WEG CFW-11 drive

Home / WEG / WEG CFW-11 drive

WEG CFW-11 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW-11 variable frequency drive series. Search or filter through the complete fault code directory below.

Heavy Duty Industrial VFD Power: 1.1 to 630 kW (1.5 to 900 HP) Vectrue Technology® & SoftPLC
Power Range 1.1 – 630 kW (1.5 – 900 HP)
Supply Voltage 200–240V / 380–480V / 500–690V AC
Control Modes V/f, VVW, Sensorless & Closed-Loop Vector
Operator Interface Detachable Graphic HMI / Backlit LCD

Complete WEG CFW-11 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F006, F021, or Overcurrent).

Fault / Alarm and MeaningCause and Remedy
F006

Imbalance or Input Phase Loss

Mains voltage imbalance too high or phase missing in the input power supply.

Cause:



  • Phase missing at the inverter's input power supply.

  • Input voltage imbalance > 5%.

  • For Frame Size E: Phase loss at L3/R or L3/S (may cause F021 or F185); phase loss at L3/T will cause F006.

  • For Frame Sizes F and G: Pre-charge circuit fault.




Note: If the motor is unloaded or operating with reduced load this fault may not occur.



Remedy:


Verify input mains wiring and fuses. Measure the incoming line voltage imbalance.

  • Fault delay is set at parameter P0357. Setting P0357 = 0 disables the fault.

  • If a single-phase power supply is used, this fault must be disabled.


A010

Rectifier High Temperature

A high temperature alarm was detected by the NTC temperature sensors located in the rectifier modules.

Cause:



  • Surrounding air temperature is too high (> 50 °C (122 °F)) and output current is too high.

  • Blocked or defective cooling fan.

  • Inverter heatsink is completely covered with dust.





Remedy:


Check the ambient operating temperature. Clean the heatsink dust and check if the cooling fans are operational.

  • This alarm can be disabled by setting parameter P0353 = 2 or 3.


F011

Rectifier Overtemperature

An overtemperature fault was detected by the NTC temperature sensors located in the rectifier modules.

Cause:



  • Surrounding air temperature is too high (> 50 °C (122 °F)) and output current is too high.

  • Blocked or defective cooling fan.

  • Inverter heatsink is completely covered with dust.





Remedy:


Reduce surrounding ambient temperature or drive output load. Inspect and replace the cooling fan if defective. Clean dust from heatsink fins.
F020

Undervoltage in the 24 Vdc Power Supply

Undervoltage fault in the 24 Vdc power supply.

Cause:


Voltage of the 24 Vdc control power supply is below the minimum value of 22.8 Vdc.



Remedy:


Check the incoming 24 Vdc control power supply and its connections. Ensure the external power source is rated correctly.
F021

DC Link Undervoltage

DC link undervoltage condition occurred.

Cause:


The input voltage is too low and the DC bus voltage dropped below the minimum permitted value (monitor value at parameter P0004):

  • Ud < 223 V: For a 200-240 V three-phase input voltage.

  • Ud < 170 V: For a 200-240 V single-phase input voltage (models CFW11XXXXS2 or CFW11XXXXB2) (P0296 = 0).

  • Ud < 385 V: For a 380 V input voltage (P0296 = 1).

  • Ud < 405 V: For a 400-415 V input voltage (P0296 = 2).

  • Ud < 446 V: For a 440-460 V input voltage (P0296 = 3).

  • Ud < 487 V: For a 480 V input voltage (P0296 = 4).

  • Ud < 530 V: Supply voltage 500-525 V (P0296 = 5).

  • Ud < 580 V: Supply voltage 550-575 V (P0296 = 6).

  • Ud < 605 V: Supply voltage 600 V (P0296 = 7).

  • Ud < 696 V: Supply voltage 660-690 V (P0296 = 8).

  • Phase loss in the input power supply.

  • Pre-charge circuit failure.

  • Parameter P0296 was set to a value above the power supply rated voltage.





Remedy:


Monitor parameter P0004. Verify mains voltage levels and check for line phase drop. Check the integrity of the pre-charge circuit components. Ensure parameter P0296 matches your actual rated supply voltage.
F022

DC Link Overvoltage

DC link overvoltage condition occurred.

Cause:


The input voltage is too high and the DC bus voltage surpassed the maximum permitted value:

  • Ud > 400 V: For 220-230 V input models (P0296 = 0).

  • Ud > 800 V: For 380-480 V input models (P0296 = 1, 2, 3, or 4).

  • Ud > 1000 V: For 500-600 V input models (P0296 = 5, 6 and 7).

  • Ud > 1200 V: For 660-690 V (P0296 = 8).

  • Inertia of the driven-load is too high or deceleration time is too short.

  • Incorrect settings for parameters P0151, P0153, or P0185.





Remedy:


Verify incoming mains supply. Increase deceleration time or reduce load inertia. Use a dynamic braking resistor if required. Check and adjust the settings of parameters P0151, P0153, and P0185.
F028

Motor Stop Time Exceeded

Motor stop time exceeded fault.

Cause:



  • Motor is being dragged by the load.

  • Sensorless control is operating with wrong orientation.





