WEG CFW100 G2 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW100 Generation 2 (G2) micro variable frequency drive series. Search or filter through the complete fault code directory below.
Power Range
0.18 – 1.5 kW (0.25 – 2.0 HP)
Supply Voltage
100–127V / 200–240V AC (1-Phase)
Control Modes
Scalar (V/F) & Vector (VVW)
Operator Interface
Integrated 4-Key HMI Keypad
Complete WEG CFW100 G2 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type F0006, F0021, or Overcurrent).
| Fault / Alarm and Meaning | Cause and Remedy |
|---|---|
| A046 Motor Overload Motor overload alarm. | Cause:
Remedy: Verify if the overload protection parameter P156 matches the connected motor's ratings. Inspect the motor shaft and driven machinery for mechanical loads or blockages. |
| A050 Power Module Overtemperature Overtemperature alarm from the power module temperature sensor (NTC). | Cause:
Remedy: Check the active operating temperature via parameter P030. Ensure surrounding cabinet ventilation is sufficient. Inspect and clean any dust or blockages from the heatsink fins. Verify the operation of the cooling fan. |
| A090 External Alarm External alarm via DIx (option “No External Alarm” in P26x). | Cause:
Remedy: Inspect connection terminals for digital inputs DI1 through DI4. Tighten any loose screws and ensure clean wire contact on the terminal strip. |
| A128 Telegram Reception Timeout Alarm indicating a serial communication fault. It indicates the equipment stopped receiving valid serial telegrams for a period longer than the setting in P314. | Cause:
Remedy: Check communication cable paths, shield grounding, and terminal blocks. Ensure the polling rate of the master controller is faster than the timeout set in P314.
|
| A133 No power supply on the CAN interface It indicates that the CAN interface has no power supply between pins 1 and 5 of the connector. | Cause:
Remedy: Measure the voltage on the CAN interface connector to verify it falls within the permitted range between pins 1 and 5. Ensure external power lines are secure and correctly polarized. |
| A134 Bus Off Buss off error detected on the CAN interface. | Cause:
Remedy: Check CAN high and low wires for short circuits or inverted lines. Verify that all nodes on the network are configured with the same communication baud rate. Check termination resistor values and placement. |
| A135 Node Guarding / Heartbeat CANopen communication error control detected a communication error using the guarding mechanism. | Cause:
Remedy: Check the times set on both the master and slave nodes. To prevent delay conflicts, configure the error detection time on the slave to be a multiple of the master's exchange interval. Verify the master's active polling state. |
| A163 Signal Fault AI1 Analogue input signal AI1 at 4 to 20 mA or 20 to 4 mA is below 4 mA. | Cause:
Remedy: Verify loop integrity for analog input 1. Inspect wiring pathways and ensure firm contact at the screw terminals. |
| A700 Remote HMI Communication Fault No communication with remote HMI, but there is an active frequency command or reference assigned to this source. | Cause:
Remedy: Check parameter P312 to verify that the HMI communication interface is configured correctly. Reconnect or replace the HMI serial cable. |
| A702 Inverter Disabled This failure occurs when there is an active SoftPLC movement block (REF block) while the "General Enable" command is disabled. | Cause:
Remedy: Check the drive control terminal states to ensure the General Enable input command is active. |
| A704 Two Movem. Enabled It occurs when 2 or more SoftPLC movement blocks (REF Block) are enabled at the same time. | Cause:
Remedy: Check the user’s SoftPLC program logic to ensure only one movement block is active at any given time. |
| A706 Refer. Nao Progr. SPLC This failure occurs when a SoftPLC movement block is enabled but the speed reference has not been programmed for the SoftPLC. | Cause:
Remedy: Check and verify the speed reference configuration in parameters P221 and P222 (Local and Remote modes). |
| A712 SPLC protected against copy It occurs when there is an attempt to copy a copy-protected SoftPLC application. | Cause:
Remedy: Verify the copyright and permission settings of the WLP application you are trying to manage. |
| F021 Undervoltage on the DC Link Undervoltage fault on the intermediate circuit. | Cause:
Remedy: Ensure the supply voltage matches the specifications listed on the inverter's rating label and is correctly set in parameter P296. Check the line phases for any missing connections or drops. Verify pre-charge circuit components are functional. |
| F022 Overvoltage on the DC Link Overvoltage fault on the intermediate circuit. | Cause:
Remedy: Verify incoming mains power supply match to rating parameters. Adjust deceleration ramp to be slower, or reduce parameter P151 setting. If necessary, consider dynamic braking options. |
| F033 VVW Self-tuning Fault Stator resistance setting fault P409. | Cause:
Remedy: Turn off the power supply and inspect all connections at the motor terminal box. Verify if the stator resistance parameter P409 and motor power parameters are correctly scaled. |
| F051 IGBTs Overtemperatures Overtemperature fault measured on the temperature sensor of the power pack. | Cause:
