Toshiba NC3 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba NC3 (TOSVERT VF-nC3) compact micro drive series. Search or filter through the complete fault code directory below.

Compact Micro Drive Power: 0.1 to 4.0 kW (0.12 to 5 HP) Built-in RS-485 Modbus RTU
Power Range 0.1 – 4.0 kW (0.12 – 5 HP)
Supply Voltage 1-Ph 120V/240V & 3-Ph 240V/400V
Control Modes V/f Control & Sensorless Vector
Operator Interface Turn-and-Push Dial & 4-Digit Display

Complete Toshiba NC3 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, OL1, or Overcurrent).

Fault Code and MeaningCause and Remedy
E (0011)
Emergency stop

Cause:

During automatic operation or remote operation, an emergency stop command is entered from the operation panel or an external (terminal or communication).



Remedy:

  • Reset the inverter.

  • If the emergency stop signal is input, reset after releasing this signal.


E-13 (0045)
Over speed fault

Cause:

The input voltage fluctuates abnormally.
Over speed fault due to the overvoltage limit operation.



Remedy:

  • Check the input voltage.

  • Install an optional braking module.


E-18 (0032)
Break in analog signal cable

Cause:

The input signal from VI is equal to or less than the F633 setting.



Remedy:

  • Check the VI signal cable for breaks.

  • Check the input signal value or setting of F633.


E-19 (0033)
CPU communications error

Cause:

A communications error occurs between control CPUs.



Remedy:

  • Contact your Toshiba distributor.


E-20 (0034)
Excessive torque boosted

Cause:

The automatic torque boost parameter F402 setting is too high.
The motor has too small impedance.



Remedy:

  • Set a lower automatic torque boost parameter F402 setting.

  • Make an auto-tuning.


E-21 (0035)
CPU fault 2

Cause:

The control CPU is defective.



Remedy:

  • Contact your Toshiba distributor.


E-26 (003A)
CPU fault 3

Cause:

Internal CPU error.



Remedy:

  • Contact your Toshiba distributor.


EEP1 (0012)
EEPROM fault 1

Cause:

The EEPROM is writing error.



Remedy:

  • Turn off the inverter, then turn it on again.

  • If it does not recover from the error, contact your Toshiba distributor.


EEP2 (0013)
EEPROM fault 2

Cause:

TYP operation was aborted by power supply off etc.
The EEPROM is reading error.



Remedy:

  • Turn off the inverter, then turn it again, and then try TYP operation again.

  • If it does not recover from the error, contact your Toshiba distributor.


EEP3 (0014)
EEPROM fault 3

Cause:

The EEPROM is defective.



Remedy:

  • Contact your Toshiba distributor.


EF2 (0022)
Ground fault trip

Cause:

A ground fault occurs in the output cable or the motor.



Remedy:

  • Check the cable and the motor for ground faults.


EPH1 (0008)
Input phase failure

Cause:

A phase failure occurred in the input line of the main circuit.
The capacitor in the main circuit lacks capacitance.



Remedy:

  • Check the main circuit input line for phase failure.

  • Set input phase failure detection selection F608=0.

  • Check the capacitor in the main circuit for exhaustion.


EPH0 (0009)
Output phase failure

Cause:

A phase failure occurred in the output line of the main circuit.
The motor has too big impedance.



Remedy:

  • Check the main circuit output line, motor, etc. for phase failure.

  • Set output phase failure detection selection F605=0.


ERR2 (0015)
Main unit RAM fault

Cause:

The control RAM is defective.



Remedy:

  • Contact your Toshiba distributor.


ERR3 (0016)
Main unit ROM fault

Cause:

The control ROM is defective.



Remedy:

  • Contact your Toshiba distributor.


ERR4 (0017)
CPU fault 1

Cause:

The control CPU is defective.



Remedy:

  • Contact your Toshiba distributor.


ERR5 (0018)
Remote control error

Cause:

The communication with external devices was broken off.



Remedy:

  • Check the remote control device, cables, etc.


ETN (0028/0054/0055/0056)
Auto-tuning error

Cause:

The motor parameters (uL, uLu, F405, F415, F417) are not set correctly.
The motor capacity is 2 classes or less than the inverter.
Output cable is too thin.
Motor is not connected.
Motor is rotating.



Remedy:

  • Set the parameters correctly as per motor nameplate and retry auto-tuning.

  • Set parameter F416 to smaller 70% of present value and retry.

  • If output cable is thin or special load, set F400=1 when trip occurs.

  • Connect the motor.

  • Check secondary magnetic contactor.

  • Wait for motor to stop rotating before auto-tuning.


ETYP (0029)
Inverter type error

Cause:

It may be a breakdown failure.



Remedy:

  • Contact your Toshiba distributor.


OC1 (0001)
Overcurrent during acceleration

Cause:

The acceleration time ACC is too short.
The V/F setting is improper.
A restart signal is input to the rotating motor after a momentary stop.
Special motor (small impedance) is used.
Cable length to motor is long.