Remedy:


Ensure the load is not driving/dragging the motor shaft during stopping. Verify the sensorless vector control tuning and orientation parameters.
F030

Power Module U Fault

Desaturation of IGBT occurred in Power Module U.

Cause:


Short-circuit between motor phases U and V or U and W.



Remedy:


Inspect output motor cables and motor terminal box for short circuits between phase U-V or U-W. If motor connections are correct, verify IGBT state.
F034

Power Module V Fault

Desaturation of IGBT occurred in Power Module V.

Cause:


Short-circuit between motor phases V and U or V and W.



Remedy:


Inspect output motor cables and motor terminal box for short circuits between phase V-U or V-W. If motor connections are correct, verify IGBT state.
F038

Power Module W Fault

Desaturation of IGBT occurred in Power Module W.

Cause:


Short-circuit between motor phases W and U or W and V.



Remedy:


Inspect output motor cables and motor terminal box for short circuits between phase W-U or W-V. If motor connections are correct, verify IGBT state.
F042

DB IGBT Fault

Desaturation of Dynamic Braking IGBT occurred.

Cause:


Short-circuit between the connection cables of the dynamic braking resistor.



Remedy:


Check connection cables of the braking resistor for insulation wear or short circuits. Verify the resistance of the dynamic braking resistor.
A046

High Load on Motor

Load is too high for the used motor.

Cause:



  • Settings of parameters P0156, P0157, and P0158 are configured too low for the connected motor.

  • Motor shaft load is excessive.





Remedy:


Adjust overload protection parameters P0156, P0157, and P0158 to match the motor's actual capacity. Check for mechanical blocks on the motor shaft.

  • This alarm can be disabled by setting parameter P0348 = 0 or 2.


A047

IGBT Overload Alarm

An IGBTs overload alarm occurred.

Cause:


Inverter output current is too high.



Remedy:


Analyze operating load and duty cycle to lower active output current.

  • This alarm can be disabled by setting parameter P0350 = 0 or 2.


F048

IGBT Overload Fault

An IGBTs overload fault occurred.

Cause:


Inverter output current is too high.



Remedy:


Analyze motor load conditions. Check drive dimensioning if current remains continuously high.
A050

IGBT High Temperature U

A high temperature alarm was detected by the NTC temperature sensors located on the IGBTs.

Cause:



  • Surrounding air temperature is too high and output current is too high.

  • Blocked or defective cooling fan.





Remedy:


Verify cooling system, fan operation, and surrounding air temperature. Keep heatsink fins clean.

  • This alarm can be disabled by setting parameter P0353 = 2 or 3.


F051

IGBT Overtemperature U

A high temperature fault was detected by the NTC temperature sensors located on the IGBTs.

Cause:



  • Blocked or defective fan.

  • Heatsink is dirty/blocked with dust.





Remedy:


Ensure fan is functioning and replace if defective. Clean dust from heatsink fins. Check ambient temperature.
A053

High Temperature on IGBTs V

Alarm of high temperature measured at the NTC temperature sensors of the IGBTs (phase V).

Cause:


High temperature measured at phase V IGBT module.



Remedy:


Verify fan operation, clean heatsink, and check ambient temperature.

  • This alarm can be disabled by setting parameter P0353 = 2 or 3.


F054

Overtemperature on IGBTs V

Fault of overtemperature measured at the NTC temperature sensors of the IGBTs (phase V).

Cause:


Overtemperature measured at phase V IGBT module.



Remedy:


Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature.
A056

High Temperature on IGBTs W

Alarm of high temperature measured at the NTC temperature sensors of the IGBTs (phase W).

Cause:


High temperature measured at phase W IGBT module.



Remedy:


Verify fan operation, clean heatsink, and check ambient temperature.

  • This alarm can be disabled by setting parameter P0353 = 2 or 3.


F057

Overtemperature on IGBTs W

Fault of overtemperature measured at the NTC temperature sensors of the IGBTs (phase W).

Cause:


Overtemperature measured at phase W IGBT module.



Remedy:


Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature.
F065 & F066

Encoder Signal Fault (SW)

Feedback obtained via encoder does not match the commanded speed.

Cause:



  • Wiring between encoder and encoder interface accessory module is interrupted.

  • Encoder is defective.

  • Encoder coupling to the motor is broken.

  • Inverter operating in current limit (if the application needs to run in such conditions, this fault should be disabled).





Remedy:


Check connections and cables between encoder and encoder accessory module. Check encoder shaft coupling.

  • This fault can be disabled via parameter P0358.


F067

Incorrect Encoder/Motor Wiring

Fault related to the phase relation of the encoder signals, if P0202 = 4 and P0408 = 0, 2, 3 or 4.

Cause:



  • Output motor cables U, V, W are inverted.

  • Encoder channels A and B are inverted.

  • Encoder was not properly mounted.

  • Motor with locked rotor or dragging at the start.





Remedy:


Check the motor output cables connection sequence (U, V, W) and the encoder channel connections (A and B). Check encoder mechanical mounting. Check if rotor is mechanically locked.

  • If P0408 > 1: Fault cannot be reset. Turn off power supply, solve the problem, and power back on.

  • If P0408 = 0: Fault can be reset. This fault can be disabled via parameter P0358.


