WEG CFW09 drive

Home / WEG / WEG CFW09 drive

WEG CFW09 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW09 (CFW-09) variable speed drive series. Search or filter through the complete fault code directory below.

Vectrue Technology® & Optimal Braking™ Power: 1.1 to 1100 kW (1.5 to 1500 HP) Intelligent Dual Display Keypad (LCD/LED)
Power Range 1.1 – 1100 kW (1.5 – 1500 HP)
Supply Voltage 220–230V / 380–480V / 500–690V AC
Control Modes V/f, VVW, Sensorless & Vector (Closed Loop)
Operator Interface Detachable Smart Keypad & SuperDrive PC

Complete WEG CFW09 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E00, E01, or Overcurrent).

Fault / Alarm and MeaningCause and Remedy
E00

Output Overcurrent / Short-circuit

Cause:



  • Short-circuit between two motor phases.

  • Short-circuit between braking resistor cables.

  • Output current reaches 2 × P295, caused by very high load inertia, acceleration ramp too fast, or incorrect regulation and/or configuration parameters.

  • Transistor module short-circuited.

  • Parameters P169 to P172 are configured too high.





Remedy:


Check output motor cabling for phase-to-phase short-circuits. Check dynamic braking resistor connection leads for insulation wear or shorts. Reduce load inertia, or increase the acceleration ramp time. Verify control parameters and decrease parameters P169 to P172 if set too high.



Reset options: Power-on, Manual reset (Key 0), Overcurrent Auto-reset, DIx, Serial, Fieldbus.
E01

Overvoltage (Ud) / DC Link Overvoltage

Cause:


The DC-bus voltage of the inverter has exceeded the permissible limits (check Ud in parameter P004):

  • 220-230 V Models: Ud > 400 V

  • 380-480 V Models: Ud > 800 V

  • 500-600 V / 500-690 V Models (supply 500-600V): Ud > 1000 V

  • 500-690 V / 660-690 V Models (supply 660-690V): Ud > 1200 V

  • Load inertia too high or deceleration ramp too short.

  • Parameters P151 or P153 are configured too high.





Remedy:


Verify incoming mains supply voltage stability (P004). Increase deceleration ramp time or reduce load inertia. Use a dynamic braking resistor if necessary. Decrease parameters P151 or P153 if set too high.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E02

Undervoltage (Ud) / DC Link Undervoltage

Cause:


The DC-bus voltage of the inverter has fallen below the permissible limits (check Ud in parameter P004):

  • 220-230 V power supply: Ud < 223 V

  • 380 V power supply: Ud < 385 V

  • 400-415 V power supply: Ud < 405 V

  • 440-460 V power supply: Ud < 446 V

  • 480 V power supply: Ud < 487 V

  • 500-525 V power supply: Ud < 532 V

  • 550-575 V power supply: Ud < 582 V

  • 600 V power supply: Ud < 608 V

  • 660-690 V power supply: Ud < 699 V

  • Phase loss at the input.

  • Auxiliary circuit fuse blown (only valid for 105 A and 130 A/220-230 V, 86 A to 600 A/380-480 V, and 44 A to 79 A/500-600 V models).

  • Pre-charge contactor is defective.

  • Parameter P296 is set to a voltage higher than the actual power supply voltage.





Remedy:


Check input mains voltages. Check terminal blocks and check for missing phases. Verify pre-charge contactor and auxiliary circuit fuses (refer to manual section 3.2.3). Ensure parameter P296 matches your actual rated supply voltage.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E03

Input Undervoltage / Phase Loss

Cause:


Power supply voltage is too low, check supply line voltage:

  • 220-230 V Models: Power Supply < 154 V

  • 380-480 V Models: Power Supply < 266 V

  • 500-600 V / 500-690 V Models: Power Supply < 361 V

  • 660-690 V Models: Power Supply < 462 V

  • Phase loss at the inverter input.

  • Activation Time limit: 2.0 s.





