WEG ADV200 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG ADV200 field-oriented vector system drive series. Search or filter through the complete fault code directory below.

Field-Oriented Vector System Drive Power: 0.75 kW to 1.65 MW (1 to 2,200 HP) Embedded STO (SIL 3) & Integrated PLC
Power Range 0.75 kW – 1.65 MW (1 – 2,200 HP)
Supply Voltage 380–480V / 500–690V AC (or DC Bus)
Control Modes FOC (Open/Closed Loop), V/f & SynRM/PM
Operator Interface Integrated Alphanumeric / Graphic LCD (KB-ADV)

Complete WEG ADV200 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type Overcurrent, Ground Fault, or DC Link OV).

Alarm Code and Display MessageCause and Solution / Remedy
0

No alarm

Cause:


No alarm present.



Remedy:


No action required.
1

Overvoltage

Cause:


DC link overvoltage alarm due to energy recovered from the motor. The voltage arriving at the drive power section is too high compared to the maximum threshold relating to the PAR 560 Mains voltage parameter setting.



Remedy:



  • Extend the deceleration ramp.

  • Use a braking resistor between terminals BR1 and BR2 to dissipate the recovered energy.

  • Use the VDC Control function.


2

Undervoltage

Cause:


DC link undervoltage alarm. The voltage arriving at the drive power section is too low compared to the minimum threshold relating to the 560 Mains voltage parameter setting. This can be caused by:

  • The mains voltage being too low or overextended voltage drops.

  • Poor cable connections (e.g., loose contactor terminals, inductance, filter, etc.).





Remedy:


Check the related connections of the drive power supply and verify its correct voltage range.
3

Ground fault

Cause:


Ground short circuit alarm.



Remedy:



  • Check drive and motor wiring.

  • Verify that the motor is not grounded.


4

Overcurrent

Cause:


Instantaneous overcurrent protection intervention alarm. This may be due to the incorrect setting of current regulator parameters, a short circuit between phases, or a ground fault on the drive output.



Remedy:



  • Check the current regulator parameters.

  • Check wiring towards the motor.


5

Desaturation

Cause:


Instantaneous overcurrent in the IGBT bridge alarm.



Remedy:


Switch the drive off and then switch it on again. If the alarm persists, contact the technical service centre.
6

MultiUndervolt

Cause:


The number of attempted automatic restarts after the Undervoltage alarm has exceeded the set PAR 4650 UVRep attempts value in the PAR 4652 UVRep delay time.



Remedy:


Too many Undervoltage alarms. Adopt the proposed solutions for the Undervoltage alarm.
7

MultiOvercurr

Cause:


Two attempted automatic restarts after the Overcurrent alarm within 30 seconds. If more than 30 seconds pass after the Overcurrent alarm was generated, the attempt counter is reset.



Remedy:


Too many Overcurrent alarms. Adopt the proposed solutions for the Overcurrent alarm.
8

MultiDesat

Cause:


Two attempted automatic restarts after the Desaturation alarm within 30 seconds. If more than 30 seconds pass after the Desaturation alarm was generated, the attempt counter is reset.



Remedy:


Too many Desaturation alarms. Adopt the proposed solutions for the Desaturation alarm.
9

Heatsink OT

Cause:


Heatsink temperature too high alarm.



Remedy:



  • Verify the correct operation of the cooling fan.

  • Check that the heatsinks are not clogged.

  • Check that the openings for the cabinet cooling air are not blocked.


10

HeatsinkS OTUT

Cause:


IGBT modules temperature too high or too low alarm.



Remedy:



  • Verify the correct operation of the cooling fan.

  • Check that the heatsinks are not clogged.

  • Check that the openings for the cabinet cooling air are not blocked.


11

Intakeair OT

Cause:


Intake drive air temperature too high alarm.



Remedy:



  • Check correct fan operation.

  • Check that the heatsinks are not clogged.

  • Check temperature in electrical panel.