F070

Overcurrent / Short-circuit

Overcurrent or short-circuit detected at the output, in the DC bus, or at the braking resistor.

Cause:



  • Short-circuit between two motor phases.

  • Short-circuit between the connection cables of the dynamic braking resistor.

  • IGBT modules are shorted.





Remedy:


Verify motor winding insulation and check cabling for phase-to-phase short-circuits. Check resistor connection cables. Check power module (IGBT) status.
F071

Output Overcurrent

The inverter output current was too high for too long.

Cause:



  • Excessive load inertia or acceleration time too short.

  • Settings of parameters P0135, P0169, and P0170 are configured too high.





Remedy:


Increase acceleration time or reduce load inertia. Analyze and lower settings in P0135, P0169, and P0170.
F072

Motor Overload

The motor overload protection operated.

Cause:



  • Settings of parameters P0156, P0157, and P0158 are configured too low for the connected motor.

  • Motor shaft load is excessive.





Remedy:


Verify motor nominal currents. Check settings of parameters P0156, P0157, and P0158. Check for mechanical load blocks.

  • This protection can be disabled by setting parameter P0348 = 0 or 3.


F074

Ground Fault

A ground fault occurred either in the cable between the inverter and the motor or in the motor itself.

Cause:



  • Shorted wiring in one or more of the output phases.

  • Motor cable capacitance is too large, resulting in current peaks at the output.





Remedy:


Verify insulation of motor cables and motor winding. If cable capacitance is high, reduce cable length or add an output reactor.

  • This fault can be disabled by setting parameter P0343 = 0.


F076

Motor Current Imbalance

Fault of motor current unbalance.

Cause:



  • Loose connection or broken wiring between the motor and inverter connection.

  • Vector control with wrong orientation.

  • Vector control with encoder: encoder wiring or encoder motor connection is inverted.





Remedy:


Check all power connections between inverter output and motor terminal box. Verify vector control orientation parameters. Check encoder cabling and orientation phase.

  • This fault can be disabled by setting parameter P0342 = 0.


F077

DB Resistor Overload

The dynamic braking resistor overload protection operated.

Cause:



  • Excessive load inertia or deceleration/braking time is too short.

  • Motor shaft load is excessive.

  • Wrong settings for parameters P0154 and P0155.





Remedy:


Increase deceleration time or reduce dynamic braking usage. Verify and correct parameters P0154 and P0155.
F078

Motor Overtemperature

Fault related to the PTC temperature sensor installed in the motor.

Cause:



  • Excessive load at the motor shaft.

  • Excessive duty cycle (too many starts / stops per minute).

  • High ambient temperature around the motor.

  • Loose connection or short-circuit (resistance < 100 Ω) in the wiring connected to the motor thermistor.

  • Motor thermistor is not installed.

  • Blocked motor shaft.





Remedy:


Check the mechanical load on the motor shaft and resolve any blockages. Reduce high start/stop duty cycles if possible. Measure thermistor wire resistance to ensure it is > 100 Ω. Verify proper installation and wiring.

  • It is required to set the analog input / output to the PTC function.

  • This fault can be disabled by setting parameter P0351 = 0 or 3.


F079

Encoder Signal Fault

Lack of encoder signals.

Cause:



  • Broken wiring between the encoder interface.

  • Defective encoder.

  • Encoder accessory is defective or not well installed on the product, and control is configured for vector with encoder.





Remedy:


Check cable connections and wiring pathways between encoder and interface board for open connections. Replace defective encoders. Re-install the encoder accessory board if fitment is loose.

  • This fault can be disabled via the DIP switches of the ENC1 or ENC2 board.


F080

CPU Watchdog

Microcontroller watchdog fault.

Cause:



  • High electrical noise/EMI.





Remedy:


Inspect grounding line connections and shield pathways. Keep signal cables isolated from high-current power cables.
F082

Copy Function Fault

Fault while copying parameters.

Cause:



  • Communication problem with the HMI.





Remedy:


Check the connection cable between the HMI and the control unit. Avoid performing copy operations in high-noise environments.
F084

Auto-diagnosis Fault

Auto-diagnosis fault.

Cause:



  • Internal hardware check failure.





Remedy:


Please contact WEG technical support.
A088

Communication Lost

Indicates a problem between the keypad and control board communication.

Cause:



  • Loose keypad cable connection.

  • Electrical noise in the installation.





Remedy:


Secure the keypad cable terminal connections on both ends. Ensure cables are routed away from power lines.
A090

External Alarm

External alarm via digital input.

Cause:



  • Wiring was not connected to the digital input (DI1 to DI8) set to "No external alarm".





Remedy:


Ensure a digital input is configured for the "No external alarm" logic. Check the external terminal strip wiring loop.
F091

External Fault

External fault via digital input.

Cause:



  • Wiring was not connected to the digital input (DI1 to DI8) set to "No external fault".





Remedy:


Check terminal block loops for open circuits on the digital inputs. Verify that the assigned digital input is closed/high under normal conditions.
F099

Invalid Current Offset

Current measurement circuit is measuring a wrong value for null current.

Cause:



  • Defect in the inverter internal circuitry.