Remedy: Check the current temperature in parameter P030. Improve airflow around the drive or lower ambient room temperature. Clear any dust or debris build-up from the heatsink fins. Verify fan operation. |
| F070 Overcurrent/Shortcircuit Overcurrent or short-circuit on the output, DC link, or braking resistor. | Cause:
Remedy: Verify motor winding and connection cables for phase-to-phase shorts. Increase the acceleration ramp time. Enable the Flying Start function if the motor is prone to rotating during startup. |
| F072 Motor Overload Motor overload fault (60 s in 1.5xInom). | Cause:
Remedy: Check and adjust the motor nominal current value in parameter P156. Check the motor shaft and driven load for mechanical blockages or excessive friction. |
| F080 CPU Fault (Watchdog) Fault related to the supervision algorithm of the inverter main CPU. | Cause:
Remedy: Inspect the installation grounding and shield connections to mitigate electrical noise. Update the control unit firmware if the issue is recurring. |
| F081 Fault on the Save User function Fault in the attempt to save the User parameter table. | Cause:
Remedy: Limit custom user parameters with non-default values to 32 items or less. Check parameter block settings. |
| F082 Fault in the Copy Function (MMF) Fault in the copy of parameters. | Cause:
Remedy: Ensure software and firmware version compatibility between the Flash Memory Module and the target drive control unit. |
| F084 Auto-diagnosis Fault Fault related to the automatic identification algorithm of the inverter hardware. | Cause:
Remedy: Check the connection and alignment of the boards inside the drive. Ensure firmware compatibility. Contact technical support if an internal hardware defect is suspected. |
| F091 External Fault External fault via DIx (“No External Fault” in P26x). | Cause:
Remedy: Verify external cabling loops to the assigned digital inputs. Tighten loose screw terminals and check contact switches. |
| F228 Timeout in receipt of telegrams Indicates a fault in the serial communication. The equipment stopped receiving valid serial telegrams for a period longer than the setting in P314. | Cause:
Remedy: Check communication cable paths, shield grounding, and terminal blocks. Ensure the polling rate of the master controller is faster than the timeout set in P314.
|
| F233 No power supply on the CAN interface It indicates that the CAN interface has no power supply between pins 1 and 5 of the connector. | Cause:
Remedy: Measure the voltage on the CAN interface connector to verify it falls within the permitted range between pins 1 and 5. Ensure external power lines are secure and correctly polarized. |
| F234 Bus Off Buss off error detected on the CAN interface. | Cause:
Remedy: Check CAN high and low wires for short circuits or inverted lines. Verify that all nodes on the network are configured with the same communication baud rate. Check termination resistor values and placement. |
| F235 Node Guarding / Heartbeat CANopen communication error control detected a communication error using the guarding mechanism. | Cause:
Remedy: Check the times set on both the master and slave nodes. To prevent delay conflicts, configure the error detection time on the slave to be a multiple of the master's exchange interval. Verify the master's active polling state. |
| F701 Remote HMI communication fault No communication with the remote HMI; however, there is an active command or frequency reference assigned to this source. | Cause:
Remedy: Check parameter P312 to verify that the HMI communication interface is configured correctly. Reconnect or replace the HMI serial cable. |
| F710 SPLC Progr. bigger than 5 KB SoftPLC program memory size fault. | Cause:
Remedy: Verify the code size inside the user application logic. Optimize the SoftPLC program blocks to fit within the 5 KB memory capacity. |
| F711 The upload of the SoftPLC application failed The upload or the SoftPLC application failed. | Cause:
Remedy: Verify application configuration and compatibility. Check parameter settings for P900 and P901. Attempt a fresh upload. |
How to Clear & Reset WEG CFW100 G2 Drive Faults
- Keypad Reset: Press the red O (Stop / Reset) key on the integrated HMI keypad once to clear active fault conditions after eliminating the root trip cause.
- Digital Input Reset (DI): If programmed via parameter P0263 (DI1 selection) or P0264–P0266, pulse the dedicated digital input terminal configured to option 5 (Fault Reset).
- WPS PC Software: Connect your PC using the optional USB plug-in module (CFW100-CUSB), open WEG Programming Suite (WPS), and send a Fault Reset command through the monitoring interface.
- Fieldbus / Serial Command: Toggle Bit 7 (Fault Reset) from `0` to `1` in the Serial Control Word via Modbus RTU using the optional RS-485 plug-in module (CFW100-CRS485).
- Complete Power Cycle: Disconnect AC line power, wait until the HMI display extinguishes completely (minimum 3 to 5 minutes to permit internal capacitor discharge), and reapply main line voltage.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across internal power terminals before touching motor leads (U, V, W), servicing terminal wiring, or installing/removing plug-in option modules on the WEG CFW100 G2 drive.