Toshiba NC1 (VF-nC1) Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba TOSVERT VF-nC1 compact micro inverter series. Search or filter through the complete fault code directory below.

Ultra-Compact Micro Inverter Power: 0.1 to 2.2 kW (0.13 to 3.0 HP) Sensorless Vector & V/f Control
Power Range 0.1 – 2.2 kW (0.13 – 3.0 HP)
Supply Voltage 100–120V / 200–240V (1-Ph & 3-Ph)
Control Modes V/f Control & Sensorless Vector
Operator Interface 4-Digit LED & Speed Potentiometer

Complete Toshiba NC1 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, or Overcurrent).

Fault Code and MeaningCause and Remedy
OC1 / OC1P
Overcurrent during acceleration

Cause:

  • The acceleration time (ACC) is too short.

  • The V/F setting is improper.

  • A restart signal is input to the rotating motor after a momentary stop.

  • A special motor (e.g. motor with small impedance) is used.




Remedy:

  • Increase the acceleration time (ACC).

  • Check the V/F parameter.

  • Use F301 (auto-restart) and F302 (ride-through control).

  • Increase or decrease the carrier frequency (F300).


OC2 / OC2P
Overcurrent during deceleration

Cause:

  • The deceleration time (dEC) is too short.




Remedy:

  • Increase the deceleration time (dEC).


OC3 / OC3P
Overcurrent during operation

Cause:

  • The load fluctuates abruptly.

  • The load is in an abnormal condition.




Remedy:

  • Reduce the load fluctuation.

  • Check the load (operated machine).


OCR
Arm overcurrent at start-up

Cause:

  • A main circuit element is defective.




Remedy:

  • Make a service call.


OCL
Overcurrent (load side at start-up)

Cause:

  • The insulation of the output main circuit or motor is defective.

  • The motor has too small impedance.




Remedy:

  • Check the cables and wires for defective insulation.


OP1
Overvoltage during acceleration

Cause:

  • The input voltage fluctuates abnormally.

  • The power supply has a capacity of 200kVA or more.

  • A power factor improvement capacitor is opened or closed.

  • A system using a thyristor is connected to the same power distribution line.

  • A restart signal is input to the rotating motor after a momentary stop.




Remedy:

  • Insert a suitable input reactor.

  • Use F301 (auto-restart) and F302 (ride-through control).


OP2
Overvoltage during deceleration

Cause:

  • The deceleration time (dEC) is too short (Regenerative energy is too large).

  • F305 (overvoltage limit operation) is off.

  • The input voltage fluctuates abnormally.




Remedy:

  • Increase the deceleration time (dEC).

  • Enable F305 (overvoltage limit operation).

  • Insert a suitable input reactor.


OP3
Overvoltage during constant-speed operation

Cause:

  • The input voltage fluctuates abnormally.

  • The motor is in a regenerative state because the load causes the motor to run at a frequency higher than the inverter output frequency.




Remedy:

  • Insert a suitable input reactor.


OL1
Inverter overload

Cause:

  • The acceleration time (ACC) is too short.

  • The DC braking amount is too large.

  • The V/F setting is improper.

  • A restart signal is input to the rotating motor after a momentary stop.

  • The load is too large.




Remedy:

  • Increase the acceleration time (ACC).

  • Reduce the DC braking amount (F251) and the DC braking time (F252).

  • Check the V/F parameter setting.

  • Use F301 (auto-restart) and F302 (ride-through control).

  • Use an inverter with a larger rating.


OL2
Motor overload

Cause:

  • The V/F setting is improper.

  • The motor is locked up.

  • Low-speed operation is performed continuously.

  • An excessive load is applied to the motor during operation.




Remedy:

  • Check the V/F parameter setting.

  • Check the load (operated machine).

  • Adjust OLM to the overload that the motor can withstand during operation in a low speed range.


EPH0
Output phase failure

Cause:

  • A phase failure occurred in the output line of the main circuit.




