WEG CFW900 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW900 high-performance variable speed drive series. Search or filter through the complete fault code directory below.
Power Range
1.1 – 630 kW (1.5 – 900 HP)
Supply Voltage
200–240V / 380–480V / 500–690V AC
Control Modes
V/f, VVW, Vector Induction & PM Motor
Operator Interface
Graphic HMI with Bluetooth® & WPS Mobile
Complete WEG CFW900 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type F006, F021, or Overcurrent).
| Fault / Alarm and Meaning | Cause and Remedy |
|---|---|
| F006 Grid Unbal./Phase Loss Unbalance or phase loss in the power supply. | Cause:
Note: In case the motor has no load on the shaft or the load is low, this fault may not occur. Actuation time is set to C7.1.1. When C7.1.1=0, the fault is disabled. Remedy: Check input grid voltage balance and secure connections on mains lines. Verify there are no open circuit fuses. If required, disable this check by setting parameter C7.1.1 = 0. |
| A010 Rectifier Overtemp. Alarm of high temperature measured in the temperature sensors (NTC) of the rectifier modules. | Cause:
Note: It can be disabled by changing the IGBT Overtemp. setting to fault only in parameter C7.5.1. Remedy: Clean any dust from heatsink fins. Verify fan operation and clear any blockages. Improve surrounding cabinet ventilation. Check settings in parameter C7.5.1. |
| F011 Rectifier Overtemp. Fault of overtemperature measured in the temperature sensors (NTC) of the rectifier modules. | Cause:
Remedy: Verify fan operation and clean heatsink fins. Improve room/enclosure ventilation as needed to reduce surrounding ambient temperature. |
| A018 Low Battery Voltage Low battery voltage alarm. | Cause:
Remedy: Perform maintenance to replace the internal battery. |
| A019 24Vdc Power Supply Overvoltage 24Vdc power supply overvoltage fault. | Cause:
Remedy: Check the external 24 Vdc supply to ensure it is configured within specifications and is not outputting voltage above 27.4 V. |
| A020 24Vdc Power Supply Undervoltage 24 Vdc power supply undervoltage fault. | Cause:
Remedy: Check the incoming 24 Vdc supply wiring and voltage levels. Ensure the external power source is rated correctly. |
| F021 DC Link Undervoltage DC link undervoltage fault. | Cause: Supply voltage is too low, producing voltage on the DC link (S2.7.1) below the minimum value:
Remedy: Verify incoming mains supply. Check input terminals and check for missing phases. Check the pre-charge circuit. Verify the configuration value of parameter C1.1.2. |
| F022 DC Link Overvoltage DC link overvoltage fault. | Cause: Supply voltage is too high, producing voltage on the DC link (S2.7.1) above the maximum permitted value:
Remedy: Check the incoming mains supply voltage. Increase deceleration ramp time, adjust load inertia, or reduce parameters C3.5.2.1, C3.5.3.2, or C3.6.1. |
| F025 Pulse Feedback Error Failure to compare the PWM pulses generated by the control and the output voltages measured by the inverter. | Cause:
Note: Reset the inverter and try again. Remedy: Check output motor cabling connections. Verify STO safety inputs circuit at terminal block XC2. Reset the drive. |
| F030 IGBT U Desat Fault of desaturation on the IGBTs of arm U. | Cause:
Remedy: Inspect output motor cables and motor terminal box for short circuits between phase U-V or U-W. If motor connections are correct, verify IGBT state. |
| F034 IGBT V Desat Fault of desaturation on the IGBTs of arm V. | Cause:
Remedy: Inspect output motor cables and motor terminal box for short circuits between phase V-U or V-W. If motor connections are correct, verify IGBT state. |
| F038 IGBT W Desat Fault of desaturation on the IGBTs of arm W. | Cause:
Remedy: Inspect output motor cables and motor terminal box for short circuits between phase W-U or W-V. If motor connections are correct, verify IGBT state. |
| F042 Brake IGBT Desat Fault of desaturation on the dynamic braking IGBT. | Cause:
Remedy: Check connection cables of the braking resistor for insulation wear or short circuits. Verify the resistance of the dynamic braking resistor. |
| A046 High Load on the Motor Motor overload alarm. | Cause:
Note: This alarm can be disabled by setting parameter C7.4.1 = 0 or 2. Remedy: Adjust motor overload protection parameters C7.4.3, C7.4.4, and C7.4.5 to match motor load specifications. Check for mechanical blocks on the motor shaft. |
