Toshiba G9 Drive Fault Codes & Diagnostic Guide
Complete fault code directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba G9 severe duty adjustable speed drive (ASD) series. Search or filter through the complete fault code directory below.
Power Range
1 – 350 HP (0.75 – 250 kW)
Supply Voltage
200–240V / 380–480V (3-Phase)
Control Modes
V/f, Sensorless & Closed-Loop Vector
Operator Interface
Plain-English LED/LCD & Rotary Dial
Complete Toshiba G9 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type OC1, OP2, OL1, or Overcurrent).
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| Atn Autotune Active | Cause: Indicates that the Autotune function is active. Remedy:
|
| dbOn DC Braking | Cause: This code conveys the DC Injection function is being carried out. The display shows db when braking and shows dbOn when the motor shaft stationary function is being carried out. Remedy:
|
| CM1 Comm1 Error | Cause: Internal communications error. Remedy:
|
| CM2 Comm2 Error | Cause: External communications error. Remedy:
|
| E Emergency Off | Cause: Output signal from the ASD is terminated and a brake may be applied if so configured. Remedy:
|
| MOFF Main Under-Voltage | Cause: Under-voltage condition at the 3-phase AC input to the ASD. Remedy:
|
| OC Over-Current | Cause: ASD output current greater than F601 setting. Remedy:
|
| *OH Over-Heat | Cause: ASD ambient temperature excessive. Remedy:
|
| OJ Timer | Cause: Run-time counter exceeded. Remedy:
|
| *OLI ASD Overload | Cause: Load requirement in excess of the capability of the ASD. Remedy:
|
| OLM Motor Overload | Cause: Load requirement in excess of the capability of the motor. Remedy:
|
| *OLR Resistor Overload | Cause: Excessive current at the Dynamic Braking Resistor. Remedy:
|
| *OP Over-Voltage | Cause: DC bus voltage exceeds specifications. Remedy:
|
| OT Over-Torque | Cause: Torque requirement in excess of the setting of F616 or F617 for a time longer than the setting of F618. Remedy:
|
| *POFF Control Under-Voltage | Cause: Under-voltage condition at the 5, 15, or the 24 VDC supply. Remedy:
|
| PtSt Reference Point | Cause: Two speed-reference frequency setpoint values are too close to each other. Remedy:
|
| UC Under-Current | Cause: Output current is below the level defined at F611 for longer than F612 (with F610 enabled). Remedy:
|
| E-10 Sink/Source Setting Error | Cause: Sink/Source configuration is incorrect. Remedy:
|
| E-11 Brake Sequence Response Error | Cause: F630 is set to a non-zero value, or setup issue. Remedy:
|
| E-12 Encoder Signal-Loss Error | Cause: ASD is configured to receive a signal from a shaft-mounted encoder and no signal is being received while running. Remedy:
|
| E-13 Speed Error | Cause: Result of a motor speed that is greater than the commanded speed when using an encoder for speed control. Remedy:
|
| E-18 Analog (Terminal) Input Loss | Cause: V/I signal loss or terminal failure. Remedy:
|
| E-19 CPU Communication Error | Cause: CPU data Transmit/Receive error. Remedy:
|
| E-20 V/f Control Error | Cause: Torque processing error. Remedy:
|
| EF1 / EF2 (Earth) Ground Fault | Cause: Current leakage to Earth Ground. Remedy:
|
| EPHI Input Phase Failure | Cause: 3-phase input to the ASD is low or missing at the R, S, or T input terminals. Remedy:
|
| EPHO Output Phase Failure | Cause: 3-phase output from the ASD is low or missing at the U, V, or W output terminals or at the input to the motor. Remedy:
|
| ERR2 RAM Fault | Cause: Internal RAM malfunction. Remedy:
|
| ETN Autotune Error | Cause: Autotune readings are significantly inconsistent with the configuration information. Remedy:
|
| OC1 Over-Current During Acceleration | Cause: Current exceeded limit during acceleration. Remedy:
|
| OC2 Over-Current During Deceleration | Cause: Current exceeded limit during deceleration. Remedy:
|
| OC3 Over-Current During Run | Cause: Current exceeded limit during constant speed run. Remedy:
|
| OCA1 / OCA2 / OCA3 Phase Over-Current | Cause: Low impedance at the U, V, or W lead of the ASD output. Remedy:
|
| OCR Dynamic Braking Resistor Over-Current | Cause: ASD inability to discharge the bus voltage during regeneration. Remedy:
|
| OP1 Over-Voltage During Acceleration | Cause: DC Bus voltage high during accel. Remedy:
|
| OP2 Over-Voltage During Deceleration | Cause: DC Bus voltage high during decel. Remedy:
|
| UP1 Main Power Under-Voltage | Cause: Input 3-phase voltage is too low. Remedy:
|
How to Clear & Reset Toshiba G9 Drive Faults
- Keypad Reset: Press the STOP/RESET key on the Electronic Operator Interface (EOI). If a trip occurs, pressing the STOP/RESET key once acknowledges the condition and clears the display if the fault condition has been eliminated.
- Terminal Board Reset: Momentarily close a circuit between the assigned discrete reset terminal (factory default RES) and control common CC for at least 20 ms, then reopen.
- ASD Pro PC Software: Connect via the serial communication port (RS-232 / RS-485) using Toshiba’s ASD Pro software, view the fault log memory, and issue a remote fault reset.
- Network Communication Control: Send a reset command by asserting the reset bit (Fault Reset) in the drive control word over Modbus RTU, Ethernet/IP, Profibus-DP, or DeviceNet.
- Power Cycle: Disconnect the main AC incoming power (R/L1, S/L2, T/L3), wait until the EOI display and internal red CHARGE LED lamp are completely unlit (approx. 15 minutes for capacitor discharge), and reapply input power.
⚠️ High-Voltage Electrical Safety Warning:
Always disconnect main three-phase AC power and wait at least 15 minutes. Use a verified digital multimeter to measure across the intermediate DC bus terminals [PA/+] and [PC/-] (or terminals PO, PA, PB, PC) to verify that residual voltage has dropped below 50VDC and confirm that the internal CHARGE LED is completely off before removing terminal shields or inspecting motor leads U/T1, V/T2, and W/T3.