Remedy:


This typically indicates hardware damage. Replace the power module or contact technical service.
A110

High Motor Temperature

Alarm related to the PTC temperature sensor installed in the motor.

Cause:



  • Excessive load at the motor shaft.

  • Excessive duty cycle (too many starts / stops per minute).

  • Surrounding air temperature too high.

  • Loose connection or short-circuit (resistance < 100 Ω) in the wiring connected to the motor thermistor.

  • Motor thermistor is not installed.

  • Blocked motor shaft.





Remedy:


Verify the mechanical motor load and operating conditions. Measure the thermistor circuit to check for high-resistance anomalies.

  • It is required to set the analog input / output to the PTC function.

  • This alarm can be disabled by setting parameter P0351 = 0 or 2.


A128

Timeout for Serial Communication

Indicates that the inverter stopped receiving valid messages within a certain time interval.

Cause:



  • Check the wiring and grounding installation.

  • The inverter has not received any new message within the time interval set at P0314.





Remedy:


Inspect the serial communication cable routing, shield grounding, and terminal blocks. Ensure the host controller is actively polling the drive within the specified timeout.

  • This alarm can be disabled by setting parameter P0314 = 0.0 s.


A129

Anybus is Offline

Alarm that indicates interruption of the Anybus-CC communication.

Cause:



  • PLC entered into the idle state.

  • Programming error. Master and slave set with a different number of I/O words.

  • Communication with master has been lost (broken cable, unplugged connector, etc.).





Remedy:


Put the PLC master back into RUN mode. Verify I/O word configuration parameters. Check physical communication cable paths and connectors.
A130

Anybus Access Error

Alarm that indicates an access error to the Anybus-CC communication module.

Cause:



  • Defective, unrecognized, or improperly installed Anybus-CC module.

  • Conflict with a WEG option board.





Remedy:


Ensure the Anybus module is firmly and correctly seated in its slot. Verify there are no address or hardware resource conflicts with other active option cards.
A133

CAN Not Powered

Alarm indicating that the power supply was not connected to the CAN controller.

Cause:



  • Broken or loose cable.

  • Power supply is off.





Remedy:


Check the external 24 Vdc supply to the CAN interface terminals. Verify connections on the CAN cabling.
A134

Bus Off

Inverter CAN interface has entered into the bus-off state.

Cause:



  • Incorrect communication baud-rate.

  • Two nodes configured with the same address in the network.

  • Wrong cable connection (inverted signals).





Remedy:


Align CAN network baud-rates. Change node addresses to ensure all are unique. Check high and low polarity on the CAN wiring bus.
A135

CANopen Communication Error

Alarm that indicates a communication error.

Cause:



  • General communication problems.

  • Wrong master configuration/settings.

  • Incorrect configuration of the communication objects.





Remedy:


Verify master system settings and check mapping parameters of PDO and SDO communication objects.
A136

Idle Master

Network master has entered into the idle state.

Cause:



  • PLC is in IDLE mode.

  • Bit of the PLC command register is set to zero (0).





Remedy:


Set the PLC status back to EXECUTION/RUN. Check PLC logic bits.
A137

DNet Connection Timeout

I/O connection timeout - DeviceNet communication alarm.

Cause:



  • One or more allocated I/O connections have entered into the timeout state.





Remedy:


Verify DeviceNet master and slave polling states. Check for line breaks on the physical bus.
A138

Profibus DP Interface in Clear Mode

It indicates that the inverter received a command from the Profibus DP network master to enter the clear mode.

Cause:



  • The network master status is not in run mode.





Remedy:


Verify the network master status, making sure it is in execution mode (Run). Refer to the Profibus DP communication manual for more information.
A139

Offline Profibus DP Interface

It indicates an interruption in the communication between the Profibus DP network master and the inverter.

Cause:



  • The network master is not configured or operating normally.

  • Profibus DP network cable routing or grounding is inadequate.





Remedy:


Check the PLC state. Check general cable routing, connection shield lines, and grounding terminals. Refer to the Profibus DP communication manual.
A140

Profibus DP Module Access Error

It indicates an error in the access to the Profibus DP communication module data.

Cause:



  • The Profibus DP module is not seated properly in the slot.





Remedy:


Verify whether the Profibus DP module is correctly fit into Slot 3. Refer to the Profibus DP communication manual.
F150

Motor Overspeed

Overspeed fault. It is activated when the real speed exceeds the value of P0134 x (100 % + P0132) for more than 20 ms.

Cause:



  • Wrong settings of parameters P0161 and/or P0162.

  • Problem with hoist-type loads (mechanical drag).





Remedy:


Adjust overspeed limit parameters P0161 and P0162. For lifting or hoist applications, verify brake coordination and torque limits.
F151

FLASH Memory Module Fault

FLASH Memory Module fault (MMF-03).

Cause:



  • Defective FLASH memory module.

  • Incorrect or loose physical connection of the FLASH memory module.





Remedy:


Verify the physical slot connection of the FLASH memory card. Replace the memory module if card is damaged.
A152

Internal Air High Temperature

Alarm indicating that the internal air temperature is too high.

Cause:



  • Surrounding air temperature is too high and excessive output current.

  • Defective internal cooling fan (if installed).