| A047 High Load on the IGBTs IGBT overload alarm. | Cause:
Remedy: Check drive load status to lower active current peaks. Ensure motor sizing matches application limits. |
| F048 Overload on the IGBTs IGBT overload fault. | Cause:
Remedy: Reduce motor load or duty cycle to prevent high output current. Verify inverter dimensioning. |
| A050 IGBT1 U Overtemp. Alarm of high temperature measured in the temperature sensors (NTC) of the IGBTs. | Cause:
Note: It can be disabled by setting parameter C7.5.1. Remedy: Clean the heatsink. Check if the cooling fan is blocked or defective. Ensure surrounding ambient temperature is within limits. |
| A051 IGBT1 V Overtemp. Alarm of high temperature measured in the temperature sensors (NTC) of the IGBTs. | Cause:
Note: It can be disabled by setting parameter C7.5.1. Remedy: Clean the heatsink. Check if the cooling fan is blocked or defective. Ensure surrounding ambient temperature is within limits. |
| A052 IGBT1 W Overtemp. Alarm of high temperature measured in the temperature sensors (NTC) of the IGBTs. | Cause:
Note: It can be disabled by setting parameter C7.5.1. Remedy: Clean the heatsink. Check if the cooling fan is blocked or defective. Ensure surrounding ambient temperature is within limits. |
| F053 IGBT1 U Overtemp. Fault of overtemperature measured in the temperature sensors (NTC) of the IGBTs. | Cause:
Remedy: Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature. |
| F054 IGBT1 V Overtemp. Fault of overtemperature measured in the temperature sensors (NTC) of the IGBTs. | Cause:
Remedy: Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature. |
| F055 IGBT1 W Overtemp. Fault of overtemperature measured in the temperature sensors (NTC) of the IGBTs. | Cause:
Remedy: Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature. |
| A060 IGBT/DRL Junction Overtemp. High temperature at the junction of the IGBTs or diodes alarm. | Cause:
Remedy: Clean the heatsink. Check if the cooling fan is blocked or defective. Ensure surrounding ambient temperature is within limits. |
| F061 IGBT/DRL Junction Overtemp. Overtemperature at the junction of the IGBTs or diodes fault. | Cause:
Remedy: Check the ventilation/cooling fan. Clean the heatsink. Check ambient temperature. |
| F062 Thermal Imbalance Power module temperature unbalance fault. | Cause:
Remedy: Verify balanced operational conditions of the IGBT modular blocks. Ensure fans are running correctly on all power books. |
| F070 DC Link Short Circuit Fault of short circuit at the output, DC link, or braking resistor. | Cause:
Remedy: Check output motor cabling for phase-to-phase short-circuits. Check dynamic braking connection leads. Verify IGBT module conditions. |
| F071 Overcur. at the Output Output overcurrent fault. | Cause:
Remedy: Increase deceleration ramp time or reduce load inertia. Check values in parameters C3.4.1 or C3.3.5.1.1. |
| F072 Motor Overload Motor overload fault. | Cause:
Note: This fault can be disabled by setting parameter C7.4.1 = 0 or 3. Remedy: Verify motor nominal currents. Check settings of parameters C7.4.3, C7.4.4, and C7.4.5. Check for mechanical load blocks on the motor shaft. |
| F074 Ground Fault Overcurrent to ground fault. | Cause:
Note: This fault can be disabled by setting parameter C7.2.1 = 0 or 3. Remedy: Verify insulation of motor cables and motor winding. If cable capacitance is high, reduce cable length or add an output reactor. |
| F078 Motor Overtemp. | Cause: Fault related to the PTC temperature sensor installed on the motor.
Note: The fault can be disabled by setting C7.5.2 = 2 or 3. It is necessary to program Slot X analog input and output for PTC function. Remedy: Check mechanical load on the motor shaft and optimize start/stop duty cycles. Ensure proper motor cooling. Measure thermistor wire resistance to verify it is > 100 Ω. Confirm correct installation and parameters on Slot X and parameter C7.5.2. |
| F080 CPU Fault (Watchdog) | Cause: Inverter control watchdog fault.
Remedy: Optimize grounding lines and shield pathways. Ensure control cables are physically separated from high-current power cables. |
| F084 Self-Diagnostics. Error | Cause: Self-Diagnostics Fault.