12

Motor OT

Cause:


Motor overtemperature alarm. Possible causes:

  • Load cycle too heavy.

  • The motor is installed in a place where the ambient temperature is too high.

  • If the motor is provided with a blower: the fan is not working.

  • If the motor is not provided with a blower: the load is too high at slow speeds. Cooling the fan on the motor shaft is not sufficient for this load cycle.

  • The motor is used at less than the rated frequency, causing additional magnetic losses.





Remedy:



  • Change the processing cycle.

  • Use a cooling fan to cool the motor.


13

Drive overload

Cause:


Drive overload alarm. The overload threshold of the accumulator of the I²t drive thermal image has been exceeded.



Remedy:


Check that the size of the drive is suitable for the application.
14

Motor overload

Cause:


Motor overload alarm. The current absorbed during operation is greater than that specified on the motor data plate. The overload threshold of the accumulator of the I²t motor thermal image has been exceeded.



Remedy:



  • Reduce the motor load.

  • Increase the size of the motor.


15

Bres overload

Cause:


Braking resistor overload alarm. The current absorbed by the resistor is greater than the rated current. The overload threshold of the accumulator of the I²t braking resistor thermal image has been exceeded.



Remedy:


Increase the Watt value of the braking resistor.
16

Phase loss

Cause:


Power phase loss alarm.



Remedy:


Check the mains voltage and whether any protections upstream of the drive have been tripped.
17

Opt Bus fault

Cause:


Error in the configuration stage or communication error.

  • XXX0H-X: If the first digit to the left of "H" in the alarm sub-code is 0, the error regards a communication problem.

  • XXXXH-X: If the first digit to the left of "H" in the alarm sub-code is other than 0, the error regards a configuration problem.





Remedy:


For configuration errors, check the configuration of the bus communication, type of bus, baudrate, address, and parameter settings.

For communication errors, verify wiring, resistance of terminations, interference immunity, and timeout settings. For further details, please refer to the user guide for the specific bus.
18

Opt 1 IO fault

Cause:


Error in the communication between Regulation and I/O expansion card in slot 1.



Remedy:


Check that it has been inserted correctly, see chapter 10.5.
19

Opt 2 IO fault

Cause:


Error in the communication between Regulation and I/O expansion card in slot 2 or 3.



Remedy:


Check that it has been inserted correctly, see chapter 10.5.
20

Opt Enc fault

Cause:


Error in the communication between Regulation and Encoder feedback card.



Remedy:


Check that it has been inserted correctly, see chapter 10.5.
21

External fault

Cause:


External alarm present. A digital input has been programmed as an external alarm, but the +24V voltage is not available on the terminal.



Remedy:


Check that the terminal screws are tight.
22

Speed fbk loss

Cause:


Speed feedback loss alarm. The encoder is not connected, not connected properly, or not powered. This can be verified by selecting the PAR 260 Motor speed parameter in the MONITOR menu.



This alarm is generated in case of an encoder fault. Each type of encoder generates a "Loss of feedback" alarm differently. See parameter 2172 SpdFbkLoss code for more information about the cause of the alarm and chapter D.1.



Remedy:



  • Check encoder wiring for integrity.

  • Check that the encoder is connected to the power supply.

  • With the drive disabled, turn the motor clockwise (seen from the motor shaft side). A positive value must be displayed.

  • If the value does not change or values are indicated randomly, check the encoder power supply and cables.

  • If the value displayed is negative, invert the encoder connections. Change channel A+ and A- or B+ and B-.

  • Check that the encoder electronics are consistent with those of the relative expansion card.


23

Overspeed

Cause:


Motor overspeed alarm. The motor speed exceeds the limits set in the PAR 4540 Overspeed threshold parameter.



Remedy:



  • Limit the speed reference.

  • Check that the motor is not driven in overspeed during rotation.


24

Speed ref loss

Cause:


Speed reference loss alarm. Occurs if the difference between the speed regulator reference and the actual motor speed is more than 100 rpm. This condition occurs because the drive is in the current limit condition.



