WEG ADV200 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG ADV200 field-oriented vector system drive series. Search or filter through the complete fault code directory below.
Power Range
0.75 kW – 1.65 MW (1 – 2,200 HP)
Supply Voltage
380–480V / 500–690V AC (or DC Bus)
Control Modes
FOC (Open/Closed Loop), V/f & SynRM/PM
Operator Interface
Integrated Alphanumeric / Graphic LCD (KB-ADV)
Complete WEG ADV200 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type Overcurrent, Ground Fault, or DC Link OV).
| Alarm Code and Display Message | Cause and Solution / Remedy |
|---|---|
| 0 No alarm | Cause: No alarm present. Remedy: No action required. |
| 1 Overvoltage | Cause: DC link overvoltage alarm due to energy recovered from the motor. The voltage arriving at the drive power section is too high compared to the maximum threshold relating to the PAR 560 Mains voltage parameter setting. Remedy:
|
| 2 Undervoltage | Cause: DC link undervoltage alarm. The voltage arriving at the drive power section is too low compared to the minimum threshold relating to the 560 Mains voltage parameter setting. This can be caused by:
Remedy: Check the related connections of the drive power supply and verify its correct voltage range. |
| 3 Ground fault | Cause: Ground short circuit alarm. Remedy:
|
| 4 Overcurrent | Cause: Instantaneous overcurrent protection intervention alarm. This may be due to the incorrect setting of current regulator parameters, a short circuit between phases, or a ground fault on the drive output. Remedy:
|
| 5 Desaturation | Cause: Instantaneous overcurrent in the IGBT bridge alarm. Remedy: Switch the drive off and then switch it on again. If the alarm persists, contact the technical service centre. |
| 6 MultiUndervolt | Cause: The number of attempted automatic restarts after the Undervoltage alarm has exceeded the set PAR 4650 UVRep attempts value in the PAR 4652 UVRep delay time. Remedy: Too many Undervoltage alarms. Adopt the proposed solutions for the Undervoltage alarm. |
| 7 MultiOvercurr | Cause: Two attempted automatic restarts after the Overcurrent alarm within 30 seconds. If more than 30 seconds pass after the Overcurrent alarm was generated, the attempt counter is reset. Remedy: Too many Overcurrent alarms. Adopt the proposed solutions for the Overcurrent alarm. |
| 8 MultiDesat | Cause: Two attempted automatic restarts after the Desaturation alarm within 30 seconds. If more than 30 seconds pass after the Desaturation alarm was generated, the attempt counter is reset. Remedy: Too many Desaturation alarms. Adopt the proposed solutions for the Desaturation alarm. |
| 9 Heatsink OT | Cause: Heatsink temperature too high alarm. Remedy:
|
| 10 HeatsinkS OTUT | Cause: IGBT modules temperature too high or too low alarm. Remedy:
|
| 11 Intakeair OT | Cause: Intake drive air temperature too high alarm. Remedy:
|
| 12 Motor OT | Cause: Motor overtemperature alarm. Possible causes:
Remedy:
|
| 13 Drive overload | Cause: Drive overload alarm. The overload threshold of the accumulator of the I²t drive thermal image has been exceeded. Remedy: Check that the size of the drive is suitable for the application. |
| 14 Motor overload | Cause: Motor overload alarm. The current absorbed during operation is greater than that specified on the motor data plate. The overload threshold of the accumulator of the I²t motor thermal image has been exceeded. Remedy:
|
| 15 Bres overload | Cause: Braking resistor overload alarm. The current absorbed by the resistor is greater than the rated current. The overload threshold of the accumulator of the I²t braking resistor thermal image has been exceeded. Remedy: Increase the Watt value of the braking resistor. |
| 16 Phase loss | Cause: Power phase loss alarm. Remedy: Check the mains voltage and whether any protections upstream of the drive have been tripped. |
| 17 Opt Bus fault | Cause: Error in the configuration stage or communication error.
