WEG CFW10 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW10 micro inverter series. Search or filter through the complete fault code directory below.

Micro Frequency Inverter Power: 0.18 to 4.0 kW (0.25 to 5 HP) Scalar (V/F) Control
Power Range 0.18 – 4.0 kW (0.25 – 5 HP)
Supply Voltage 110–127V / 200–240V (1/3-Phase)
Control Modes Linear & Quadratic V/F (Scalar)
Operator Interface Built-in LED Keypad (HMI-CFW10)

Complete WEG CFW10 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E00, E02, or Overcurrent).

Fault / Alarm and MeaningCause and Remedy
E00

Output Overcurrent (between phases)

Cause:



  • Short-circuit between two motor phases.

  • Short circuit between ground and one or more output phases (if occurring during power-up).

  • Inertia of the load is too high, or acceleration ramp is too short.

  • Parameter P169 configured too high.

  • Incorrect configuration/setting of parameters P136 and/or P137.

  • IGBT transistor module is short-circuited.





Remedy:


Check output motor cabling for phase-to-phase short-circuits. Check for ground short-circuits on output phases. Increase the acceleration ramp time or reduce load inertia. Verify control parameters, and decrease parameter P169 or parameters P136/P137 if configured incorrectly. Inspect output IGBT modules.



Reset options: Power-on, Manual reset (Key 0), Auto-Reset, DI (Digital Input).
E01

DC Link Overvoltage

Cause:


Power supply voltage is too high, generating in the DC link a voltage higher than the allowed value:

  • Models 200-240 V: Ud > 410 V

  • Models 110-127 V: Ud > 460 V


Additional factors:

  • Load inertia too high and deceleration ramp is too short.

  • Setting of parameter P151 is configured too high.





Remedy:


Verify incoming mains supply voltage stability. Increase deceleration ramp time or reduce load inertia. Use a dynamic braking resistor if required. Decrease parameter P151 if configured too high.



Reset options: Power-on, Manual reset (Key 0), Auto-Reset, DI (Digital Input).
E02

DC Link Undervoltage (Ud)

Cause:


Power supply voltage is too low, causing a DC link voltage below the allowed value (monitored in parameter P004):

  • Models 200-240 V: Ud < 200 V

  • Models 110-127 V: Ud < 250 V





Remedy:


Check incoming supply voltage (P004) and ensure compliance with drive ratings. Check for input phase losses or general voltage drops.



Reset options: Power-on, Manual reset (Key 0), Auto-Reset, DI (Digital Input).
E04

Inverter Overtemperature

Cause:



  • Ambient temperature too high (> 50 ºC), (> 40 °C for the 15.2 A model) and/or output current too high.

  • Blocked or defective fan.


Note: The heatsink overtemperature protection (E04) is activated when the heatsink temperature (P008) reaches 103 ºC (or 133 ºC for the 15.2 A model).



Remedy:


Allow the inverter to cool down before attempting to reset. Clean heatsink fins and verify that the cooling fan is operating correctly. Ensure surrounding ambient temperature is within limits.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DI (Digital Input).
E05

Overload at output (I × t Function)

Cause:



  • Parameter P156 is configured too low for the connected motor.

  • Motor is under an actual overload condition.





Remedy:


Verify motor current settings (P156) match motor nameplate rating. Reduce motor shaft load.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DI (Digital Input).
E06

External Error

Cause:



  • Wiring at digital inputs DI1 through DI4 is open [not connected to GND (pin 5 of the XC1 control connector)].


Note: Valid when digital input programmed for external fault is open.



Remedy:


Verify external fault wiring connections on digital inputs. Ensure inputs DI1 through DI4 are connected to GND (pin 5 of the XC1 connector) under normal conditions to prevent false triggering.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DI (Digital Input).
E08

CPU Error

Cause:



  • High electrical noise.





Remedy:


Check the cabinet grounding and shield terminations to mitigate noise.



Reset options: Power-on, Manual reset (Key 0), Auto-reset, DI (Digital Input).
E09

Program Memory Error (Checksum)

Cause:



  • Memory with corrupted values.





Remedy:


This indicates internal card memory failure. Please contact WEG technical support for control board evaluation.



Reset: Contact WEG (refer to section 7.3).
E24

Programming error

Cause:



  • Incompatible parameters were programmed. Refer to table 5.1.





Remedy:


This fault is automatically reset when the incompatible parameters are correctly programmed. Resolve conflicting parameter values according to manual Table 5.1 definitions.
E31

Keypad (HMI) Connection Fault

Cause:



  • Inverter control circuit is defective.

  • Electrical noise in the installation (electromagnetic interference).





Remedy:


Check keypad RJ45/serial cable connections. Protect the cable from electromagnetic noise. If the inverter control circuit itself is defective, contact WEG Servicing (Refer to section 7.3).



Reset: Contact WEG Servicing (Refer to section 7.3).
E41

Self-Diagnosis Fault

Cause:



  • Inverter power circuit is defective.





Remedy:


Contact WEG technical support/servicing for hardware evaluation.



Reset: Contact WEG Servicing (refer to section 7.3).

How to Clear & Reset WEG CFW10 Drive Faults

  1. Keypad Reset (O Key): Press the red O (STOP / RESET) key on the integrated HMI keypad while the error code (e.g., E00 to E41) is blinking on the 4-digit LED display.
  2. Digital Input Reset (DI): If an available digital input (DI1 to DI4) has been configured as Reset via parameters P263 to P266 = 12, cycle the corresponding terminal switch from open to closed.
  3. Auto-Reset Configuration: Program parameter P206 (Auto-Reset Time) to a value greater than 0 seconds. When set, the inverter will automatically reset resettable faults after the configured interval.
  4. Power Cycle: Disconnect the incoming AC power supply. Wait at least 10 minutes for the internal DC bus filter capacitors to fully discharge and the display to power down completely before restoring mains power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect AC mains supply power and wait at least 10 minutes for internal capacitors to discharge. Verify with a calibrated digital multimeter that the DC bus voltage across terminals [+UD] and [BR] (or intermediate DC bus) has dropped strictly below 50VDC before inspecting motor terminals U, V, W or removing terminal strip covers on the WEG CFW10 drive.