WEG Drives Fault Codes & Troubleshooting

Complete diagnostic database for 13 WEG drive series (CFW, ADV & ADL series). Browse fault codes, alarms, causes, and step-by-step fixes for industrial AC variable speed drives, HVAC inverters, and lift controllers. Select your drive model series below to access parameter checks, root cause analysis, and physical inspection workflows.

10 CFW Series Drives 3 Industrial & Lift Series 13 Total Series

WEG CFW Series AC Variable Frequency Drives

10 Models

WEG Industrial & Elevator Drives

3 Models

Most Common WEG Drive Fault Codes

Diagnostic Quick Reference
Fault Code Alarm Code Fault Description Common Root Cause
F0070 / F0071 A0046 Overcurrent / Short Circuit Output current exceeded peak allowable limit; phase-to-phase short on U, V, W, jammed mechanical load, or rapid acceleration ramp.
F0022 A0022 DC Bus Overvoltage DC link voltage exceeded upper threshold; high regenerative energy returned during deceleration ramp without dynamic braking resistor.
F0006 A0006 DC Bus Undervoltage Intermediate DC link voltage dropped below operating limit; mains supply failure, severe line voltage sag, or open pre-charge relay.
F0072 A0072 Ground / Earth Fault Ground leakage current detected at motor output phases; damaged motor power cable jacket or deteriorated stator insulation.
F0078 A0047 Motor Overload (I²t) Continuous operation exceeding motor nameplate Full Load Amps (FLA) according to electronic thermal model; mechanical binding.
F0080 / F0081 A0050 Heatsink Overtemperature IGBT module or heatsink temperature sensor exceeded safety threshold; clogged ventilation ducts, fan failure, or high ambient (>50°C).
F0030 A0030 Input Phase Loss Missing phase or high DC bus ripple detected on incoming 3-phase line terminals (L/L1, N/L2, L3) or blown line-side fuse.

How to Clear & Reset WEG Faults

  1. HMI Keypad Reset: Press the red O / RESET key directly on the front-mounted HMI keypad after addressing the fault root cause.
  2. Digital Input (DI) Terminal: Apply a momentary 24VDC pulse to the digital input configured for Reset (e.g., parameter P0263–P0270 set to option Reset).
  3. SuperDrive G2 / WPS Software: Connect via USB or fieldbus, open the diagnostic status window inside WEG SuperDrive G2 or WPS (WEG Programming Suite), and click “Reset Fault”.
  4. Main Power Disconnect Cycle: Turn off incoming 3-phase AC line power, wait until the internal DC bus charge LED completely turns off and voltage drops below 50VDC (minimum 5 minutes), and reapply power.
⚠️ High-Voltage Safety Warning: Lethal intermediate circuit DC bus voltage remains stored inside the filter capacitors even after disconnecting input AC power. Wait at least 5 minutes after power shut-off and verify with a calibrated digital multimeter across terminals (+UD) and (-UD) (or +DC and -DC) that the voltage is strictly below 50VDC before inspecting internal connections or motor terminals.