Remedy: Power down the inverter and check internal circuitry. Contact technical support for card evaluation if fault is persistent. |
| A090 External Alarm | Cause: External alarm via digital input.
Note: Necessary to set the DI in parameter C7.10.1. Remedy: Check digital input terminal loops and secure connections to prevent open circuit alarms. |
| F091 External Protection | Cause: External fault via digital input.
Note: Necessary to set the DI in parameter C7.10.2. Remedy: Check digital input terminal loops and ensure external switches are not triggering open circuits. |
| F099 Invalid Curr. Offset | Cause: Current measurement circuit has a value out of the standards for zero current.
Remedy: Check the internal current sensors. Board replacement or factory repairs may be necessary. |
| F104 A/D Converter Error | Cause: Fault reading the A/D converter that measures the inverter currents and voltages.
Remedy: Inspect control module circuits. Verify that general installation grounding, cable shielding, and panel layouts are properly set up to mitigate EMI. |
| A110 High Motor Temperature | Cause: Alarm related to the PTC temperature sensor installed on the motor.
Note: The alarm can be disabled by setting C7.5.2. It is necessary to program Slot X analog input and output for PTC function. Remedy: Check mechanical load, motor bearings, and temperature. Secure thermistor wire terminal screws and verify resistance is not < 100 Ω. |
| A128 Serial Communication Timeout | Cause: It indicates that the CFW900 stopped receiving telegrams on the serial interface for a period longer than the setting programmed in C9.3.5.
Note: Make sure the master always sends telegrams to the equipment within a period shorter than the setting in C9.3.5. It can be disabled by setting C9.3.5=0.0 s. Remedy: Check serial connections, shield grounding, and wiring. Adjust master polling times, or disable timeout by modifying C9.3.5. |
| A133 No Power Supply on the CAN Interface | Cause: It actuates when the CAN interface is powered and lack of power supply to the interface is detected.
Note: Measure if there is voltage within the allowed range between pins 1 and 5 of the CAN interface connector. Remedy: Check external 24 Vdc supply is active and connected correctly to pins 1 and 5. Verify cable polarity. |
| A134 Bus Off | Cause: Bus off error detected on the CAN interface.
Remedy: Verify CAN cabling polarity and check for line shorts. Match network node baud rates. Check termination resistor locations. Cycle power to reestablish communications. |
| A135 CANopen Off-line | Cause: It occurs if the state of the CANopen node changes from operational to pre-operational.
Note: Check the operation of the error control mechanisms (Heartbeat/Node Guarding). Remedy: Check master configuration times and correct. Address network communication lag or noise. |
| A136 Master in Idle | Cause: It actuates when communicating with the DeviceNet network master in Run mode, and transition to Idle mode is detected.
Remedy: Set the master operation control switch to Run or verify the configuration word bits on the master controller. |
| A137 DeviceNet connection timeout | Cause: It indicates that one or more DeviceNet I/O connections has expired. It occurs when, for some reason, after the cyclical communication between the master and the product has started, this communication is interrupted.
Remedy: Check DeviceNet master state. Inspect physical network cables for breaks or loose connections. |
| A145 SNTP Connection Timeout | Cause: It indicates that the inverter tried to connect to the NTP server and got no response. It occurs when, for some reason, after starting connection with the NTP server, the server did not return the response requested by the inverter.
Remedy: Check configuration and IP address. Verify that the NTP server is still active and reachable over the network. |
| A149 Timeout Modbus TCP | Cause: It indicates that the device stopped receiving valid telegrams for a period longer than the setting in C9.6.3. The time counting starts as soon as it receives the first valid telegram.
Note: This function can be disabled in parameter C9.6.3. Remedy: Check connections, cables, and grounding. Ensure the master/client is sending telegrams faster than the timeout configured in parameter C9.6.3, or adjust C9.6.3 to disable the timeout. |
| F150 Motor Overspeed | Cause: Overspeed fault.
Note: Activated when the actual speed exceeds the value of C4.3.1.1.2 x (100 % + C7.7.1) for more than 20 ms. Remedy: Verify parameter configurations for C3.3.2.1.2 and C3.3.2.1.3. For hoisting/crane applications, ensure proper load control and braking logic. |
| A152 Pow.Int. Air Overtemp. | Cause: High internal air temperature alarm.