Remedy: For configuration errors, check the configuration of the bus communication, type of bus, baudrate, address, and parameter settings. For communication errors, verify wiring, resistance of terminations, interference immunity, and timeout settings. For further details, please refer to the user guide for the specific bus. |
| 18 Opt 1 IO fault | Cause: Error in the communication between Regulation and I/O expansion card in slot 1. Remedy: Check that it has been inserted correctly, see chapter 10.5. |
| 19 Opt 2 IO fault | Cause: Error in the communication between Regulation and I/O expansion card in slot 2 or 3. Remedy: Check that it has been inserted correctly, see chapter 10.5. |
| 20 Opt Enc fault | Cause: Error in the communication between Regulation and Encoder feedback card. Remedy: Check that it has been inserted correctly, see chapter 10.5. |
| 21 External fault | Cause: External alarm present. A digital input has been programmed as an external alarm, but the +24V voltage is not available on the terminal. Remedy: Check that the terminal screws are tight. |
| 22 Speed fbk loss | Cause: Speed feedback loss alarm. The encoder is not connected, not connected properly, or not powered. This can be verified by selecting the PAR 260 Motor speed parameter in the MONITOR menu. This alarm is generated in case of an encoder fault. Each type of encoder generates a "Loss of feedback" alarm differently. See parameter 2172 SpdFbkLoss code for more information about the cause of the alarm and chapter D.1. Remedy:
|
| 23 Overspeed | Cause: Motor overspeed alarm. The motor speed exceeds the limits set in the PAR 4540 Overspeed threshold parameter. Remedy:
|
| 24 Speed ref loss | Cause: Speed reference loss alarm. Occurs if the difference between the speed regulator reference and the actual motor speed is more than 100 rpm. This condition occurs because the drive is in the current limit condition. Note: This is only available in the Flux Vect OL and Flux Vect OC mode. Remedy:
|
| 25 Emg stop alarm | Cause: Emergency stop alarm. The Stop key on the keypad was pressed with the PAR 1008 Stop key mode parameter set to EmgStop&Alarm. Active in remote control mode (PAR 1012=1) both by using "Terminals" command or "Digital" commands and, in local control mode (PAR 1012=0) by using "Terminals" command. Remedy: Eliminate the reason for which the Stop key on the keypad was pressed and reset the drive. |
| 26 Power down | Cause: The drive was enabled with no supply voltage at the power section. Remedy: Check the drive power supply. |
| 27 ExtIO fault | Cause: Communication fault with the external module. Remedy: See paragraph "8.1.2 ExtIO fault Alarm", page 129. |
| 28 FastLink fault | Cause: FastLink communication fault. Remedy: See paragraph "8.1.3 FastLink Alarm", page 130. |
| 29 Brake fault | Cause: Incorrect setting of brake control function parameters. Remedy: See menu 22.13 - FUNCTIONS/BRAKE CONTROL. |
| 30 Motor pre OT | Cause: Motor overtemperature prealarm. % value of threshold compared to PAR 4532 MotorOT thr. Remedy: Verify if the value is set too low for the current duty cycle. Ensure the duty cycle matches drive thermal specifications. |
| 31 Mot phase loss | Cause: Output phase loss. Remedy: Check the Drive/motor output connections. |
| 32 Condensation | Cause: High condensation level inside the drive. Operating conditions (combination of ambient temperature, humidity, and cooling liquid temperature) are not safe. Remedy: Safe conditions are obtained when the work point is under the respective curve indicated in the graph of chapter 22.18 - FUNCTIONS/LC CONTROL. Otherwise, you must take adequate precautions to lower the ambient temperature and/or the relative humidity or to raise the cooling liquid temperature. |
| 33 ... 40 Plc1 fault ... Plc8 fault | Cause: An enabled application developed in the IEC 61131-3 environment has found the conditions for generating this specific alarm to be true. The meaning of the alarm depends on the type of application. The XXXXH-X sub-code indicates the reason for the error. Remedy: Refer to the documentation concerning the enabled application. Make a note of the XXXXH-X code to discuss it with the service centre. |
| 41 Watchdog | Cause: May occur during functioning when the watchdog protection of the microcontroller is activated. The alarm is inserted in the alarm list and alarm log. Following this alarm:
The XXXXH-X sub-code indicates the reason for the error. Remedy: If the alarm was a consequence of a variation to the drive configuration (parameter setting, installation of an option, downloading of a PLC application), remove it. Switch the drive off and then switch it on again. Take note of the XXXXH-X code for examination with the service centre. |
| 42 Trap error | Cause: This condition can occur during operation when the trap micro protection is enabled. The alarm is included in the list of alarms and alarm log. Following this alarm:
The XXXXH-X code (SubHandler-Class) indicates the reason for the error. Remedy: If the alarm was a consequence of a variation to the drive configuration (parameter setting, installation of an option, downloading of a PLC application), remove it. Switch the drive off and then switch it on again. Take note of the XXXXH-X code for examination with the service centre. |
| 43 System error | Cause: This condition can occur during operation when the operating system protection is enabled. The alarm is included in the list of alarms and alarm log. Following this alarm:
The XXXXH-X code (Error-Pid) indicates the reason for the error. Remedy: If the alarm was a consequence of a variation to the drive configuration (parameter setting, installation of an option, downloading of a PLC application), remove it. Switch the drive off and then switch it on again. Take note of the XXXXH-X code for examination with the service centre. |
| 44 User error | Cause: This condition can occur during operation when the software protection is enabled. The alarm is included in the list of alarms and alarm log. Following this alarm:
The XXXXH-X (Error-Pid) code indicates the reason for the error. Remedy: If the alarm was a consequence of a variation to the drive configuration (parameter setting, installation of an option, downloading of a PLC application), remove it. Switch the drive off and then switch it on again. Make a note of the XXXXH-X code to discuss it with the service centre. |
| 45 Param error | Cause: Occurs if an error happens during the enabling of the parameter database saved in the Flash memory. The alarm is included in the list of alarms and alarm log. The XXXXH-X code indicates the IPA of the parameter that has been set outside the range allowed when the database is enabled. Remedy: Set the parameter causing the error to a value within the range and run Save parameter. Switch the drive off and then switch it back on again. If the IPA of the parameter is not shown in the manual, contact the service centre. |
| 46 Load default | Cause: Can occur during loading of the parameter database saved in the Flash memory. This is normal if it appears under the following conditions:
If this message appears when the drive is already in use, it means there has been a problem in the parameter database saved in the Flash memory. When displayed, the drive restores the default database.
