WEG CFW501 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW501 HVAC-R variable speed drive series. Search or filter through the complete fault code directory below.
Power Range
0.18 – 110 kW (0.25 – 150 HP)
Supply Voltage
200–240V / 380–480V (1-Ph & 3-Ph)
Control Modes
Scalar (V/f) & Voltage Vector (VVW)
Operator Interface
Integrated HMI Keypad & SuperDrive G2
Complete WEG CFW501 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type F0006, F0021, or Overcurrent).
| Alarm / Fault and Meaning | Cause and Remedy |
|---|---|
| A0046 Motor Overload Motor overload alarm. | Cause:
Remedy: Verify if parameters P0156, P0157, and P0158 are configured correctly according to the motor's actual capacity. Inspect the motor shaft and machine for mechanical blocks. |
| A0047 IGBT Overload Overload alarm on the power pack with IGBTs. | Cause:
Remedy: Analyze operating load levels and duty cycles to lower active output current. Check for mechanical drag. |
| A0050 Power Module Overtemperature Overtemperature alarm from the power module temperature sensor (NTC). | Cause:
Remedy: Inspect cooling fan operation and clean any dust or debris from heatsink fins. Improve room/enclosure ventilation as needed. |
| A0090 External Alarm External alarm via DIx (option No External Alarm in P026x). | Cause:
Remedy: Inspect terminal connections for digital inputs DI1 through DI8. Secure loose terminals and ensure reliable contact switch states. |
| A0098 Interruption of Self-tuning It indicates interruption of self-tuning. | Cause:
Remedy: Ensure the digital input assigned to keep the drive enabled remains active during the entire self-tuning routine execution. |
| A0128 Telegram Reception Timeout Alarm indicating a serial communication fault. It indicates the equipment stopped receiving valid serial telegrams for a period longer than the setting in P0314. | Cause:
Remedy: Verify serial communication cabling, connections, and grounding lines. Ensure the master's polling interval is shorter than parameter P0314, or disable this timeout check in parameter P0314. |
| A0160 Safe State Active It indicates to the user that the safety functions module has enabled the safe state for the inverter (safe torque off). | Cause:
Remedy: Verify the safety input circuits. Confirm that STO terminals are properly energized and wired to ensure they are not de-energized under normal operational status. |
| A0161 SS1-t Timing Active It indicates to the user that the safety functions module is executing the timing of the SS1-t safety function. | Cause:
Remedy: Informational status indicating the safety module is currently executing the safe stop timing countdown. Check safety circuitry logic. |
| A0162 Safety Functions Module in Programming Mode It indicates to the user that the safety functions module is in the programming mode of the safety functions. | Cause:
Remedy: Verify DIP switch positions on the safety module. Ensure DIP switches are set back to run mode if programming is complete. |
| A0163 Signal Fault AIx 4..20 mA Analogue input signal AIx at 4 to 20 mA or 20 to 4 mA is below 2 mA. | Cause:
Remedy: Check input loop wires for breaks or open circuits. Verify parameter configuration settings for AIx. |
| A0168 Speed Error too High Difference between Speed Reference and Effective Speed greater than the setting in P0360. | Cause:
Remedy: Check if the motor is stalled or heavily overloaded. Verify load status. If appropriate, adjust torque current limits in P0360. |
| A0181 Invalid Clock Value Invalid clock value alarm. | Cause:
Remedy: Set the correct date and time at parameters P0194 to P0199. Replace the internal keypad battery if dead. |
| A0210 Drive in Bypass Mode Indicates that the drive is in Bypass mode. | Cause:
Remedy: Check digital input settings and external wiring assigned to Bypass mode activation. |
| A0211 Drive in Fire Mode Indicates that the drive is in Fire Mode. | Cause:
Remedy: Check the status of the digital input assigned to activate the Fire Mode. Confirm that external switch logic is correct and not stuck in the active state. |
| A0213 Protection Against Short Cycles Alarm indicating that short cycle protection has occurred. | Cause:
Remedy: Review system start/stop demands. Verify configurations set in parameters P0586 and P0587. |
| A0700 Communication Fault with Remote HMI No communication with remote HMI, but there is no speed command or reference for this source. | Cause:
Remedy: Check parameter P0312 to verify that the HMI communication interface is configured correctly. Reconnect or replace the HMI serial cable. |
| A0702 Inverter Disabled This failure occurs when there is an active SoftPLC movement block (REF block) while the "General Enable" command is disabled. | Cause:
Remedy: Check the drive control terminal states to ensure the General Enable input command is active. |
| A0704 Two Movem. Enabled It occurs when 2 or more SoftPLC movement blocks (REF Block) are enabled at the same time. | Cause:
Remedy: Check the user’s SoftPLC program logic to ensure only one movement block is active at any given time. |
| A0706 Refer. Not Progr. SoftPLC This failure occurs when a SoftPLC movement block is enabled but the speed reference has not been programmed for the SoftPLC. | Cause:
Remedy: Check and verify the speed reference configuration in parameters P0221 and P0222 (Local and Remote modes). |
| A0708 SoftPLC Application Stopped SoftPLC application not running. | Cause:
Remedy: Verify parameter configurations for P1000 and P1001. Upload a compatible version of the SoftPLC application. |
| A0710 SoftPLC Progr. Bigger than 8 kB This failure occurs when the user tries to download a SoftPLC program bigger than 8 kB. | Cause:
Remedy: Check project size. Optimize and compress the SoftPLC code structure to fit within permitted memory limits. |
| A0750 Program AIx for Process Variable of Internal PID Controller Alarm indicating that an analog input was not programmed for the process variable of the internal PID controller. | Cause:
Remedy: Configure parameter P0231 or P0236 to option 5 or 6 according to the PID loop feedback setup. |
| A0752 Program DIx for Automatic / Manual Selection of the Internal PID Controller Alarm indicating that a digital input was not programmed for automatic / manual selection of the internal PID controller. | Cause:
Remedy: Set the assigned digital input parameter (P0263 to P0266) to 20 to enable automatic/manual control routing. |
| A0754 Program LOCAL Reference (P0221) for SoftPLC Alarm indicating that the origin of the speed reference in LOCAL mode was not programmed for SoftPLC. | Cause:
Remedy: Set parameter P0221 to 7 if utilizing the PID controller in local mode. |
| A0756 Program REMOTE Reference (P0222) for SoftPLC Alarm indicating that the origin of the speed reference in REMOTE mode was not programmed for SoftPLC. | Cause:
Remedy: Set parameter P0222 to 7 if utilizing the PID controller in remote mode. |
| A0758 Program Indirect Engineering Unit 4 (P0516) for Hz or rpm Alarm indicating that the parameter for engineering unit of the motor speed was not programmed for Hz or rpm. | Cause:
Remedy: Configure parameter P0516 to option 13 (Hz) or 3 (rpm) to match your application units. |
| A0760 Low Level of the Process Variable of the Internal PID Controller Alarm indicating that the process variable of the internal PID controller has a low value. | Cause:
Remedy: Verify the process feedback sensor. Adjust parameters P1024 (threshold) and P1025 (delay time) if necessary. |
| A0762 High Level in the Process Variable of the Internal PID Controller Alarm indicating that the process variable of the internal PID controller has a high value. | Cause:
Remedy: Check for high limits in the process line (overpressure, high flow, etc.). Verify parameters P1026 and P1027. |
| A0764 Frequency Inverter in Sleep Mode Alarm indicating that the CFW501 frequency inverter is in the sleep mode. | Cause:
Remedy: Informational alarm status indicating sleep mode has engaged. To adjust this behavior, modify parameters P1028 (sleep speed) or P1029 (sleep delay time). |
| A0766 Dry Pump Detected Alarm indicating a dry pump condition was detected for the pump driven by the inverter. | Cause: Parameter P1033 is programmed for 1, the motor speed is above the speed programmed in P1034, and the motor torque has remained below the value programmed in P1035 for the time programmed in P1036. Remedy: Verify the fluid flow to the pump and check for blockages or dry lines. Verify the parameter configurations for P1033, P1034, P1035, and P1036. |
| A0768 Broken Belt Detected Alarm indicating a broken belt condition was detected for the motor driven by the inverter. | Cause: Parameter P1037 is programmed for 1, the motor speed is above the speed programmed in P1047, and the motor torque has remained below the value programmed in P1048 for the time programmed in P1049. Remedy: Check the mechanical coupling belt/pulley state. Verify the parameter configurations for P1037, P1047, P1048, and P1049. |
| A0770 Filter Maintenance Alarm indicating the need to replace the system filter. | Cause: Parameter P1041 is programmed for 1, and the total motor operation time shown in P1043 is above the value programmed in P1042. Remedy: Perform scheduled maintenance to replace the system filter. Reset the elapsed timer if required. |
| A0780 Program AIx for Process Variable of the External PID Controller Alarm indicating that an analog input was not programmed for the process variable of the external PID controller. | Cause: Parameter P0231 or P0236 was not programmed for option 8. Remedy: Set parameter P0231 or P0236 to option 8 to correctly route the external PID process feedback. |