Note: The alarm can be disabled by setting C7.5.1. Remedy: Improve enclosure ventilation. Replace any defective internal cooling fans. Set parameter C7.5.1 to adjust alarm behavior if desired. |
| F153 Pow.Int. Air Overtemp. | Cause: Internal air overtemperature fault.
Remedy: Check local cooling conditions, clear air blockages, and ensure cabinet fans are running correctly. |
| A154 Cont.Int.Air Overtemp. | Cause: Control circuit high temperature alarm.
Note: The alarm can be disabled by setting C7.5.1. Remedy: Check cooling fan status, clean heatsink, and improve room airflow. Use C7.5.1 to adjust alarm behavior if desired. |
| F155 Cont.Int.Air Overtemp. | Cause: Control circuit overtemperature fault.
Remedy: Check cooling fan, clean heatsink, and reduce ambient/room temperatures if too high. |
| A156 IGBT undertemperature | Cause: Alarm of undertemperature measured by the sensors in the IGBTs, rectifier, power and/or control below -30 °C.
Note: The alarm can be disabled by setting C7.5.1. Remedy: Verify ambient working temperature. Provide workspace heating if operating in extreme cold. Use parameter C7.5.1 to bypass if desired. |
| F157 IGBT undertemperature | Cause: Fault of undertemperature measured by the sensors in the IGBTs, rectifier, power and/or control below -30 °C.
Remedy: Check the installation environment. Provide heating element control inside the cabinet for operation in cold environments. |
| F158 Corrupted settings | Cause: Inverter settings are invalid.
Note: Restore the settings from a backup. Remedy: Restore the parameter settings from a validated backup file. |
| F160 STO90 Fault | Cause: It indicates to the user that STO90 is in a fault state.
Remedy: Verify safety input circuits. Confirm STO1 and STO2 terminals are balanced and synchronized. Check DIP switches S1/S2 positions. Replace module if defective. |
| F161 STO90 Off-line | Cause: It indicates to the user that CFW900 central control has lost communication with STO90.
Remedy: Check terminal contacts and board fitment. Verify central control unit circuit. |
| F171 Pow. Fan 1 Speed | Cause: Heat sink fan 1 speed fault.
Remedy: Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective. |
| F172 Pow. Fan 2 Speed | Cause: Heat sink fan 2 speed fault.
Remedy: Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective. |
| F173 Pow. Fan 3 Speed | Cause: Heat sink fan 3 speed fault.
Remedy: Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective. |
| F174 Pow. Fan 4 Speed | Cause: Heat sink fan 4 speed fault.
Remedy: Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective. |
| F175 Int. Fan 1 Speed | Cause: Internal fan 1 speed fault.
Remedy: Clean fan blades and secure connections. Replace if mechanically failed. |
| F176 Int. Fan 2 Speed | Cause: Internal fan 2 speed fault.
Remedy: Clean fan blades and secure connections. Replace if mechanically failed. |
| A181 Clock with invalid value | Cause: Clock with wrong time.
Note: Set the date and time in C11.1.2. Remedy: Configure date and time parameter C11.1.2. Replace the internal battery if discharged or missing. |
| F185 Pre-charge Protection | Cause: It indicates pre-charge contactor fault.
Remedy: Check pre-charge contactor and loop fuses. Verify incoming input phases. |
| A186 Pow. Fan 1 Speed | Cause: Heat sink fan low speed alarm.
Remedy: Clean fan blades and ensure bearing path is clear. Check connections. |
| A187 / A188 / A189 Pow. Fan 2, 3, 4 Speed Heatsink fan low speed alarm. | Cause:
Remedy: Check fan bearings and clear dirt build-up from blades. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective. |
| A190 / A191 Int. Fan 1, 2 Speed Internal fan low speed alarm. | Cause:
Remedy: Check internal fan blades and clear dirt. Ensure power supply connections to the fan are secure. Replace the fan module if mechanically defective. |
| F228 Serial Communication Timeout | Cause: It indicates that the CFW900 stopped receiving telegrams on the serial interface for a period longer than the setting programmed in C9.3.5.
Note: Make sure the master always sends telegrams to the equipment within a period shorter than the setting in C9.3.5. It can be disabled by setting C9.3.5=0.0 s. Remedy: Check serial connections, shield grounding, and wiring. Adjust master polling times, or disable timeout by modifying C9.3.5. |
| F233 No Power Supply on the CAN Interface | Cause: It actuates when the CAN interface is powered and lack of power supply to the interface is detected.