  • For CFW-11M and frame sizes E, F, G: High temperature (> 45 ºC) inside the cabinet.





Remedy:


Ensure enclosure or cabinet ventilation fan is operating correctly. Clear blockages from airflow grilles.

  • This alarm can be disabled by setting parameter P0353 = 1 or 3.


F153

Internal Air Overtemperature

Internal air overtemperature fault.

Cause:


Critical overtemperature detected in internal air pathways.



Remedy:


Shut down the inverter and check enclosure ventilation. Verify cooling fan function.
A155

Undertemperature

Only 1 sensor indicates temperature below -30 ºC.

Cause:



  • Surrounding air temperature ≤ -30 °C (-22 °F).





Remedy:


Verify ambient working temperature. Provide workspace heating if operating in extreme cold.
F156

Undertemperature

Undertemperature fault (below -30 °C (-22 °F)) in the IGBTs or rectifier measured by the temperature sensors.

Cause:



  • Surrounding air temperature ≤ -30 °C (-22 °F).





Remedy:


Check the installation environment. Provide heating element control inside the cabinet for operation in cold environments.
F160

Safety Stop Relays

Safety Stop relay fault.

Cause:



  • Only +24 Vdc was applied to a single STO input (STO1 or STO2).

  • One of the safety relays is defective.





Remedy:


Ensure dual channel wiring is balanced. Apply +24 Vdc to both STO inputs. Replace safety module if relays are physically defective.
F161

Timeout PLC11CFW-11

Cause:


PLC accessory board communication timeout.



Remedy:


Refer to the PLC11-01 Module programming manual.
A162

Incompatible PLC Firmware

Cause:


Firmware mismatch between control board and installed PLC card.



Remedy:


Update control board or PLC card firmware to compatible versions.
A163

Break Detect AI1

It indicates that the AI1 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range.

Cause:



  • Broken AI1 current loop cable.

  • Bad contact at the signal connection to the terminal strip.





Remedy:


Inspect analogue input 1 loop cabling for breaks. Tighten screw terminal contacts.
A164

Break Detect AI2

It indicates that the AI2 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range.

Cause:



  • Broken AI2 current loop cable.

  • Bad contact at the signal connection to the terminal strip.





Remedy:


Inspect analogue input 2 loop cabling for breaks. Tighten screw terminal contacts.
A165

Break Detect AI3

It indicates that the AI3 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range.

Cause:



  • Broken AI3 current loop cable.

  • Bad contact at the signal connection to the terminal strip.





Remedy:


Inspect analogue input 3 loop cabling for breaks. Tighten screw terminal contacts.
A166

Break Detect AI4

It indicates that the AI4 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range.

Cause:



  • Broken AI4 current loop cable.

  • Bad contact at the signal connection to the terminal strip.





Remedy:


Inspect analogue input 4 loop cabling for breaks. Tighten screw terminal contacts.
F174, F175, F176

Fan Speed Fault (Left / Center / Right)

Heatsink fan speed faults.

Cause:



  • Dirt on the fan blades and in the bearings.

  • Defective fan hardware.

  • Defective fan power supply line connection.





Remedy:


Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective.
A177

Fan Replacement

Fan replacement alarm (P0045 > 50000 hours).

Cause:


The operating hours of the heatsink fan have exceeded 50,000 hours.



Remedy:


Perform preventive fan replacement maintenance.

  • This alarm can be disabled by setting parameter P0354 = 0.


F178

Heatsink Fan Speed Alarm

This alarm indicates a speed/operating problem with the heatsink fan.

Cause:



  • Dirt on the blades and in the bearings of the fan.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Clear any build-up on fan blades and check bearing rotation. Ensure power line connectors are secure.
F179

Heatsink Fan Speed Fault

This fault indicates a speed/operating problem with the heatsink fan.

Cause:



  • Dirt on the blades and in the bearings of the fan.

  • Defective fan.

  • Defective fan power supply connection.





Remedy:


Check and clean the fan module. Replace if damaged.

  • This monitoring function can be disabled by setting parameter P0354 = 0.


A181

Invalid Clock Value

Invalid clock value alarm.

Cause:



  • Keypad real-time clock battery is discharged, defective, or not installed.





Remedy:


Set the correct date and time at parameters P0194 to P0199. Replace the internal keypad battery if dead.
F182

Pulse Feedback Fault

Indicates a fault on the output pulses feedback.

Cause:



  • No motor is connected, or the motor connected to the inverter output is too small.

  • Possible defect on the internal feedback circuits of the inverter.





Remedy:


Verify if a motor is connected. Check if motor rating matches the drive capacity. Reset the inverter and try again.

  • Alternatively, set parameter P0356 = 0 and try again.


F183

IGBT Overload + Temperature

Overtemperature related to the IGBTs overload protection.

Cause:



  • Surrounding air temperature is too high.

  • Operation with output frequencies < 10 Hz under overload conditions.





Remedy:


Verify ambient cooling path functionality. Avoid running the drive continuously below 10 Hz during high overload conditions.
F185

Pre-charge Contac Fault

It indicates a fault at the pre-charge contactor.

Cause:



  • Pre-charge contactor defect.

  • Open command fuse.