Remedy:

  • Increase the acceleration time ACC.

  • Check the V/F parameter.

  • Use F301 (auto-restart) and F302 (ride-through control).

  • In case of Pt=0, 1, decrease vb.

  • In case of Pt=2, 3, 4, set F415 (Motor rated current) and make an auto-tuning.

  • Install AC reactors on the output side.


OC2 (0002)
Overcurrent during deceleration

Cause:

The deceleration time dEC is too short.
The cable length to a motor is long.



Remedy:

  • Increase the deceleration time dEC.

  • Install AC reactors on the output side.


OC3 (0003)
Overcurrent during constant speed operation

Cause:

The load fluctuates abruptly.
The load is in an abnormal condition.
The cable length to a motor is long.



Remedy:

  • Reduce the load fluctuation.

  • Check the load (operated machine).

  • Install AC reactors on the output side.


OCA (0005)
Arm overcurrent at start-up

Cause:

A main circuit element is defective.



Remedy:

  • Contact your Toshiba distributor.


OCL (0004)
Overcurrent (load side at start-up)

Cause:

The insulation of the output main circuit or motor is defective.
The motor has too small impedance.



Remedy:

  • Check the secondary wiring and insulation state.

  • Set F613=2, 3.


OH (0010)
Overheat

Cause:

The cooling fan is life or fault.
The ambient temperature is high or low outside a specified ambient temperature.



Remedy:

  • The cooling fan requires replacement if it does not rotate. Contact distributor.

  • Operate at a specified ambient temperature.


OL1 (000D)
Inverter overload

Cause:

Acceleration time ACC too short.
DC braking amount too large.
V/F setting improper.
Restart signal input to rotating motor.
Load is too large.



Remedy:

  • Increase acceleration time ACC.

  • Reduce DC braking amount F251 and time F252.

  • Check V/F parameter setting.

  • Use F301 (auto-restart) and F302 (ride-through).

  • Use an inverter with a larger rating.

  • Reduce F300 (PWM carrier frequency) to 4kHz or less.


OL2 (000E)
Motor overload

Cause:

V/F setting improper.
Motor is locked up.
Low-speed operation performed continuously.
Excessive load applied.



Remedy:

  • Check V/F parameter setting.

  • Check the load (operated machine).

  • Adjust OLM to the overload the motor can withstand in low speed range.


OL3 (003E)
Main module overload

Cause:

Carrier frequency is high and load current increased at low speeds (mainly 15Hz or less).



Remedy:

  • Raise the operation frequency.

  • Reduce the load.

  • Reduce F300 (PWM carrier frequency).

  • Set F316=1 (Carrier frequency with automatic reduction).


OP1 (000A)
Overvoltage during acceleration

Cause:

Input voltage fluctuates abnormally (Power supply >200kVA, Capacitor open/close, Thyristor connected).
Restart signal input to rotating motor.



Remedy:

  • Insert a suitable input reactor.

  • Use F301 (auto-restart) and F302 (ride-through control).


OP2 (000B)
Overvoltage during deceleration

Cause:

Deceleration time dEC is too short (Regenerative energy too large).
Overvoltage limit operation F305 is disabled.
Input voltage fluctuates abnormally.



Remedy:

  • Increase deceleration time dEC.

  • Set overvoltage limit operation F305 to 0, 2, 3.

  • Insert a suitable input reactor.


OP3 (000C)
Overvoltage during constant-speed

Cause:

Input voltage fluctuates abnormally.
Motor is in regenerative state (load pushes motor faster than frequency).



Remedy:

  • Insert a suitable input reactor.

  • Install an optional brake module.


OT (0020)
Over-torque trip

Cause:

Over-torque reaches detection level during operation.



Remedy:

  • Enable F615 (over-torque trip selection).

  • Check system error.


UC (001D)
Low-current operation Trip

Cause:

Output current decreased to low-current detection level during operation.



Remedy:

  • Enable F610 (low-current detection).

  • Check suitable detection level (F609, F611, F612).

  • Contact distributor if setting is correct.


UP1 (001E)
Under voltage trip (main circuit)

Cause:

The input voltage (in the main circuit) is too low.



Remedy:

  • Check the input voltage.

  • Enable F627 (undervoltage trip selection).

  • Set F627=0 or 2, F302 and F301 for momentary power failure measures.


A-05
Output frequency upper limit

Cause:

Attempt made to operate at frequency higher than 10 times the base frequency.



Remedy:

  • Operate at a frequency within 10 times the base frequency.


A-17
Operation panel key alarm

Cause:

RUN or STOP key held down for >20 seconds.
Key is faulty.



Remedy:

  • Check the operation panel.


ATN
Auto-tuning

Cause:

Auto-tuning in process.



Remedy:

  • Normal if message disappears after a few seconds.