Remedy:

  • Check the main circuit output line, motor, etc., for phase failure.

  • Enable F605 (Output phase failure detection).


EPH1
Input phase failure

Cause:

  • A phase failure occurred in the input line of the main circuit.

  • The inverter may trip because of EPH1 if switching between acceleration and deceleration is done in succession at intervals of less than 1 second.




Remedy:

  • Check the main circuit input line for phase failure.

  • Enable F608 (input phase failure detection). Set the F608 parameter to 0.


OH
Overheat

Cause:

  • The cooling fan does not rotate.

  • The ambient temperature is too high.

  • The vent is blocked up.

  • A heat generating device is installed close to the inverter.

  • The thermistor in the unit is broken.




Remedy:

  • Restart the operation by resetting the inverter after it has cooled down enough.

  • The fan requires replacement if it does not rotate during operation.

  • Secure sufficient space around the inverter.

  • Do not place any heat-generating device near the inverter.

  • Make a service call.


*UP1
Undervoltage trip (main circuit)

Cause:

  • The input voltage (in the main circuit) is too low.




Remedy:

  • Check the input voltage.

  • Enable F627 (undervoltage trip selection).

  • To cope with a momentary stop due to undervoltage, enable F302 (ride-through control) and F301 (auto-restart).


EF2
Ground fault trip / Arm overcurrent

Cause:

  • A ground fault occurs in the output cable or the motor.

  • A main circuit element is defective.




Remedy:

  • Check the cable and the motor for ground faults.

  • Make a service call.


E
Emergency stop

Cause:

  • During automatic operation or remote operation, a stop command is entered from the operation panel or a remote input device.




Remedy:

  • Reset the inverter.


Err2
Main unit RAM fault

Cause:

  • The control RAM is defective.




Remedy:

  • Make a service call.


Err3
Main unit ROM fault

Cause:

  • The control ROM is defective.




Remedy:

  • Make a service call.


Err4
CPU fault trip

Cause:

  • The control CPU is defective.




Remedy:

  • Make a service call.


Err5
Remote control error

Cause:

  • An error arises during remote operation.




Remedy:

  • Check the remote control device, cables, etc.


Err7
Current detector fault

Cause:

  • The current detector is defective.




Remedy:

  • Make a service call.


EEP1
EEPROM fault 1

Cause:

  • A data writing error occurs.




Remedy:

  • Turn off the inverter, then turn it on again. If it does not recover from the error, make a service call.


EEP2
EEPROM fault 2

Cause:

  • Power supply is cut off during tyP operation and data writing is aborted.




Remedy:

  • Turn the power off temporarily and turn it back on, and then try tyP operation again.


EEP3
EEPROM fault 3

Cause:

  • A data writing error occurs.




Remedy:

  • Turn off the inverter, then turn it on again. If it does not recover from the error, make a service call.


E-18
Break in analog signal cable

Cause:

  • The signal input via VI/S3 is below the analog signal detection level set with F633.




Remedy:

  • Check the cables for breaks and change the setting of F633 if no breaks are found.


E-19
CPU communications error

Cause:

  • A communications error occurs between control CPUs.




Remedy:

  • Make a service call.


E-20
Excessive torque boosted

Cause:

  • The torque boost parameter (vb) is set too high.

  • The impedance of the motor is too small.




Remedy:

  • Decrease the setting of the torque boost parameter (vb).

  • If no improvement results, contact Toshiba Technical Support Center.


OFF
ST terminal OFF

Cause:

  • The ST-CC circuit is opened.




Remedy:

  • Close the ST-CC circuit.


nOFF
Undervoltage in main circuit

Cause:

  • The supply voltage between R, S and T is under voltage.




Remedy:

  • Measure the main circuit supply voltage. If the voltage is at a normal level, the inverter requires repairing.


rtry
Retry in process

Cause:

  • The inverter is in the process of retry.

  • A momentary stop occurred.




