Toshiba Q9+ Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the Toshiba Q9+ (Q9 Plus) HVAC and pump adjustable speed drive series. Search or filter through the complete fault code directory below.

HVAC & Pump Dedicated Drive Power: 0.75 to 300 kW (1 to 400 HP) Embedded BACnet MS/TP & Modbus RTU
Power Range 0.75 – 300 kW (1 – 400 HP)
Supply Voltage 3-Phase 200–240V / 380–480V AC
Control Modes V/f, Vector & VLP Pump Control
Operator Interface 8-Line Backlit LCD Keypad & HOA

Complete Toshiba Q9+ Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type OC1, OP1, OL1, or Overcurrent).

Fault Code and MeaningCause and Remedy
Atn
Autotune Active

Cause:
  • Autotune function is active.



Remedy:
  • Information only; wait for completion.

nErr
No Error

Cause:
  • No active errors.



Remedy:
  • None required.

LOFr
Virtual Linear Pump Low Frequency

Cause:
  • Virtual Linear Pump function is operating at the Low-Frequency Limit setting.



Remedy:
  • Information only.

Pump
Virtual Linear Pump On

Cause:
  • Virtual Linear Pump function is enabled and active.



Remedy:
  • Information only.

4-20 mA
4-20 Signal Loss

Cause:

  • Misconnection, poor connection, or broken wire.

  • Improper programming at F201 and associated parameters.




Remedy:

  • Check wiring and connections.

  • Verify parameter F201 settings.


*OL1
ASD Overload

Cause:

  • Carrier frequency is too high.

  • Excessive load.

  • Acceleration time is too short.

  • DC damping rate is too high.

  • Motor is starting into a spinning load after a momentary power failure.

  • ASD is improperly matched to the application.




Remedy:

  • Reduce carrier frequency or load.

  • Increase acceleration time.

  • Check DC damping settings.


CM1
Comm Error Interruption

Cause:

  • Improperly programmed ASD.

  • Improper communications settings.




Remedy:

  • Verify ASD programming and communication settings.


CM2
Comm Error 2

Cause:
  • Improperly connected cables.



Remedy:
  • Check communication cables and connections.

DAMP
Damper Closed

Cause:
  • Improper configuration/programming for Damper Control at discrete input terminals.



Remedy:
  • Check Damper Control configuration.

*OP
DC Bus Over-Volts

Cause:

  • ASD is attempting to start into a spinning motor after a momentary power loss.

  • Incoming commercial power voltage level is above the specified range.

  • Deceleration time is too short.

  • Voltage spikes at the 3-phase input.

  • Over-Voltage Stall feature is turned off.

  • System is regenerating / Load fluctuations.




Remedy:

  • Install inductive filter if spikes are present.

  • Increase deceleration time.

  • Enable Over-Voltage Stall feature.


*POFF
DC Under-Volts

Cause:

  • Defective control board.

  • Excessive load on power supply.

  • Low input voltage.




Remedy:

  • Check input voltage.

  • Check for excessive load.


E
Emergency Off

Cause:

  • Stop-Reset was pressed twice at the EOI.

  • E-OFF command was received remotely.




Remedy:

  • Reset the system.


HLd
Heavy Load

Cause:

  • Acceleration time is too short.

  • ASD is improperly matched to the application.

  • Excessive load.




Remedy:

  • Increase acceleration time.

  • Verify drive sizing for the load.


LLd
Light Load

Cause:
  • ASD is improperly matched to the application.



Remedy:
  • Verify drive sizing.

LLt
Lower Limit Time

Cause:
  • Lower-Limit Time reached.



Remedy:
  • Parameter F256 adjustment is required.

MOFF
Main Under-Volts

Cause:

  • 3-phase input voltage low.

  • Defective control board.

  • Excessive load on power supply.




Remedy:

  • Under-Voltage/Ridethrough settings require adjustment.


OLM
Motor Overload

Cause:

  • V/f setting requires adjustment.

  • Motor is locked.

  • Continuous operation at low speed.

  • Motor is improperly matched to the load.




Remedy:

  • Adjust V/f settings.

  • Check for mechanical binding/locking.


OC
Over-Current

Cause:

  • Phase-to-phase short (U/T1, V/T2, or W/T3).

  • Defective IGBT.

  • ASD output to the motor is connected incorrectly.

  • ASD is attempting to start into a spinning motor.

  • Motor/machine is jammed.

  • Mechanical brake engaged while ASD is running.

  • Acceleration/deceleration time is too short.

  • Voltage Boost setting is too high.

  • V/f setting adjustment is required.




Remedy:

  • Check motor and cabling for shorts.

  • Adjust Acceleration/Deceleration times.

  • Check mechanical brakes and load.


*OH
Over-Heating

Cause:

  • ASD is operating at an elevated temperature.

  • ASD is too close to heat-generating equipment.