  • Phase loss in the input L1/R or L2/S.

  • Incorrect parameter setting for Frame Size E models supplied by the DC link (parameter P0355 is set to 1).





Remedy:


Inspect pre-charge contactor mechanism and verify internal command fuses. Check main incoming line terminals for input phase drops at L1/R or L2/S.

  • For models Frame E supplied directly by the DC link, verify parameter P0355 is set to 0.


F186 to F190

Sensor 1 to 5 Temperature Fault

It indicates a temperature fault at the temperature sensors (1, 2, 3, 4, or 5).

Cause:



  • Motor high temperature.





Remedy:


Check the motor loading condition to prevent thermal overload. Verify cooling fan performance, airflow paths, and motor installation layout.
A191 to A195

Sensor 1 to 5 Temperature Alarm

It indicates a temperature alarm at the temperature sensors (1, 2, 3, 4, or 5).

Cause:



  • Motor high temperature.

  • A problem in the wiring connecting the sensor to the IOE 01, IOE 02, or IOE 03 module.





Remedy:


Verify motor current and cooling efficiency. Check the sensor cabling connections to the IOE module ports.
A196 to A200

Sensor 1 to 5 Cable Alarm

Sensor cable alarm (Sensor 1, 2, 3, 4, or 5).

Cause:



  • Shorted temperature sensor.





Remedy:


Check the temperature sensor cables and terminals for a short circuit. Replace damaged cables or defective sensor assemblies.
F228

Serial Communication Timeout

Serial communication interface timeout.

Cause:



  • Timeout in RS-232 / RS-485 serial communication.





Remedy:


Verify connection leads, shielding, and termination resistors. Check the serial transmission settings on the master controller.

  • Refer to the RS-232 / RS-485 Serial communication manual for details.


F229 & F230

Anybus Offline / Access Error

Anybus offline alarm or module access error.

Cause:



  • Anybus-CC interface module offline state or access fault.





Remedy:


Verify that the module is correctly mounted and seated in its slot. Check communication status.

  • Refer to the Anybus-CC communication manual for details.


F233 & F234

CAN Bus Power Failure / Bus Off

CAN interface fault.

Cause:



  • CAN bus power supply failure or interface bus-off.





Remedy:


Ensure auxiliary power supply to the CAN controller terminals is within parameters. Verify bus routing and node termination.

  • Refer to the CANopen communication manual and/or DeviceNet communication manual.


F235

CANopen Communication Error

CANopen communication error alarm.

Cause:



  • Baud-rate settings mismatched or message frames lost.





Remedy:


Verify CANopen configuration parameter settings and communication objects.

  • Refer to the CANopen communication manual for details.


F236 & F237

Master Idle / DeviceNet Timeout

Network master idle or DeviceNet connection timeout.

Cause:



  • PLC or scanner in idle mode, or DeviceNet timed out.





Remedy:


Verify scanner state is set to Run. Check physical network trunks for cable breaks.

  • Refer to the DeviceNet communication manual for details.


F238, F239, F240

Profibus DP Clear Mode / Offline / Access Error

Profibus communication exceptions.

Cause:



  • Profibus DP network offline, master in clear mode, or module access error.





Remedy:


Check the status of the Profibus DP network master. Ensure card fitment inside the controller is secure.

  • Refer to the Profibus DP communication manual for details.


A300 / F301

High Temp / Overtemp IGBT U B1

High temperature alarm / overtemperature fault at book 1 U phase IGBT NTC sensor.

Cause:



  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model.



Remedy:


Reduce surrounding ambient temperature or output load. Clean the heatsink fins of book 1. Inspect and replace the cooling fan if defective.
A303 / F304

High Temp / Overtemp IGBT V B1

High temperature alarm / overtemperature fault at book 1 V phase IGBT NTC sensor.

Cause:



  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model.



Remedy:


Reduce surrounding ambient temperature or output load. Clean the heatsink fins of book 1. Inspect and replace the cooling fan if defective.
A306 / F307

High Temp / Overtemp IGBT W B1

High temperature alarm / overtemperature fault at book 1 W phase IGBT NTC sensor.

Cause:



  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model.



Remedy:


Reduce surrounding ambient temperature or output load. Clean the heatsink fins of book 1. Inspect and replace the cooling fan if defective.
A309 / F310

High Temp / Overtemp IGBT U B2

High temperature alarm / overtemperature fault at book 2 U phase IGBT NTC sensor.

Cause:



  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model.



Remedy:


Reduce surrounding ambient temperature or output load. Clean the heatsink fins of book 2. Inspect and replace the cooling fan if defective.
A312 / F313

High Temp / Overtemp IGBT V B2

High temperature alarm / overtemperature fault at book 2 V phase IGBT NTC sensor.

Cause:



  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model.



Remedy:


Reduce surrounding ambient temperature or output load. Clean the heatsink fins of book 2. Inspect and replace the cooling fan if defective.
A315 / F316

High Temp / Overtemp IGBT W B2

High temperature alarm / overtemperature fault at book 2 W phase IGBT NTC sensor.

Cause:



  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model.