Remedy: Allow the drive to restore the default database. Verify configuration settings and parameters. If the error occurs during normal operation, inspect the flash memory integrity. |
| 47 Plc cfg error | Cause: This can occur during loading of the MDPLC application. The Mdplc application present on the drive is not run. Diagnostic Sub-codes:
Remedy: Remove the MDPLC application or download a correct MDPLC application. |
| 48 Load par def plc | Cause: This can occur during loading of the parameter database saved in the Flash memory of the MDPLC application. It is normal if it appears the first time the drive is switched on, after downloading a new application. If this message appears when the drive is already in use, it means there has been a problem in the parameter database saved in the Flash memory. In this case, the drive automatically runs the Load default command.
Remedy: Set the parameters to the desired value and run Save parameter. |
| 49 Key failed | Cause: This can occur at drive power-on if the wrong enabling key is entered for a given firmware function.
Remedy: Contact WEG for the correct key to enable the desired firmware function. |
| 50 Encoder error | Cause: This condition may occur when the drive is powered during encoder setup each time parameter 552 Regulation mode is set.
Remedy:
|
| 51 Opt cfg change | Cause: This may occur when powering the drive if an expansion card has been removed or replaced or the incorrect enable key is inserted for a given firmware function.
Remedy: Check the hardware configuration, then press ESC. Save the parameters (Save parameters, menu 04.01 par 550) to save the new hardware configuration. |
| 52 HumTempSensErr | Cause: Disconnection or short circuit of the humidity sensor built into the ADV200-LC drive.
Remedy: Reset the drive. If the problem persists, contact WEG Customer Service. |
| 53 ... 60 Plc9 fault ... Plc16 fault | Cause: An enabled application developed in the IEC 61131-3 environment has found the conditions for generating this specific alarm to be true. The meaning of the alarm depends on the type of application. The XXXXH-X sub-code indicates the reason for the error. Remedy: Refer to the documentation concerning the enabled application. Make a note of the XXXXH-X code to discuss it with the service centre. |
| 61 UV Wng&Restart | Cause: Parameter 4640 UnderV restart is set to "Enable". An undervoltage condition is detected, the drive is disabled, and a UV Wng & Restart warning signal is generated. Remedy: Check drive power supply wirings and verify its correct voltage range. |
| 62 An inpLoss | Cause: Occurs under the following conditions:
Remedy: Check the physical wiring and connections of the sensor/input line. |
| 63 UV Ride Thr | Cause: Parameter 3280 UV RT enable is set to 1. Due to a mains voltage dip (Mains loss), the DC link voltage value is lower than the threshold set in PAR 3282 UV RT on. Remedy: Check drive power supply wirings and verify its correct voltage range. |
How to Clear & Reset WEG ADV200 Drive Faults
- Keypad Reset: Press the red Reset / Stop key on the integrated programming keypad (KB-ADV). If the drive is under remote bus or terminal control, toggle to local mode before attempting manual keypad reset.
- Digital Input Reset (DI): If assigned in menu 08 DIGITAL INPUTS (parameter PAR 1000 – Fault Reset), apply a 24V pulse transition to the assigned digital input terminal to clear the trip condition.
- WEG_eXpress / GF_eXpress PC Tool: Connect a PC via the integrated RS485 communication port or optional USB/Ethernet expansion card, open the configuration tool, and click “Fault Reset” in the drive monitoring view.
- Fieldbus Control Word: Assert Bit 7 (Fault Reset) in the Command Word (parameter PAR 500 – Drive Commands) via Profinet, EtherNet/IP, EtherCAT, Profibus-DP, or CANopen networks.
- Power Cycle: Disconnect the incoming 3-phase AC line supply, wait at least 15 minutes until the internal DC bus filter capacitors fully discharge and all LED indicators/keypad backlight extinguish completely, then re-energize the unit.
⚠️ High-Voltage Electrical Safety Warning:
Always disconnect incoming power and wait a minimum of 15 minutes for intermediate DC bus link capacitors to fully discharge. Confirm with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] (or dynamic braking terminals [BR+/BR-]) before opening terminal covers or servicing output motor leads U, V, and W on the WEG ADV200 drive.