Remedy:


Check mains supply line for phase drops or drops in voltage. Verify general supply voltage stability.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E04

Inverter Overtemperature or Pre-charge Circuit Defective

Cause:



  • Ambient temperature too high (> 40 °C) and/or output current too high; or ambient temperature < -10 °C.

  • Cooling blowers are locked or defective.

  • Auxiliary circuit fuse blown (only valid for 105 A and 130 A/220-230 V, 86 A to 600 A/380-480 V, and 44 A to 79 A/500-600 V models).

  • Problem with the supply voltage (voltage sag or interruption/phase loss lasting for more than 2 seconds) with the phase loss detection disabled (P214 = 0).

  • Inverted polarity signal at Analog inputs AI1/AI2.





Remedy:


Verify cooling fan is functioning and clean any dust from the heatsink. Improve cabinet airflow. Verify ambient working temperatures (ensure between -10 °C and 40 °C). Check supply lines and auxiliary circuit fuses (refer to manual section 3.2.3). Verify polarity on analog input channels AI1/AI2.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E05

Inverter / Motor Overload (I × t Function)

Cause:



  • Parameters P156, P157, and P158 are configured too low for the connected motor.

  • Motor is under an actual overload condition.





Remedy:


Verify motor nominal currents and check P156, P157, and P158 against nameplate data. Check mechanical load on shaft.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E06

External Fault

Cause:



  • Any digital input (DI3 to DI7) programmed for external fault detection (parameters P265 to P270 set to 4 – No Ext Flt) is open (not connected to +24 V).

  • Terminal block XC12 on the control board CC9 is not properly connected.





Remedy:


Verify external cabling loops to the assigned digital inputs. Ensure terminal block XC12 on the control board CC9 is fully seated.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E07

Encoder Fault

Cause:



  • Miswiring between encoder and terminal block XC9 (optional board EBA/EBB/EBC/EBE).

  • Encoder is defective.




Note: This fault is valid only if P202 = 4 (Vector with Encoder).



Remedy:


Check encoder connection sequence to XC9. Verify mechanical mounting of encoder (refer to manual section 8.2). Swap encoder if defective.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E08

CPU Error (watchdog)

Cause:



  • High electrical noise.





Remedy:


Optimize cabinet grounding and shield terminations to mitigate noise.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E09

Program Memory Error (Checksum)

Cause:



  • Memory with corrupted values.





Remedy:


This indicates internal card memory failure. Please contact WEG technical support.



Reset: Contact WEG.
E10

Error in the Copy Function

Cause:



  • Attempted to copy HMI parameters to an inverter with a different software version.





Remedy:


Verify firmware and software versions match between target inverter and HMI file before copying.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E11

Ground Fault

Cause:



  • Short-circuit between one or more output phases and ground.

  • Motor cable capacitance to ground is too high.





Remedy:


Verify insulation of motor cables and motor winding. If cable is extremely long, shorten lines or add an output reactor.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E12

Braking Resistor Overload

Cause:



  • Load inertia too high or deceleration ramp too short.

  • Load on the motor shaft too high.

  • Parameters P154 and P155 are programmed incorrectly.





Remedy:


Increase deceleration ramp time. Adjust mechanical shaft load. Verify and correct parameter configurations for P154 and P155.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx.
E13

Incorrect encoder sense of rotation

Cause:



  • Cables U, V, W to motor are inverted.

  • Encoder channels A and B are inverted.

  • Encoder mounted in wrong position.




Note: This is valid for P202 = 4 (Encoder), with P408 = runs to Imr. This fault can only occur during Self-tuning.



Remedy:


Do not reset this fault and restart without first correcting the direction of either the encoder or the motor. Swap motor output phases (U, V, W) or invert encoder channels A and B. Correct physical mount orientation of the encoder.
E15

Motor Phase Loss

Cause:



  • Bad contact or broken wiring between motor and inverter.