CLR
Clear command acceptable

Cause:

Displayed when pressing STOP key while an error code is displayed.



Remedy:

  • Press the STOP key again to clear the trip.


DB
DC braking

Cause:

DC braking in process.



Remedy:

  • Message goes off in several tens of seconds if no problem.


E1 / E2 / E3
Flowing out of excess number of digits

Cause:

Number of digits (e.g. frequencies) is more than 4.



Remedy:

  • Lower the frequency free unit magnification F702.


E-49
External power supply logic switching check

Cause:

Input terminal switched to sink logic of external power (+24V).



Remedy:

  • Remove connection of control terminals, reset or power cycle to switch logic.


E-50
Source logic switching check

Cause:

Input terminal switched to source logic.



Remedy:

  • Informational alarm.


E-51
Sink logic switching check

Cause:

Input terminal switched to sink logic.



Remedy:

  • Informational alarm.


EASY / STD
Switching display of Easy/Standard mode

Cause:

EASY key was pushed.



Remedy:

  • Indicates mode change.


EOFF
Emergency stop command acceptable

Cause:

Operation panel used to stop operation in auto/remote control mode.



Remedy:

  • Press STOP for emergency stop. Press any other key to cancel.


ERR1
Frequency point setting error

Cause:

Frequency setting signals at points 1 and 2 are too close.



Remedy:

  • Set points 1 and 2 apart from each other.


HEAD / END
Display of first/last data items

Cause:

First or last data item in group reached.



Remedy:

  • Press MODE key to exit data group.


HI / LO
Setting error alarm

Cause:

Error found in a setting when data is reading or writing.



Remedy:

  • Check whether the setting is made correctly.


INIT
Parameters in initialization

Cause:

Parameters are being initialized to default.



Remedy:

  • Normal if message disappears after a while.


LSTP
Auto-stop (continuous low limit)

Cause:

Automatic stop function (F256) activated.



Remedy:

  • Function cancelled when freq reference reaches LL+0.2Hz or command OFF.


MOFF
Undervoltage in main circuit

Cause:

Supply voltage between R, S, T is under voltage.
Shorting-bar between P0 and PA/+ removed (120V class).



Remedy:

  • Measure main circuit supply voltage.

  • Connect shorting-bar between P0 and PA/+.


NERR
No trip of past trip

Cause:

No new record of past trip.



Remedy:

  • Normal operation.


OFF
ST terminal OFF

Cause:

ST-CC circuit is opened.



Remedy:

  • Close the ST-CC circuit.


PASS / FAIL
Password verification

Cause:

Result of password input for F739.



Remedy:

  • PASS = correct, FAIL = incorrect.


RTRY
Retry in process

Cause:

Inverter in process of retry after momentary stop.



Remedy:

  • Inverter restarts automatically. Be careful.


SET
Input requirement of region setting

Cause:

Power supplied to inverter for the first time.



Remedy:

  • Set region setting using setting dial (set SET to 0, TYP to 13).


STOP
Deceleration stop during power failure

Cause:

Decel stop during power failure (F302) activated.



Remedy:

  • To restart, reset power or input operation signal again.


C
Overcurrent pre-alarm

Cause:

Current flows at or higher than stall prevention level.



Remedy:

  • Same as OC (overcurrent).


H
Overheat pre-alarm

Cause:

Overheat protection pre-alarm level reached.



Remedy:

  • Same as OH (overheat).


L
Overload pre-alarm

Cause:

Cumulative overload reaches 50% or more of trip value.



Remedy:

  • Same as OL (overload).


P
Overvoltage pre-alarm

Cause:

Voltage generated at or higher than stall prevention level.



Remedy:

  • Same as OP (overvoltage).


T
Communication pre-alarm

Cause:

Communication broken off at or higher than F803 setting.



Remedy:

  • Same as ERR5 (communication fault).


How to Clear & Reset Toshiba NC3 Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the front panel twice after resolving the fault cause (the first press acknowledges and clears the trip display; the second press returns the inverter to normal output frequency display).
  2. Control Terminal Reset (Digital Input): Assign the Fault Reset function (Function 10) to a programmable digital input terminal (such as F, R, S1, or S2) and briefly close the circuit to control common CC.
  3. Setting Dial Navigation: Rotate the central turn-and-push setting dial to inspect the trip history parameter (ALH / Alarm History), confirm the operating conditions at the moment of the trip, and press the dial to clear if parameter-prompted.
  4. RS-485 Communication: If operating via the bottom RJ45 serial port, send a reset control command bit over Modbus RTU or Toshiba protocol to clear the inverter trip state remotely.
  5. Power Cycle: Disconnect the incoming AC power supply. Wait at least 15 minutes until the 4-digit LED display and the internal CHARGE lamp turn off completely to allow the DC bus capacitors to discharge safely, then restore mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] before inspecting motor leads, opening terminal covers, or touching output terminals U/T1, V/T2, and W/T3 on the Toshiba NC3 drive.