Note: Measure if there is voltage within the allowed range between pins 1 and 5 of the CAN interface connector. Remedy: Check external 24 Vdc supply is active and connected correctly to pins 1 and 5. Verify cable polarity. |
| F234 Bus Off | Cause: Bus off error detected on the CAN interface.
Remedy: Check CAN high and low wires for short circuits or inverted signals. Match node baud rates across the network. Check termination resistor values and placement. |
| F235 CANopen Off-line | Cause: It occurs if the state of the CANopen node changes from operational to pre-operational.
Note: Check the operation of the error control mechanisms (Heartbeat/Node Guarding). Remedy: Check master configuration times and correct. Address network communication lag or noise. |
| F236 Master in Idle | Cause: It actuates when communicating with the DeviceNet network master in Run mode, and transition to Idle mode is detected.
Remedy: Set the master operation control switch to Run or verify the configuration word bits on the master controller (refer to master device documentation). |
| F237 DeviceNet connection timeout | Cause: It indicates that one or more DeviceNet I/O connections has expired. It occurs when, for some reason, after the cyclical communication between the master and the product has started, this communication is interrupted.
Remedy: Check DeviceNet master state. Inspect physical network cables for breaks or loose connections. |
| F249 Modbus TCP Timeout | Cause: It indicates that the device stopped receiving valid telegrams for a period longer than the setting in C9.6.3.
Note: This function can be disabled in parameter C9.6.3. Remedy: Check connections, cables, and grounding. Ensure the master/client is sending telegrams faster than the timeout configured in parameter C9.6.3, or adjust C9.6.3 to disable the timeout. |
| A345 / F346 / A348 / F349 / A351 / F352 IGBT P.U/P.V/P.W B1 High Load & Overload | Cause: Alarm / Fault of overload on IGBT 1 of phase U, V, or W.
Remedy: Reduce motor load or adjust acceleration parameters to lower active output current levels. Check drive sizing if current remains continuously high. |
| A354 / F355 / A357 / F358 / A360 / F361 IGBT P.U/P.V/P.W B2 High Load & Overload | Cause: Alarm / Fault of overload on IGBT 2 of phase U, V, or W.
Remedy: Reduce motor load or adjust acceleration parameters to lower active output current levels. Check drive sizing if current remains continuously high. |
| F600 Pulse Update Error | Cause: Fault related to updating the PWM pulses.
Remedy: Check the physical state of the control board. If the pulse updates are failing, the internal circuitry may be defective. |
| F606 Power Monitor Comm Lost | Cause: Communication fault between AUI and PMON.
Remedy: Verify internal power board status. Ensure proper connection cables are secure and grounding pathways are clear of noise interference. |
| F607 SMM Comm Lost | Cause: Communication fault between PWC and SMM.
Remedy: Verify safety interface board is powered and seated correctly. Protect connection ports from electromagnetic noise. |
| F608 Code Flow Failure | Cause: Internal fault during inverter operation. Remedy: Reset the inverter. Load the factory default parameters. If the problem persists, contact WEG assistance. |
| F609 Model Version Incompatible | Cause: Inverter model data version is incompatible with the actual firmware. Remedy: Contact technical support to arrange the model update. |
| A700 / F701 HMI Disconnected | Cause: Alarm / Fault related to the HMI disconnection.
Remedy: Ensure remote HMI is plugged in and check keypad serial connections. |
| A702 Inverter Disabled | Cause: Alarm indicates that the General Enable command is Inactive.
Remedy: Ensure the drive General Enable command is active. Check SoftPLC application logic parameters. |
| A706 SPLC Refer. Not Progr. | Cause: Reference not programmed for SoftPLC.
Remedy: Ensure local and remote speed reference setups are configured correctly for SoftPLC in parameter C4.3.1.2. |
| A708 / F709 SoftPLC Not Running | Cause: SoftPLC application is not running.
Remedy: Configure and run the SoftPLC application. Check parameters in S6.1.1 and C10.1.3. |
| F1000 Accessory firmware update error | Cause: Error during accessory firmware update.
Remedy: Update the inverter base firmware to compatible levels. |
| A1012 / F1013 Default Slot AI1 cable disconnection | Cause: Analogue input signal set to actual mode is out of the range 4 to 20 mA.