Remedy:


Reduce surrounding ambient temperature or output load. Clean the heatsink fins of book 2. Inspect and replace the cooling fan if defective.
A318 / F319

High Temp / Overtemp IGBT U B3

High temperature alarm / overtemperature fault at book 3 U phase IGBT NTC sensor.

Cause:



  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model.



Remedy:


Reduce surrounding ambient temperature or output load. Clean the heatsink fins of book 3. Inspect and replace the cooling fan if defective.
A321

High Temp IGBT V B3

High temperature alarm measured with the temperature sensor (NTC) of the book 3 V phase IGBT.

Cause:



  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model.



Remedy:


Reduce surrounding ambient temperature or output load. Clean the heatsink fins of book 3. Inspect and replace the cooling fan if defective.
F322 (10) / A324 (10) / F325 (10)

Book 3 V & W Phase High Temp / Overtemp

Cause:


High temperature alarm / overtemperature fault measured at the NTC temperature sensor of the Book 3 (V or W phase) IGBT.

  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model. Refer to section 3.1 - Installation Environment of the CFW-11M user's manual.



Remedy:


Reduce surrounding ambient temperature or drive output current. Clean the dirty heatsink fins on the respective Book 3 module. Inspect and replace any defective cooling fans.
A327 (10) / F328 (10) / A330 (10) / F331 (10) / A333 (10) / F334 (10)

Book 4 High Temp / Overtemp (U, V, W Phases)

Cause:


High temperature alarm / overtemperature fault measured at the NTC temperature sensor of the Book 4 (U, V, or W phase) IGBT.

  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model. Refer to section 3.1 - Installation Environment of the CFW-11M user's manual.



Remedy:


Check operating conditions. Reduce ambient operating temperature or lower the output current. Clean heatsink fins on the Book 4 assembly. Verify functional operation of the cooling fans.
A336 (10) / F337 (10) / A339 (10) / F340 (10) / A342 (10) / F343 (10)

Book 5 High Temp / Overtemp (U, V, W Phases)

Cause:


High temperature alarm / overtemperature fault measured at the NTC temperature sensor of the Book 5 (U, V, or W phase) IGBT.

  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model. Refer to section 3.1 - Installation Environment of the CFW-11M user's manual.



Remedy:


Inspect ventilation pathways. Reduce ambient temperature or active output current. Clean the dirty heatsink fins on the Book 5 module. Replace defective cooling fans.
A345 (10) / F346 (10) / A348 (10) / F349 (10) / A351 (10) / F352 (10)

Book 1 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 1 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).





Remedy:


Analyze motor operating conditions. Verify motor loading and adjust duty cycles or check mechanical obstructions on the shaft. Ensure output wiring conforms to the layout guidelines of figure 8.1.
A354 (10) / F355 (10) / A357 (10) / F358 (10) / A360 (10) / F361 (10)

Book 2 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 2 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).





Remedy:


Verify motor load requirements. Check for mechanical blocks or high-friction conditions. Verify physical layout of output wiring according to figure 8.1.
A363 (10) / F364 (10) / A366 (10) / F367 (10) / A369 (10) / F370 (10)

Book 3 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 3 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).





Remedy:


Inspect motor load demand. Lower output current levels where possible. Check and align system connections to comply with figure 8.1 parameters.
A372 (10) / F373 (10) / A375 (10) / F376 (10) / A378 (10) / F379 (10)

Book 4 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 4 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).





Remedy:


Assess operating loads. Ensure system sizing parameters match current demands. Inspect output connections in accordance with manual guidelines.
A381 (10) / F382 (10) / A384 (10) / F385 (10) / A387 (10) / F388 (10)

Book 5 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 5 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).




Note: Temperature > 40 ºC or 45 ºC depending on the model; refer to section 3.1 - Installation Environment of the CFW-11M user's manual.



Remedy:


Review application demands and current limits. Check for mechanical drag. Align connection structures with the schematic requirements shown in figure 8.1.
A390 (10)

Current Unbalance at Phase U B1

Cause:


Phase U Book 1 current unbalance alarm. It indicates a 20 % unbalance in the current distribution between this phase and the smallest current of the same phase in another book, only when the current in this phase is higher than 75 % of its nominal value.

  • Poor electrical connection between the DC bus and the power unit.

  • Poor electrical connection between the power unit output and the motor.





Remedy:


Verify the physical and electrical integrity of the connections between the DC bus and the power unit. Check the output cable terminal connections to the motor for loose or high-resistance paths.



Note: During fast acceleration or braking, this alarm may be indicated momentarily, disappearing after 3 seconds. This is not an indication of any anomaly in the inverter. If the alarm persists when the motor is operating at a constant speed, it is an indication of an anomaly in the current distribution among the power units.
F322 (10) / A324 (10) / F325 (10)

Book 3 V & W Phase High Temp / Overtemp

Cause:


High temperature alarm / overtemperature fault measured at the NTC temperature sensor of the Book 3 (V or W phase) IGBT.

  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model. Refer to section 3.1 - Installation Environment of the CFW-11M user's manual.



Remedy:


Reduce surrounding ambient temperature or drive output current. Clean the dirty heatsink fins on the respective Book 3 module. Inspect and replace any defective cooling fans.
A327 (10) / F328 (10) / A330 (10) / F331 (10) / A333 (10) / F334 (10)

Book 4 High Temp / Overtemp (U, V, W Phases)

Cause:


High temperature alarm / overtemperature fault measured at the NTC temperature sensor of the Book 4 (U, V, or W phase) IGBT.