  • Incorrect value programmed in parameter P401.

  • Vector Control without orientation.

  • Vector Control with encoder, encoder wiring or connection to motor is inverted.





Remedy:


Check motor cables and winding loop continuity. Verify parameter P401 rating settings. Review vector control orientation parameters and check encoder connections.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E17

Overspeed Fault

Cause:



  • The effective overspeed has exceeded the value of P134 + P132 for longer than 20 ms.





Remedy:


Verify speed loop tuning and speed feedback channels. Check mechanical load variations.
E24

Programming Error

Cause:



  • Incompatible parameters were programmed (refer to manual Table 4.2).





Remedy:


This fault is automatically reset when the incompatible parameters are correctly programmed. Resolve conflicting parameter values according to manual Table 4.2 definitions.
E31

Keypad (HMI) Connection Fault

Cause:



  • Keypad cable misconnected.

  • Electrical noise in the installation (electromagnetic interference).





Remedy:


This fault is automatically reset when HMI communication with the inverter is reestablished. Check keypad RJ45/serial cable connections. Protect the cable from electromagnetic noise.
E32

Motor Overtemperature

Cause:



  • Motor is under an actual overload condition.

  • Duty cycle is too high (too many starts/stops per minute).

  • Ambient temperature is too high.

  • Motor thermistor miswiring or short-circuit (resistance < 100 Ω) at terminals XC4:2 and XC4:3 of the optional board EBA or at terminals XC5:2 and XC5:3 of the optional board EBB.

  • Parameter P270 programmed to 16 unintentionally, with EBA/EBB board not installed and/or motor thermistor not connected.

  • Motor is in locked rotor condition.




Note: Overtemperature protection (4).



Remedy:


Check motor load status and duty cycles. Reduce starts/stops per minute. Verify thermistor cabling loop resistance is not < 100 Ω. Check configuration parameter P270. Verify motor shaft is free to rotate.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus.
E33

Speed without Control

Cause:



  • Overweight load conditions.

  • Brake Failure.




Note: Control parameter (8).



Remedy:


Check mechanical brakes and load stability.
E34

Long Period at Torque Limitation

Cause:



  • The load was too heavy and the CFW-09 operated at torque limitation for a period longer than allowed.

  • Failure on the brake opening caused the CFW-09 to operate at torque limitation for a period longer than allowed.




Note: Torque limit parameter (9).



Remedy:


Reduce motor load. Verify brake opening coil, connections, and limit switches.
E41

Self Diagnosis Fault

Cause:



  • Memory error or any internal inverter circuit defective.





Remedy:


Contact WEG technical support for control card evaluation.



Reset: Contact WEG.

How to Clear & Reset WEG CFW09 Drive Faults

  1. Keypad Reset: Press the red O (Stop / Reset) key on the detachable smart HMI keypad. If operating under remote automation control (REM), toggle to local mode (LOC) via the LOC/REM key before executing a manual reset.
  2. Digital Input Reset (DI): If programmed in parameters P263 to P268 (DI1 to DI6 function) for “Fault Reset” (option 8 / Reset), activate the assigned digital input terminal momentarily to clear the trip.
  3. SuperDrive PC Software: Connect via the RS-232 / RS-485 serial communication interface (KSD-CFW09), open the WEG SuperDrive software, and click “Fault Reset” in the online diagnostic monitor.
  4. Fieldbus Network: Set the reset bit in the control word via serial communication protocols (Modbus RTU built-in, or optional Profibus DP / DeviceNet expansion cards).
  5. Power Cycle Reset: Disconnect AC line input power, wait for the DC link bus capacitors to fully discharge (wait until keypad display and status LEDs turn completely off, approx. 5 minutes), then reapply mains power.
⚠️ High-Voltage Electrical Safety Warning: Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC / -DC] or [UDC+ / UDC-] before inspecting motor leads, opening terminal covers, or touching output terminals U, V, and W on the WEG CFW09 drive.