| A0782 Program DIx for Automatic / Manual Selection of the External PID Controller Alarm indicating that a digital input was not programmed for automatic / manual selection of the external PID controller. | Cause: Parameter P0263, P0264, P0265, or P0266 was not programmed for option 21. Remedy: Set the assigned digital input parameter (P0263 to P0266) to 21 to enable manual/automatic switching functions. |
| A0784 Program AOx for Output of the External PID Controller Alarm indicating that an analog output was not programmed for output of the external PID controller. | Cause: Parameter P0251 or P0254 was not programmed for option 15. Remedy: Configure parameter P0251 or P0254 to option 15 to set the analog output target. |
| A0786 Low Level of the Process Variable of the External PID Controller Alarm indicating that the process variable of the external PID controller has a low value. | Cause: Parameter P1055 is programmed for 1, and the process variable of the external PID controller remained below the value programmed in P1056 for the duration set in P1057. Remedy: Verify the process feedback loops and verify configurations in parameters P1055, P1056, and P1057. |
| A0788 High Level of the Process Variable of the External PID Controller Alarm indicating that the process variable of the external PID controller has a high value. | Cause: Parameter P1055 is programmed for 1, and the process variable of the external PID controller remained above the value programmed in P1058 for the duration set in P1059. Remedy: Verify process line sensors. Check parameter thresholds set in P1055, P1058, and P1059. |
| F0021 Undervoltage on the DC Link Undervoltage fault on the intermediate circuit. | Cause:
Remedy: Check input mains voltages. Check terminal blocks and check for missing phases. Verify parameters in P0296. |
| F0022 Overvoltage on the DC Link Overvoltage fault on the intermediate circuit. | Cause:
Remedy: Ensure input voltage matches ratings. Increase deceleration time. Adjust parameters P0151, P0153, or P0185. |
| F0031 Communication Fault with Plug-in Module Main control cannot set a communication link with the plug-in module. | Cause:
Remedy: Check the physical fit and terminal pin contacts of the plug-in card. Replace the card if damaged. Verify identification parameter P0027. |
| F0032 Fault in the Plug-in Module Connection Plug-in module was incorrectly disconnected with the VSD powered up. | Cause:
Remedy: Ensure drive power is isolated before disconnecting accessory cards. Inspect the plugin board pins and re-seat correctly. |
| F0033 Self-tuning Fault Stator resistance setting fault P0409. | Cause:
Remedy: Turn off the power supply and inspect all connections at the motor terminal box. Verify if stator resistance parameter P0409 and motor power ratings are configured correctly. |
| F0048 Overload on the IGBTs Overload fault on the power pack with IGBTs (3 s in 2 x InomHD). | Cause:
Remedy: Reduce motor load to prevent current spikes. Check application sizing. |
| F0051 IGBTs Overtemperature Overtemperature fault measured on the temperature sensor of the power pack. | Cause:
Remedy: Ensure ambient room temperature is within limits. Clean heatsink fins and verify that the cooling fan is operating correctly. |
| F0068 Motor Overtemperature (dedicated input) Overtemperature fault measured on the motor temperature sensor (Triple PTC) via dedicated circuitry in the power scheme. | Cause:
Remedy: Check the motor shaft and driven load for mechanical blockages. Optimize duty cycles. Measure thermistor circuit resistances and secure connections. |
| F0070 Overcurrent/Short circuit Overcurrent or short-circuit on the output, DC Link or braking resistor. | Cause:
Remedy: Verify motor winding and connection cables for phase-to-phase shorts. Increase the acceleration ramp time. Enable the Flying Start function if the motor is prone to rotating during startup. |
| F0072 Motor Overload Motor overload fault (60 s in 1.5 x P0401). | Cause:
Remedy: Verify motor rated currents and adjust parameters P0156, P0157, and P0158. Check mechanical load on shaft. |
| F0074 Ground Fault Ground overcurrent fault. | Cause:
Note: This failure may be disabled by setting parameter P0343 to 0. Remedy: Verify insulation of motor cables and motor winding. If cable capacitance is high, reduce cable length or add an output reactor. |
| F0076 Motor Connection Error This fault indicates the motor presents phase loss, imbalanced phase current, or is disconnected. | Cause:
Remedy: Verify output cabling loops and check motor terminal box contacts. |
