage Boost.

  • Check for shorts or mechanical jams.


Overcurrent Dec

Overcurrent during Decel

Cause:

  • Phase-to-phase short (U, V, or W).

  • Deceleration time is too short.

  • Motor/machine jammed or brake engaged.

  • ASD current exceeds rated limit (340% or 320%) during deceleration.




Remedy:

  • Increase Decel time.

  • Check for shorts or jams.


Overcurrent Run

Overcurrent during Run

Cause:

  • Load fluctuations.

  • ASD is operating at an elevated temperature.

  • ASD current exceeds rated limit during fixed-speed run.




Remedy:

  • Check load conditions and cooling.


Overheat

Overheat

Cause:

  • Cooling fan inoperative.

  • Ventilation openings are obstructed.

  • Internal thermistor is disconnected.




Remedy:

  • Clean vents and check fans.


Speed Error

Speed Error

Cause:

  • Motor speed is greater than commanded speed (with encoder).

  • Improper encoder connection or setup.

  • Defective encoder.




Remedy:

  • Check encoder and setup.


Overtorque

Overtorque

Cause:

  • Torque requirement in excess of settings (F616/F617) for time set at F618.

  • ASD improperly matched to application.

  • Load is obstructed.




Remedy:

  • Clear obstructions.

  • Adjust torque limits if safe.


Overvolt Accel

Overvoltage during Accel

Cause:

  • Motor running during restart.




Remedy:

  • Ensure motor is stopped or enable catch-on-fly if available.


Overvolt Decel

Overvoltage during Decel

Cause:

  • Deceleration time is too short.

  • DBR value is too high or DBR required.

  • Stall protection is disabled.

  • 3-phase input voltage out of specification.

  • Input reactance required.




Remedy:

  • Increase Decel time.

  • Install/Check DBR.


Overvolt Run

Overvoltage during Run

Cause:

  • Load fluctuations.

  • 3-Phase input voltage out of specification.




Remedy:

  • Check input voltage stability.


Positional Err

Positional Error

Cause:

  • Resulting position exceeds limits of Position Control setting.




Remedy:

  • Check position control settings and limits.


RAM/ROM Err

RAM or ROM Error

Cause:

  • Internal RAM or ROM malfunction.




Remedy:

  • Contact service.


Sink/Source Error

Sink/Source Configuration Error

Cause:

  • Improperly positioned Sink/Source jumper.

  • Sink/Source configuration of option device is incorrect.




Remedy:

  • Check jumper positions and option device configuration.


Type(form) Error

Typeform Error

Cause:

  • Firmware information loaded into Gate Driver board is inconsistent with device.

  • Gate Driver board has been replaced or is defective.




Remedy:

  • Verify firmware version and board compatibility.


U/V/W Phase OC

Phase Overcurrent (U, V, or W)

Cause:

  • Low impedance at the U, V, or W lead of the ASD output.




Remedy:

  • Check output cabling and motor insulation for shorts.


How to Clear & Reset Toshiba Q7 Drive Faults

  1. Keypad Reset: Press the red STOP/RESET key on the Electronic Operator Interface (EOI). When a trip condition occurs, pressing STOP/RESET acknowledges the fault and clears the screen once the abnormal operating condition has returned to normal limits.
  2. Terminal Board Reset: Momentarily close an external dry contact across the assigned reset terminal (default terminal RES) and control common CC for at least 20 ms, then release.
  3. Building Automation System (BAS) Reset: Send a remote trip reset command across the embedded communication network (BACnet MS/TP, Metasys N2, Modbus RTU, or optional LonWorks) via the network control word.
  4. ASD Pro Diagnostic Software: Connect via the RS-232/RS-485 serial communication port using Toshiba’s ASD Pro software tool, check the fault history and operating status logs, and issue a remote software reset.
  5. Mains Power Cycle: Disconnect the main incoming AC line power (R/L1, S/L2, T/L3), wait until the keypad LCD display and internal red CHARGE indicator lamp are fully extinguished (approx. 15 minutes for capacitor bank discharge), and restore power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect incoming main three-phase AC power and wait a minimum of 15 minutes. Use a verified, calibrated digital multimeter to test intermediate DC bus terminals [PA/+] and [PC/-] (or terminals PO, PA, PB, PC) to confirm that voltage has dropped below 50VDC and verify that the internal CHARGE LED is completely extinguished before opening enclosures or touching terminals R/L1, S/L2, T/L3, U/T1, V/T2, and W/T3.