  • Cooling fan vent is obstructed.

  • Cooling fan is inoperative.

  • Internal thermistor is disconnected.




Remedy:

  • Check cooling fans and vents.

  • Ensure proper ambient temperature and clearance.


Ot
Over-Torque

Cause:

  • ASD is improperly matched to the application.

  • Parameter F616 or F617 setting is too low.

  • Obstructed load.




Remedy:

  • Adjust parameters F616 or F617.

  • Check for load obstructions.


LtA
Part Replace

Cause:
  • Part Replacement Alarm at F634 timed out.



Remedy:
  • Perform required maintenance and reset timer.

OJ
Run-Time Counter

Cause:
  • User-Set Run-Time Counter Exceeded.



Remedy:
  • Type Reset is required; select Clear run timer.

OLSt
Soft Stall

Cause:
  • Overload Soft Stall Active.



Remedy:
  • Soft Stall selection adjustment is required (F017).

PtC
Thermal Err

Cause:
  • Option Thermal Sensor Threshold Exceeded.



Remedy:
  • User-set thermal threshold setting of F646 is exceeded.

UC
Under-Current

Cause:
  • Output Current of the ASD is Below the Level Defined at F611.



Remedy:

  • Disable detection at F610.

  • Parameter F611 adjustment is required.


E-19
Abnormal CPU2

Cause:
  • Abnormal CPU2 Communication.



Remedy:
  • Service call is required.

E-18
Analog Input Loss

Cause:

  • V/I input terminal configured for operation but the voltage/current input is either missing or low.

  • Over-current at P24.




Remedy:
  • Check analog input signals and P24 connection.

E-10
Analog Input OV

Cause:
  • Analog Input Terminal Over-Voltage.



Remedy:
  • Mis-wire at the ASD input terminals; check wiring.

OL1
ASD Overload (Trip)

Cause:

  • Acceleration time is too short.

  • DC Injection current is too high.

  • V/f setting needs to be adjusted.

  • Motor is running during restart.

  • ASD/motor is improperly matched to the application.




Remedy:

  • Adjust acceleration time or DC Injection settings.

  • Adjust V/f settings.


Err2
ASD RAM Fault

Cause:
  • ASD RAM Fault.



Remedy:
  • Service call is required.

Err3
ASD ROM Fault

Cause:
  • ASD ROM Fault.



Remedy:
  • Service call is required.

EtyP
ASD Type Error

Cause:

  • Firmware information (typeform) loaded into the Application Board is inconsistent with the Motor Control Board.

  • Application Board or Motor Control Board is defective.




Remedy:
  • Service call is required.

E-26
CPU Fault

Cause:
  • CPU Fault.



Remedy:
  • Service call is required.

EEP2, EEP3
Ctrl Read Err

Cause:
  • Initial Read Error (Parameter Initialization).



Remedy:
  • Service call is required.

Err7
Current Err

Cause:

  • Current Detection Hardware Error.

  • Improper low-current detection level setting.

  • Motor (phase) is disconnected.




Remedy:

  • Check motor connections.

  • Check detection level settings.


E-22
Discrete In Volts

Cause:
  • Discrete input terminal configured for operation and the input activation voltage level is out of specification.



Remedy:
  • Check input voltage levels.

EEP1
EEPROM Write Err

Cause:
  • EEPROM Fault (Writing Error).



Remedy:
  • Service call is required.

Etn
Autotuning Err

Cause:

  • Autotune readings are inconsistent with the configuration.

  • Non-3-phase motor is being used.

  • Improper settings at F400 or F410 – F413.

  • Using a motor with significantly smaller rating than ASD.

  • ASD output cabling is too small/long or has EMF interference.

  • Motor is running during Autotune.




Remedy:

  • Verify motor type and ratings.

  • Check parameters F400-F413.


Etn2
Leak Inductance Err

Cause:
  • Autotuning Error — Leak Inductance Error.



Remedy:
  • Improper setting at F412; adjust setting.

Etn3
Motor Rating Err

Cause:
  • Autotuning Error — Motor Rating Error.



Remedy:
  • Improper setting at F405, F406, or F407; adjust settings.

Etn1
Torque Boost Err

Cause:
  • Autotuning Error — Torque Boost Error.



Remedy:
  • Improper setting at F410; adjust setting.

E
Emergency Off (Trip)

Cause:

  • Stop-Reset was pressed twice at the EOI.

  • E-Off command was received remotely.




Remedy:
  • Select stopped method at F603.

E-12
Encoder Loss

Cause:
  • Encoder signal is not received.



Remedy:
  • Check encoder connections.

Err6
Gate Array Fault

Cause:
  • Defective gate array or gate array malfunction.



Remedy:
  • Service call is required.

EF1, EF2
Ground Fault

Cause:

  • Mis-wired ground.

  • Loose ground connection.