Remedy:

  • The inverter is normal if it restarts after several tens of seconds. Be careful of the machine because it may suddenly restart.


Err1
Frequency point setting error

Cause:

  • The frequency setting signals at points 1 and 2 are set too close to each other.




Remedy:

  • Set the frequency setting signals at points 1 and 2 apart from each other.


CLr
Clear command acceptable

Cause:

  • This message is displayed when pressing the STOP key while an error code is displayed.




Remedy:

  • Press the STOP key again to clear the trip.


EOFF
Emergency stop command acceptable

Cause:

  • The operation panel is used to stop the operation in automatic control or remote control mode.




Remedy:

  • Press the STOP key for an emergency stop. To cancel the emergency stop, press any other key.


HI / LO
Setting error alarm

Cause:

  • An error is found in a setting when data is reading or writing.




Remedy:

  • Check whether the setting is made correctly.


HEAd / End
Display of first/last data items

Cause:

  • The first or last data item in the data group is displayed.




Remedy:

  • Press the MON key to exit the data group.


db
DC braking

Cause:

  • DC braking in process.




Remedy:

  • The message goes off in several tens of seconds if no problem occurs.


E1
Flowing out of excess number of digits

Cause:

  • The numeric value displayed (e.g., frequency) has a larger number of digits than the display panel.




Remedy:

  • When a frequency is displayed, decrease the setting of F702 (free unit).


StOP
Momentary power failure slowdown stop prohibition

Cause:

  • The slowdown stop prohibition function set with F302 (momentary power failure ride-through operation) is activated.




Remedy:

  • To restart operation, reset the inverter or input an operation signal again.


Init
Parameters in the process of initialization

Cause:

  • Parameters are being initialized to default values.




Remedy:

  • Normal if the message disappears after a while.


E-17
Operation panel key fault

Cause:

  • The RUN or STOP key is held down for more than 5 seconds.

  • The RUN or STOP key is faulty.




Remedy:

  • Check the operation panel.


E-50
Source logic switching confirmation alarm

Cause:

  • The input terminal is switched to source logic mode.




Remedy:

  • Check whether cables are connected correctly, and then specify a proper logic.

  • Check whether cables are connected correctly, and then reset the inverter or turn it off temporarily and turn it back on. Logics will be switched.


C, P, L, H
Alarms displayed during operation

Cause:

  • C: Overcurrent alarm

  • P: Overvoltage alarm

  • L: Overload alarm

  • H: Overheat alarm




Remedy:

  • If two or more problems arise simultaneously, they blink in order C, P, L, H.


How to Clear & Reset Toshiba NC1 Drive Faults

  1. Keypad Reset: Press the STOP key twice on the front integrated operation panel while the trip code is displayed. The first press acknowledges the fault status, and the second clears the trip alarm.
  2. Control Terminal Reset (RES): If a programmable digital input terminal is assigned to the reset function (RES), momentarily connect it to terminal CC (common) for at least 0.1 seconds, then disconnect.
  3. Serial Communication Reset: Issue a fault reset command by sending the reset bit via the RS-232C or RS-485 communication interface converter (RS2001Z / RS4001Z) using the TOSHIBA communication protocol.
  4. Power Cycle: Disconnect the incoming AC line power supply. Wait until the LED display completely turns off (allow at least 10 minutes for full internal DC capacitor discharge), then reconnect mains power.
  5. Root Cause Clearance: Before resetting high-current trips such as OC1/OC2/OC3 (Overcurrent) or OLL (Inverter Overload), always check motor leads and load mechanics to prevent internal power component damage.
⚠️ High-Voltage Electrical Safety Warning: Wait at least 10 minutes after turning off the AC input supply and verify with a calibrated DC voltmeter that the intermediate circuit voltage across terminals [PA/+] and [PC/-] is strictly below 50VDC before inspecting motor terminals U, V, W or working on input wiring of the Toshiba NC1 inverter.