Note: This is only available in the Flux Vect OL and Flux Vect OC mode.



Remedy:



  • Check the drive load conditions.

  • Check the number of encoder impulses.


25

Emg stop alarm

Cause:


Emergency stop alarm. The Stop key on the keypad was pressed with the PAR 1008 Stop key mode parameter set to EmgStop&Alarm.



Active in remote control mode (PAR 1012=1) both by using "Terminals" command or "Digital" commands and, in local control mode (PAR 1012=0) by using "Terminals" command.



Remedy:


Eliminate the reason for which the Stop key on the keypad was pressed and reset the drive.
26

Power down

Cause:


The drive was enabled with no supply voltage at the power section.



Remedy:


Check the drive power supply.
27

ExtIO fault

Cause:


Communication fault with the external module.



Remedy:


See paragraph "8.1.2 ExtIO fault Alarm", page 129.
28

FastLink fault

Cause:


FastLink communication fault.



Remedy:


See paragraph "8.1.3 FastLink Alarm", page 130.
29

Brake fault

Cause:


Incorrect setting of brake control function parameters.



Remedy:


See menu 22.13 - FUNCTIONS/BRAKE CONTROL.
30

Motor pre OT

Cause:


Motor overtemperature prealarm. % value of threshold compared to PAR 4532 MotorOT thr.



Remedy:


Verify if the value is set too low for the current duty cycle. Ensure the duty cycle matches drive thermal specifications.
31

Mot phase loss

Cause:


Output phase loss.



Remedy:


Check the Drive/motor output connections.
32

Condensation

Cause:


High condensation level inside the drive. Operating conditions (combination of ambient temperature, humidity, and cooling liquid temperature) are not safe.



Remedy:


Safe conditions are obtained when the work point is under the respective curve indicated in the graph of chapter 22.18 - FUNCTIONS/LC CONTROL. Otherwise, you must take adequate precautions to lower the ambient temperature and/or the relative humidity or to raise the cooling liquid temperature.
33 ... 40

Plc1 fault ... Plc8 fault

Cause:


An enabled application developed in the IEC 61131-3 environment has found the conditions for generating this specific alarm to be true. The meaning of the alarm depends on the type of application.



The XXXXH-X sub-code indicates the reason for the error.



Remedy:


Refer to the documentation concerning the enabled application. Make a note of the XXXXH-X code to discuss it with the service centre.
41

Watchdog

Cause:


May occur during functioning when the watchdog protection of the microcontroller is activated. The alarm is inserted in the alarm list and alarm log. Following this alarm:

  • The drive automatically runs a reset.

  • Motor control is not available.


The XXXXH-X sub-code indicates the reason for the error.



Remedy:


If the alarm was a consequence of a variation to the drive configuration (parameter setting, installation of an option, downloading of a PLC application), remove it. Switch the drive off and then switch it on again. Take note of the XXXXH-X code for examination with the service centre.
42

Trap error

Cause:


This condition can occur during operation when the trap micro protection is enabled. The alarm is included in the list of alarms and alarm log. Following this alarm:

  • The drive automatically runs a reset.

  • Motor control is not available.


The XXXXH-X code (SubHandler-Class) indicates the reason for the error.



Remedy:


If the alarm was a consequence of a variation to the drive configuration (parameter setting, installation of an option, downloading of a PLC application), remove it. Switch the drive off and then switch it on again. Take note of the XXXXH-X code for examination with the service centre.
43

System error

Cause:


This condition can occur during operation when the operating system protection is enabled. The alarm is included in the list of alarms and alarm log. Following this alarm:

  • The drive automatically runs a reset.

  • Motor control is not available.


The XXXXH-X code (Error-Pid) indicates the reason for the error.