  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model. Refer to section 3.1 - Installation Environment of the CFW-11M user's manual.



Remedy:


Check operating conditions. Reduce ambient operating temperature or lower the output current. Clean heatsink fins on the Book 4 assembly. Verify functional operation of the cooling fans.
A336 (10) / F337 (10) / A339 (10) / F340 (10) / A342 (10) / F343 (10)

Book 5 High Temp / Overtemp (U, V, W Phases)

Cause:


High temperature alarm / overtemperature fault measured at the NTC temperature sensor of the Book 5 (U, V, or W phase) IGBT.

  • High ambient temperature (*) and high output current.

  • Blocked or defective cooling fan.

  • Fins of the book heatsink too dirty, impairing the airflow.




(*) Note: Temperature > 40 ºC or 45 ºC, depending on the model. Refer to section 3.1 - Installation Environment of the CFW-11M user's manual.



Remedy:


Inspect ventilation pathways. Reduce ambient temperature or active output current. Clean the dirty heatsink fins on the Book 5 module. Replace defective cooling fans.
A345 (10) / F346 (10) / A348 (10) / F349 (10) / A351 (10) / F352 (10)

Book 1 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 1 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).





Remedy:


Analyze motor operating conditions. Verify motor loading and adjust duty cycles or check mechanical obstructions on the shaft. Ensure output wiring conforms to the layout guidelines of figure 8.1.
A354 (10) / F355 (10) / A357 (10) / F358 (10) / A360 (10) / F361 (10)

Book 2 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 2 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).





Remedy:


Verify motor load requirements. Check for mechanical blocks or high-friction conditions. Verify physical layout of output wiring according to figure 8.1.
A363 (10) / F364 (10) / A366 (10) / F367 (10) / A369 (10) / F370 (10)

Book 3 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 3 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).





Remedy:


Inspect motor load demand. Lower output current levels where possible. Check and align system connections to comply with figure 8.1 parameters.
A372 (10) / F373 (10) / A375 (10) / F376 (10) / A378 (10) / F379 (10)

Book 4 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 4 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).





Remedy:


Assess operating loads. Ensure system sizing parameters match current demands. Inspect output connections in accordance with manual guidelines.
A381 (10) / F382 (10) / A384 (10) / F385 (10) / A387 (10) / F388 (10)

Book 5 High Load / Overload (U, V, W Phases)

Cause:


Overload alarm / overload fault at Book 5 (U, V, or W phase) IGBT.

  • High current at the inverter output (refer to figure 8.1 of the CFW-11M user's manual).




Note: Temperature > 40 ºC or 45 ºC depending on the model; refer to section 3.1 - Installation Environment of the CFW-11M user's manual.



Remedy:


Review application demands and current limits. Check for mechanical drag. Align connection structures with the schematic requirements shown in figure 8.1.
A390 (10)

Current Unbalance at Phase U B1

Cause:


Phase U Book 1 current unbalance alarm. It indicates a 20 % unbalance in the current distribution between this phase and the smallest current of the same phase in other book, only when the current in this phase is higher than 75 % of its nominal value.

  • Poor electrical connection between the DC bus and the power unit.

  • Poor electrical connection between the power unit output and the motor.





Remedy:


Verify the physical and electrical integrity of the connections between the DC bus and the power unit. Check the output cable terminal connections to the motor for loose or high-resistance paths.



Note: During fast acceleration or braking, this alarm may be indicated momentarily, disappearing after 3 seconds. This is not an indication of any anomaly in the inverter. If the alarm persists when the motor is operating at a constant speed, it is an indication of an anomaly in the current distribution among the power units.

How to Clear & Reset WEG CFW-11 Drive Faults

  1. Keypad Reset: Press the red “O / STOP / RESET” key on the detachable graphic HMI keypad. If the drive is operating under remote control (REM), toggle to local control (LOC) using the LOC/REM key before executing a manual reset.
  2. Digital Input Reset (DI): If programmed via parameters P0263 to P0270 (DI1 to DI8 function) with option 20 (Reset), apply a 24V pulse to the assigned digital input terminal on the control board.
  3. SuperDrive G2 PC Software: Connect a PC using the standard built-in mini-USB port on the front module, launch WEG SuperDrive G2 or WLP, and trigger the “Fault Reset” command within the drive status screen.
  4. Fieldbus Control Word: Transition Bit 7 (Fault Reset) from `0` to `1` in the Control Word (parameter P0680 / P0682) across serial Modbus-RTU, Profibus-DP, DeviceNet, or CANopen communication links.
  5. Power Cycle: Disconnect the incoming 3-phase AC mains supply, wait at least 10 minutes until the HMI backlight turns completely off and intermediate capacitors discharge, then re-energize the unit.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect the main supply power and wait at least 10 minutes for internal capacitors to fully discharge. Verify with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+UD] and [-UD] (or dynamic braking terminal [BR]) before opening covers or inspecting motor output terminals U, V, and W on the WEG CFW-11 drive.