Remedy:
  • Check ground wiring and connections.

EPH1
Input Phase Failure

Cause:

  • Mis-wired input phase.

  • Loose input phase connection.




Remedy:
  • Check input phase wiring.

UC
Low-Current (Trip)

Cause:
  • Improper low-current detection level setting.



Remedy:
  • Adjust detection level setting.

Err8
Net Card Err

Cause:

  • Optional device malfunction.

  • Improper system settings (at ASD or optional device).

  • Loose or improper connection.




Remedy:
  • Check network option card settings and connections.

OH2
Option Over-Heat

Cause:
  • Over temperature condition detected by option board.



Remedy:
  • Check PTC1 or PTC2 (see F637 and F638).

EPH0
Output Phase Failure

Cause:

  • Mis-wired output phase.

  • Loose output phase connection.




Remedy:
  • Check output wiring.

OCL
Output Short

Cause:

  • ASD is starting into a rotating motor.

  • Phase-to-phase short (U/T1, V/T2, or W/T3).

  • Acceleration time is too short.

  • Motor/machine is jammed or brake engaged.




Remedy:

  • Short Circuit Detection adjustment is required (F613).

  • Check motor and mechanical systems.


OC1, OC1P
Over-Current Acc

Cause:

  • V/f setting needs to be adjusted.

  • Restart from a momentary power outage.

  • Phase-to-phase short.

  • Acceleration time is too short.




Remedy:

  • Adjust V/f or acceleration settings.

  • Check for shorts.


OC2, OC2P
Over-Current Dec

Cause:

  • Deceleration time is too short.

  • Motor/machine is jammed or brake engaged.




Remedy:

  • Increase deceleration time.

  • Check mechanical system.


OC3, OC3P
Over-Current Run

Cause:

  • ASD/Motor is improperly matched to the application.

  • Load fluctuations.

  • ASD is operating at an elevated temperature.




Remedy:

  • Check load and drive sizing.

  • Check environmental conditions.


E-13
Over-Speed

Cause:

  • Motor speed greater than commanded speed.

  • Improper encoder connection or setup.

  • Defective encoder.




Remedy:
  • Check encoder and speed control settings.

Ot
Over-Torque (Trip)

Cause:
  • Output torque requirement in excess of F616 or F617 settings for longer than F618 setting.



Remedy:
  • Adjust torque limit settings.

OP1
Over-Voltage Acc

Cause:
  • Motor is running during restart.



Remedy:
  • Stop motor before restart or use catch-spin.

OP2
Over-Voltage Dec

Cause:

  • Deceleration time is too short.

  • Stall prevention is disabled.

  • Input reactance is required.




Remedy:

  • Increase deceleration time.

  • Enable stall prevention.


OP3
Over-Voltage Run

Cause:

  • Load fluctuations.

  • 3-phase input voltage out of specification.




Remedy:
  • Check input voltage stability and load.

E-21
Stack Err

Cause:
  • Stack Overflow Error.



Remedy:
  • Service call is required.

SOut
Step-Out (PM)

Cause:
  • Step-Out (For PM Motors Only).



Remedy:
  • Service call is required.

OCA1
U-Phase OC

Cause:
  • U-Phase Over-Current (Low impedance at U/T1 phase).



Remedy:
  • Check motor winding/cabling for short.

OCA2
V-Phase OC

Cause:
  • V-Phase Over-Current (Low impedance at V/T2 phase).



Remedy:
  • Check motor winding/cabling for short.

OCA3
W-Phase OC

Cause:
  • W-Phase Over-Current (Low impedance at W/T3 phase).



Remedy:
  • Check motor winding/cabling for short.

How to Clear & Reset Toshiba Q9+ Drive Faults

  1. Keypad Reset: Press the red STOP / RESET key on the Electronic Operator Interface (EOI) twice after clearing the trip source (the first press acknowledges the fault display and the second resets the drive to standby mode).
  2. Control Terminal Reset (RES): Momentarily close the circuit between terminal RES and terminal CC (Control Common) on the control terminal strip.
  3. Building Automation System (BAS) Reset: Write a logic high (`1`) to the fault reset command bit via embedded communication protocols (BACnet MS/TP, Metasys N2, APOGEE FLN, or Modbus RTU).
  4. Hand-Off-Auto (HOA) Bypass Units: For units equipped with an integrated bypass enclosure, ensure the HOA selector switch is set to OFF before clearing faults or switching between ASD and Bypass contactor lines.
  5. Power Cycle: Disconnect line input power via the external disconnect or integral circuit breaker. Wait at least 15 minutes for the CHARGE lamp and LCD screen to go dark (allowing intermediate DC bus capacitors to discharge safely) before restoring power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [PA/+] and [PC/-] before opening covers, inspecting motor circuits, or servicing power terminals U/T1, V/T2, and W/T3 on the Toshiba Q9+ drive.