Remedy:


If the alarm was a consequence of a variation to the drive configuration (parameter setting, installation of an option, downloading of a PLC application), remove it. Switch the drive off and then switch it on again. Take note of the XXXXH-X code for examination with the service centre.
44

User error

Cause:


This condition can occur during operation when the software protection is enabled. The alarm is included in the list of alarms and alarm log. Following this alarm:

  • The drive automatically runs a reset.

  • Motor control is not available.


The XXXXH-X (Error-Pid) code indicates the reason for the error.



Remedy:


If the alarm was a consequence of a variation to the drive configuration (parameter setting, installation of an option, downloading of a PLC application), remove it. Switch the drive off and then switch it on again. Make a note of the XXXXH-X code to discuss it with the service centre.
45

Param error

Cause:


Occurs if an error happens during the enabling of the parameter database saved in the Flash memory. The alarm is included in the list of alarms and alarm log.



The XXXXH-X code indicates the IPA of the parameter that has been set outside the range allowed when the database is enabled.



Remedy:


Set the parameter causing the error to a value within the range and run Save parameter. Switch the drive off and then switch it back on again. If the IPA of the parameter is not shown in the manual, contact the service centre.
46

Load default

Cause:


Can occur during loading of the parameter database saved in the Flash memory. This is normal if it appears under the following conditions:

  • The first time the drive is switched on.

  • When a new version of the firmware is downloaded.

  • When the regulation card is installed on a new size.

  • When a new region is entered.


If this message appears when the drive is already in use, it means there has been a problem in the parameter database saved in the Flash memory. When displayed, the drive restores the default database.

  • 0001H-1: The database saved is not valid

  • 0002H-2: The database saved is not compatible

  • 0003H-3: The saved database refers to a different size and not to the current size





Remedy:


Allow the drive to restore the default database. Verify configuration settings and parameters. If the error occurs during normal operation, inspect the flash memory integrity.
47

Plc cfg error

Cause:


This can occur during loading of the MDPLC application. The Mdplc application present on the drive is not run.



Diagnostic Sub-codes:

  • 0004H-4: The application that has been downloaded has a different CRC on the DataBlock and Function table.

  • 0065H-101: The application that has been downloaded has an invalid identification code (Info).

  • 0066H-102: The application that has been downloaded uses an incorrect task number (Info).

  • 0067H-103: The application that has been downloaded has an incorrect software configuration.

  • 0068H-104: The application that has been downloaded has a different CRC on the DataBlock and Function table.

  • 0069H-105: A Trap error or System error has occurred. The drive has automatically executed a Power-up operation. Application not executed. See the Alarm List for more information about an error that has occurred.

  • 006AH-106: The application that has been downloaded has an invalid identification code (Task).

  • 006BH-107: The application that has been downloaded uses an incorrect task number (Task).

  • 006CH-108: The application that has been downloaded has an incorrect CRC (Tables + Code).




Remedy:


Remove the MDPLC application or download a correct MDPLC application.
48

Load par def plc

Cause:


This can occur during loading of the parameter database saved in the Flash memory of the MDPLC application.



It is normal if it appears the first time the drive is switched on, after downloading a new application. If this message appears when the drive is already in use, it means there has been a problem in the parameter database saved in the Flash memory. In this case, the drive automatically runs the Load default command.

  • 0001H-1: The database saved is not valid.




Remedy:


Set the parameters to the desired value and run Save parameter.
49

Key failed

Cause:


This can occur at drive power-on if the wrong enabling key is entered for a given firmware function.

  • 0001H-1: Incorrect PLC key. PLC application not available.




Remedy:


Contact WEG for the correct key to enable the desired firmware function.
50

Encoder error

Cause:


This condition may occur when the drive is powered during encoder setup each time parameter 552 Regulation mode is set.

  • 100H-256: An error occurred during setup; the information received from the encoder is not reliable. If the encoder is used for feedback, the Speed fbk loss [22] alarm is also generated.

  • 200H-512: The firmware on the optional encoder card is incompatible with that on the regulation card. The information received from the encoder is not reliable.




Remedy:



  • For sub-code 100H-256, take the recommended action for the Speed fbk loss [22] alarm.