Remedy: Inspect AI1 loop cabling for breaks. Tighten screw terminal contacts. |
| A1014 / F1015 Default Slot AI2 cable disconnection | Cause: Analogue input signal set to actual mode is out of the range 4 to 20 mA.
Remedy: Inspect AI2 loop cabling for breaks. Tighten screw terminal contacts. |
| F1100 Slot A incompatible accessory | Cause: Error during accessory firmware update.
Remedy: Update the inverter base firmware to support the accessory update. |
| F1101 Slot A Initialization Error | Cause: It was not possible to initialize a resource required for the accessory to work.
Remedy: Ensure no resource overlapping is present on Slot A. Connect only one network communication accessory at a time. |
| F1103 Slot A accessory connection | Cause: Loss of communication with the accessory.
Remedy: Reduce local electromagnetic noise and structural vibrations. Inspect physical terminals and check accessory board firmware state. |
| A1104 / F1105 Slot A Temperature Warning / Fault Temperature or overtemperature inside the Slot A accessory is high. | Cause:
Remedy: Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits. |
| A1106 / F1107 Slot A enc. A cable disconnection Encoder channel A signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1108 / F1109 Slot A enc. B cable disconnection Encoder channel B signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1110 / F1111 Slot A enc. Z cable disconnection Encoder channel Z signal is not detected correctly. | Cause:
Remedy: Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1112 to F1117 Slot A AI1, AI2, AI3 Cable Disconnection Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| A1118 / F1119 Slot A AI4 Cable Disconnection Analog input signal AI4 set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| F1125 Slot A temp. sensor wrong hw config | Cause:
Remedy: Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1. |
| A1126 / F1127 Slot A temperature sensor 1 error | Cause:
Remedy: Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1128 / F1129 Slot A sensor 1 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1130 / F1131 Slot A temperature sensor 2 error | Cause:
Remedy: Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1132 / F1133 Slot A sensor 2 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1134 / F1135 Slot A temperature sensor 3 error | Cause:
Remedy: Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1136 / F1137 Slot A sensor 3 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1138 / F1139 Slot A temperature sensor 4 error | Cause:
Remedy: Check temperature sensor 4 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1140 / F1141 Slot A sensor 4 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1142 / F1143 Slot A temperature sensor 5 error | Cause:
Remedy: Check temperature sensor 5 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1144 / F1145 Slot A sensor 5 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1146 / F1147 Slot A temperature sensor 6 error | Cause:
Remedy: Check temperature sensor 6 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1148 / F1149 Slot A sensor 6 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| F1200 Slot B incompatible accessory | Cause:
Remedy: Update the inverter base software to a compatible version. |
| F1201 Slot B Initialization Error | Cause:
Remedy: Review Slot B accessory layouts. Ensure only one module is configured for each type of network protocol on the inverter at any time. |
| F1203 Slot B accessory connection | Cause:
Remedy: Trace electrical grounds and apply EMI shielding where appropriate. Secure physical slot fitment to prevent vibration issues. Re-flash card firmware if corrupted. |
| A1204 / F1205 Slot B Temperature Warning / Fault Temperature or overtemperature inside the Slot B accessory is high. | Cause:
Remedy: Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits. |
| A1206 / F1207 Slot B enc. A cable disconnection Encoder channel A signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1208 / F1209 Slot B enc. B cable disconnection Encoder channel B signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1210 / F1211 Slot B enc. Z cable disconnection Encoder channel Z signal is not detected correctly. | Cause:
Remedy: Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1212 to F1217 Slot B AI1, AI2, AI3 Cable Disconnection Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| A1218 / F1219 Slot B AI4 Cable Disconnection Analog input signal AI4 set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| F1225 Slot B temp. sensor wrong hw config | Cause:
Remedy: Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1. |
| A1226 / F1227 Slot B temperature sensor 1 error | Cause:
Remedy: Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1228 / F1229 Slot B sensor 1 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1230 / F1231 Slot B temperature sensor 2 error | Cause:
Remedy: Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1232 / F1233 Slot B sensor 2 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1234 / F1235 Slot B temperature sensor 3 error | Cause:
Remedy: Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1236 / F1237 Slot B sensor 3 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1238 / F1239 Slot B temperature sensor 4 error | Cause:
Remedy: Check temperature sensor 4 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1240 / F1241 Slot B sensor 4 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1242 / F1243 Slot B temperature sensor 5 error | Cause:
Remedy: Check temperature sensor 5 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1244 / F1245 Slot B sensor 5 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1246 / F1247 Slot B temperature sensor 6 error | Cause:
Remedy: Check temperature sensor 6 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1248 / F1249 Slot B sensor 6 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| F1300 Slot C incompatible accessory | Cause:
Remedy: Update the inverter base software to a compatible version. |
| F1301 Slot C Initialization Error | Cause:
Remedy: Review Slot C accessory layouts. Ensure only one module is configured for each type of network protocol on the inverter at any time. |
| F1303 Slot C accessory connection | Cause:
Remedy: Trace electrical grounds and apply EMI shielding where appropriate. Secure physical slot fitment to prevent vibration issues. Re-flash card firmware if corrupted. |
| A1304 / F1305 Slot C Temperature Warning / Fault Temperature or overtemperature inside the Slot C accessory is high. | Cause:
Remedy: Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits. |
| A1306 / F1307 Slot C enc. A cable disconnection Encoder channel A signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1308 / F1309 Slot C enc. B cable disconnection Encoder channel B signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1310 / F1311 Slot C enc. Z cable disconnection Encoder channel Z signal is not detected correctly. | Cause:
Remedy: Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1312 to F1317 Slot C AI1, AI2, AI3 Cable Disconnection Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| A1318 / F1319 Slot C AI4 Cable Disconnection Analog input signal AI4 set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| F1325 Slot C temp. sensor wrong hw config | Cause:
Remedy: Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1. |
| A1326 / F1327 Slot C temperature sensor 1 error | Cause:
Remedy: Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1328 / F1329 Slot C sensor 1 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1330 / F1331 Slot C temperature sensor 2 error | Cause:
Remedy: Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1332 / F1333 Slot C sensor 2 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1334 / F1335 Slot C temperature sensor 3 error | Cause:
Remedy: Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1336 / F1337 Slot C sensor 3 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1338 / F1339 Slot C temperature sensor 4 error | Cause:
Remedy: Check temperature sensor 4 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1340 / F1341 Slot C sensor 4 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1342 / F1343 Slot C temperature sensor 5 error | Cause:
Remedy: Check temperature sensor 5 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1344 / F1345 Slot C sensor 5 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1346 / F1347 Slot C temperature sensor 6 error | Cause:
Remedy: Check temperature sensor 6 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1348 / F1349 Slot C sensor 6 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| F1400 Slot D incompatible accessory | Cause:
Remedy: Update the inverter base software to a compatible version. |
| F1401 Slot D Initialization Error | Cause:
Remedy: Review Slot D accessory layouts. Ensure only one module is configured for each type of network protocol on the inverter at any time. |
| F1403 Slot D accessory connection | Cause:
Remedy: Trace electrical grounds and apply EMI shielding where appropriate. Secure physical slot fitment to prevent vibration issues. Re-flash card firmware if corrupted. |
| A1404 / F1405 Slot D Temperature Warning / Fault Temperature or overtemperature inside the Slot D accessory is high. | Cause:
Remedy: Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits. |
| A1406 / F1407 Slot D enc. A cable disconnection Encoder channel A signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1408 / F1409 Slot D enc. B cable disconnection Encoder channel B signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1410 / F1411 Slot D enc. Z cable disconnection Encoder channel Z signal is not detected correctly. | Cause:
Remedy: Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1412 to F1417 Slot D AI1, AI2, AI3 Cable Disconnection Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| A1418 / F1419 Slot D AI4 Cable Disconnection Analog input signal AI4 set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| F1425 Slot D temp. sensor wrong hw config | Cause:
Remedy: Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1. |
| A1426 / F1427 Slot D temperature sensor 1 error | Cause:
Remedy: Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1428 / F1429 Slot D sensor 1 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1430 / F1431 Slot D temperature sensor 2 error | Cause:
Remedy: Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1432 / F1433 Slot D sensor 2 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1434 / F1435 Slot D temperature sensor 3 error | Cause:
Remedy: Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1436 / F1437 Slot D sensor 3 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1438 / F1439 Slot D temperature sensor 4 error | Cause:
Remedy: Check temperature sensor 4 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1440 / F1441 Slot D sensor 4 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1442 / F1443 Slot D temperature sensor 5 error | Cause:
Remedy: Check temperature sensor 5 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1444 / F1445 Slot D sensor 5 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1446 / F1447 Slot D temperature sensor 6 error | Cause:
Remedy: Check temperature sensor 6 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1448 / F1449 Slot D sensor 6 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| F1500 Slot E incompatible accessory | Cause:
Remedy: Update the inverter base software to a compatible version. |
| F1501 Slot E Initialization Error | Cause:
Remedy: Review Slot E accessory layouts. Ensure only one module is configured for each type of network protocol on the inverter at any time. |
| F1503 Slot E accessory connection | Cause:
Remedy: Trace electrical grounds and apply EMI shielding where appropriate. Secure physical slot fitment to prevent vibration issues. Re-flash card firmware if corrupted. |
| A1504 / F1505 Slot E Temperature Warning / Fault Temperature or overtemperature inside the Slot E accessory is high. | Cause:
Remedy: Check and improve enclosure ventilation. Inspect cooling fans or auxiliary cabinet cooling systems. Ensure ambient operating temperature is within limits. |
| A1506 / F1507 Slot E enc. A cable disconnection Encoder channel A signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel A cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1508 / F1509 Slot E enc. B cable disconnection Encoder channel B signal is not detected correctly. | Cause:
Note: This check can be disabled by setting parameter C5.n.6.2 (where n is the slot index where the accessory is installed). Remedy: Verify the physical and electrical integrity of the encoder channel B cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1510 / F1511 Slot E enc. Z cable disconnection Encoder channel Z signal is not detected correctly. | Cause:
Remedy: Verify the physical and electrical integrity of the encoder channel Z (marker) cabling. Check terminal connections and verify the encoder auxiliary power supply voltage. |
| A1512 to F1517 Slot E AI1, AI2, AI3 Cable Disconnection Analog input signal (AI1, AI2, or AI3) set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| A1518 / F1519 Slot E AI4 Cable Disconnection Analog input signal AI4 set to 4 to 20 mA mode is out of range. | Cause:
Remedy: Check loops for physical line breaks. Clean and secure terminal connections. |
| F1525 Slot E temp. sensor wrong hw config | Cause:
Remedy: Check the physical DIP switch settings on the CFW900-TEMP-01 module. Ensure they correspond directly to the parameter configuration described in section C5.2.6.1. |
| A1526 / F1527 Slot E temperature sensor 1 error | Cause:
Remedy: Check temperature sensor 1 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1528 / F1529 Slot E sensor 1 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1530 / F1531 Slot E temperature sensor 2 error | Cause:
Remedy: Check temperature sensor 2 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1532 / F1533 Slot E sensor 2 high temp / overtemperature | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
| A1534 / F1535 Slot E temperature sensor 3 error | Cause:
Remedy: Check temperature sensor 3 cabling for open or short circuits. Verify that surrounding environmental temperatures are within system parameters. |
| A1536 Slot E sensor 3 high temp | Cause:
Remedy: Verify equipment active operating temperature levels. Review parameter configurations for fault actuation thresholds. |
How to Clear & Reset WEG CFW900 Drive Faults
- Keypad Reset: Press the red “O / STOP / RESET” key on the front graphic HMI keypad. If the unit is configured in remote mode (REM), switch to local mode (LOC) before initiating a manual keypad reset.
- Digital Input Reset (DI): If assigned in configuration menu C9 (I/O Configuration) to the “Fault Reset” function, pulse the assigned 24V digital input terminal to clear trip status.
- WPS PC Software & WPS Mobile: Connect using the embedded dual Ethernet ports, standard USB-C port, or integrated Bluetooth via the WPS Mobile application, and issue a “Fault Reset” command from the diagnostics dashboard.
- Industrial Ethernet / Fieldbus: Assert Bit 7 (Fault Reset) in the Control Word (S1.6.3 / CIP Bit 2) via native EtherNet/IP, Modbus TCP, Profinet, or RS485 Modbus RTU communications.
- Power Cycle: Disconnect the three-phase AC mains supply, wait at least 10 minutes until the DC bus capacitors completely discharge and the HMI display extinguishes, then re-apply input power.
⚠️ High-Voltage Electrical Safety Warning:
Always disconnect incoming power and wait a minimum of 10 minutes for intermediate DC bus link capacitors to fully discharge. Confirm with a calibrated digital multimeter that the DC bus voltage measures strictly below 50VDC across terminals [+UD] and [-UD] (or dynamic braking terminal [BR]) before removing terminal covers or touching motor output connections U, V, and W on the WEG CFW900 drive.