Toshiba G7 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba G7 True Torque Control2 adjustable speed drive series. Search or filter through the complete fault code directory below.
Power Range
1 – 350 HP (0.75 – 260 kW)
Supply Voltage
200–240V / 380–480V / 520–600V
Control Modes
True Torque Control² (Vector & V/f)
Operator Interface
240 x 64 Graphical LCD Keypad (EOI)
Complete Toshiba G7 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| CM1 Comm1 Error | Cause: Internal communications error. Remedy:
|
| CM2 Comm2 Error | Cause: External communications error. Remedy:
|
| EMG Emergency Off | Cause: Output signal from the ASD is terminated and a brake may be applied if so configured. Remedy:
|
| MOFF Main Undervoltage | Cause: Undervoltage condition at the 3-phase AC input to the ASD. Remedy:
|
| OC Over Current | Cause: ASD output current greater than F601 setting. Remedy:
|
| OH Overheat | Cause: ASD ambient temperature excessive. Remedy:
|
| OJ Timer | Cause: Run-time counter exceeded. Remedy:
|
| OLI ASD Overload | Cause: Load requirement in excess of the capability of the ASD. Remedy:
|
| OLM Motor Overload | Cause: Load requirement in excess of the capability of the motor. Remedy:
|
| OLR Resistor Overload | Cause: Excessive current at the Dynamic Braking Resistor. Remedy:
|
| OP Overvoltage | Cause: DC bus voltage exceeds specifications. Remedy:
|
| OT Overtorque | Cause: Torque requirement in excess of the setting of F616 or F617 for a time longer than the setting of F618. Remedy:
|
| POFF Control Undervoltage | Cause: Undervoltage condition at the 5, 15, or the 24 VDC supply. Remedy:
|
| PtSt Reference Point | Cause: Two speed-reference frequency setpoint values are too close to each other. Remedy:
|
| UC Undercurrent | Cause: Output current of the ASD is below the level defined at F611 and remains there for the time set at F612. Remedy:
|
| Autotune Error Autotune Malfunction | Cause: Autotune readings that are significantly inconsistent with the configuration information. Remedy:
|
| Communication Error Comms Malfunction | Cause: System communication failure. Remedy:
|
| CPU Fault Processor Error | Cause: Internal processor error. Remedy:
|
| DC Bus Undervoltage Bus Voltage Low | Cause: DC Bus voltage dropped below limit. Remedy:
|
| DC Fuse Open Internal Fuse Blown | Cause: Internal DC bus fuse is open. Remedy:
|
| Dynamic Braking Resistor Overcurrent DBR Overcurrent | Cause: ASD inability to discharge the bus voltage during regeneration. Remedy:
|
| Earth Fault Ground Fault | Cause: Current leakage to Earth Ground detected. Remedy:
|
| EEPROM Data Fault Memory Error | Cause: Internal EEPROM malfunction. Remedy:
|
| Encoder Loss Signal Missing | Cause: Encoder signal missing while running during closed-loop operation. Remedy:
|
| Gate Array Fault Hardware Failure | Cause: Defective Gate Array or Gate Array malfunction. Remedy:
|
| Input Phase Loss Phase Missing | Cause: 3-phase input to the ASD is low or missing. Remedy:
|
| Load Drooping Load Error | Cause: Load requirement is in excess of the capabilities of the motor. Remedy:
|
| Load End Short Circuit Output Short | Cause: Improper wiring at the ASD output to the motor. Remedy:
|
| Low Current Current Low | Cause: Improper Low Current detection level setting. Remedy:
|
| Option Fault Card Error | Cause: Optional device malfunction. Remedy:
|
| Output Phase Loss Motor Phase Lost | Cause: 3-phase output from the ASD is low or missing. Remedy:
|
| Overcurrent During Acceleration Accel OC | Cause: Overcurrent detected while ramping up speed. Remedy:
|
| Overcurrent During Deceleration Decel OC | Cause: Overcurrent detected while ramping down speed. Remedy:
|
| Overcurrent During Run Run OC | Cause: Overcurrent detected at constant speed. Remedy:
|
| Over Speed Speed Limit Exceeded | Cause: Result of a motor speed that is greater than the commanded speed when using an encoder for speed control. Remedy:
|
| PG Type/Connection Error Encoder Error | Cause: ASD is configured to receive a signal from a shaft-mounted encoder and no signal is being received. Remedy:
|
| Phantom Fault System Fault | Cause: In a multiple ASD configuration a faulted ASD signals the remaining ASDs that a fault has occurred. Remedy:
|
| Position Deviation Error Position Error | Cause: Operating in the Position Control mode and the resulting position exceeds the limits of the F631 setting. Remedy:
|
| Sink/Source Setting Error Jumper Error | Cause: Logic setting mismatch. Remedy:
|
| Torque Proving Fault Brake Logic Error | Cause: Torque proving logic failed. Remedy:
|
| Typeform Error Firmware Mismatch | Cause: Firmware information loaded into the Gate Driver board is inconsistent with the device. Remedy:
|
| U/V/W Phase Short Circuit Output Short | Cause: Low impedance at the U, V, or W lead of the ASD output. Remedy:
|
How to Clear & Reset Toshiba G7 Drive Faults
- Keypad Reset (EOI): Press the red STOP/RESET key on the front Electronic Operator Interface (EOI). When a fault occurs, the graphical LCD screen will flash the trip code and description. Pressing the STOP/RESET key after eliminating the root cause resets the fault condition.
- Control Terminal Reset (RES): Momentarily close a dry contact between the programmable digital input terminal configured as RES (Reset) and common control terminal CC. The contact closure must satisfy the programmed input filter delay time in parameter F143.
- Parameter Re-initialization (tyP): Open Program Mode on the EOI keypad, navigate to the Utility / Reset parameter group, and select parameter tyP (Reset Selection) to clear the fault log or restore standard factory defaults if memory corruption occurred.
- Serial Fieldbus Reset: If networked via Modbus RTU, Profibus-DP, Ethernet/IP, or DeviceNet option modules, transmit a trip clear bit command (Bit 7 of the drive command control word) from your master controller (PLC/DCS).
- Mains Power Cycle: Switch off the main incoming 3-phase AC supply line (terminals R/L1, S/L2, T/L3). Allow at least 10 minutes for the internal DC bus filter capacitors to discharge and the front charge lamp to extinguish completely before restoring AC power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] (or terminals PO and PC) before inspecting motor leads, opening terminal enclosures, or touching output load terminals T1/U, T2/V, and T3/W on the Toshiba G7 drive.