  • For sub-code 200H-512, contact WEG to update the firmware on the optional encoder card.


51

Opt cfg change

Cause:


This may occur when powering the drive if an expansion card has been removed or replaced or the incorrect enable key is inserted for a given firmware function.

  • 0064H-100: Card removed from slot 1.

  • 0014H-20: Card removed from slot 2.

  • 0003H-3: Card removed from slot 3.

  • 0078H-120: Card removed from slot 1 and from slot 2.

  • 0067H-103: Card removed from slot 1 and from slot 3.

  • 0017H-23: Card removed from slot 2 and from slot 3.

  • 007BH-123: Card removed from slot 1, from slot 2, and from slot 3.




Remedy:


Check the hardware configuration, then press ESC. Save the parameters (Save parameters, menu 04.01 par 550) to save the new hardware configuration.
52

HumTempSensErr

Cause:


Disconnection or short circuit of the humidity sensor built into the ADV200-LC drive.

  • 0x0: No error.

  • 0x1: Communication error on humidity / temperature sensor.

  • 0x2: Error on NTC temperature sensor for temperature of liquid flowing into heatsink.

  • 0x3: Communication error and NTC temperature sensor.




Remedy:


Reset the drive. If the problem persists, contact WEG Customer Service.
53 ... 60

Plc9 fault ... Plc16 fault

Cause:


An enabled application developed in the IEC 61131-3 environment has found the conditions for generating this specific alarm to be true. The meaning of the alarm depends on the type of application.



The XXXXH-X sub-code indicates the reason for the error.



Remedy:


Refer to the documentation concerning the enabled application. Make a note of the XXXXH-X code to discuss it with the service centre.
61

UV Wng&Restart

Cause:


Parameter 4640 UnderV restart is set to "Enable". An undervoltage condition is detected, the drive is disabled, and a UV Wng & Restart warning signal is generated.



Remedy:


Check drive power supply wirings and verify its correct voltage range.
62

An inpLoss

Cause:


Occurs under the following conditions:

  • The input signal is below 0.1V or 4-20mA.

  • The KTY84 sensor short-circuits or disconnects.





Remedy:


Check the physical wiring and connections of the sensor/input line.
63

UV Ride Thr

Cause:


Parameter 3280 UV RT enable is set to 1. Due to a mains voltage dip (Mains loss), the DC link voltage value is lower than the threshold set in PAR 3282 UV RT on.



Remedy:


Check drive power supply wirings and verify its correct voltage range.

How to Clear & Reset WEG ADV200 Drive Faults

  1. Keypad Reset: Press the red Reset / Stop key on the integrated programming keypad (KB-ADV). If the drive is under remote bus or terminal control, toggle to local mode before attempting manual keypad reset.
  2. Digital Input Reset (DI): If assigned in menu 08 DIGITAL INPUTS (parameter PAR 1000 – Fault Reset), apply a 24V pulse transition to the assigned digital input terminal to clear the trip condition.
  3. WEG_eXpress / GF_eXpress PC Tool: Connect a PC via the integrated RS485 communication port or optional USB/Ethernet expansion card, open the configuration tool, and click “Fault Reset” in the drive monitoring view.
  4. Fieldbus Control Word: Assert Bit 7 (Fault Reset) in the Command Word (parameter PAR 500 – Drive Commands) via Profinet, EtherNet/IP, EtherCAT, Profibus-DP, or CANopen networks.
  5. Power Cycle: Disconnect the incoming 3-phase AC line supply, wait at least 15 minutes until the internal DC bus filter capacitors fully discharge and all LED indicators/keypad backlight extinguish completely, then re-energize the unit.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect incoming power and wait a minimum of 15 minutes for intermediate DC bus link capacitors to fully discharge. Confirm with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+DC] and [-DC] (or dynamic braking terminals [BR+/BR-]) before opening terminal covers or servicing output motor leads U, V, and W on the WEG ADV200 drive.