| F0078 Motor Overtemperature Overtemperature fault measured on the motor temperature sensor (Triple PTC) via analog input AIx or digital input DIx. | Cause:
Remedy: Check the motor shaft and driven load for mechanical blockages. Optimize duty cycles. Measure thermistor circuit resistances and secure connections. |
| F0080 CPU Fault (Watchdog) Fault related to the supervision algorithm of the inverter main CPU. | Cause:
Remedy: Verify cabinet grounding and shield terminations. Update firmware if required. |
| F0081 Firmware Update Device firmware update failure. | Cause:
Remedy: Verify the communication configurations match 38400 bps, 8-E-2. Inspect cabling and verify that the plugin module version is 1.03 or newer. |
| F0082 Incompatible Firmware Firmware incompatible with the product on which it was recorded. | Cause:
Remedy: Ensure you are using the correct firmware file designed specifically for this drive model. Check control unit circuits if error repeats. |
| F0083 Hardware Identification Failed PWM active level previously set on the inverter does not match the identified hardware. | Cause:
Remedy: Upload factory default parameter settings. Clean contact pins and ensure cards are firmly seated together. |
| F0084 Identification of the Power Hardware Failed Fault related to the automatic identification algorithm of the inverter power pack. | Cause:
Remedy: Check the connection pins between the control unit and power pack. Ensure compatible firmware is utilized. |
| F0085 Plug-in Module Will not Start Failure in the initialization of the plug-in module. | Cause:
Remedy: Verify physical seat of the plug-in board. Check for firmware matching. |
| F0086 Module Identification Failed Fault related to the automatic identification algorithm of the safety functions module. | Cause:
Remedy: Re-seat safety module card. If no safety board is installed, confirm the STO jumper plug is correctly fitted into its port. |
| F0087 Iu Current Offset Fault Fault related to the measurement of the Iu current offset. | Cause:
Remedy: Verify internal cabling connections and current sensor plugs. Apply noise mitigation shielding and ground connections. |
| F0088 Iv Current Offset Fault Fault related to the measurement of the Iv current offset. | Cause:
Remedy: Verify internal cabling connections and current sensor plugs. Apply noise mitigation shielding and ground connections. |
| F0089 Iw Current Offset Fault Fault related to the measurement of the Iw current offset. | Cause:
Remedy: Verify internal cabling connections and current sensor plugs. Apply noise mitigation shielding and ground connections. |
| F0091 External Fault External fault via DIx (No External Fault in P026x). | Cause:
Remedy: Verify external cabling loops to the assigned digital inputs. Tighten loose screw terminals and check contact switches. |
| F0100 EEPROM fault This fault occurs when there are problems booting parameters in the RAM and EEPROM memory areas. | Cause:
Remedy: Attempt parameter reset or firmware reload. If the error remains, replace the control unit card. |
| F0101 DataFlash fault This fault occurs when the DataFlash reading or writing response time is exceeded. | Cause:
Remedy: Check the physical state of the control board. If parameters cannot be written, the flash memory chips may be defective. |
| F0150 Motor Overspeed Overspeed fault. It is activated when the real speed exceeds the value of P0134 x (100 % + P0132) for more than 20 ms. | Cause:
Remedy: Adjust overspeed limit parameters P0161 and P0162. For lifting or hoist applications, verify brake coordination and torque limits. |
| F0158 Incomp. Main Sw Version Main firmware version is different from the plug-in firmware version. | Cause:
Remedy: Perform parameter synchronization. Update plugin software or see Section 2.3 FIRMWARE COMPATIBILITY of the manual for compatibility mappings. |
| F0160 Safety Functions Module in Fault State It indicates to the user that the safety functions module went into fault state. | Cause:
Remedy: Verify balanced dual-channel STO cabling. Confirm DIP switches S2 are correctly set. Reset the programming loop or replace safety card if physically defective. |
| F0161 Safety Functions Module Communication Fault It indicates to the user that the inverter has lost communication with the safety functions module. | Cause:
Remedy: Check the terminal seating and card fitment in the slot. Inspect interface connectors for damaged pins. |
| F0162 Hardware Incompatibility Illegal configuration for STO module with 600 V inverter. | Cause:
Remedy: Change the inverter voltage class or remove the STO safety module card from this unit. |
| F0169 Speed Error too High Difference between Speed Reference and Effective Speed greater than the setting in P0360 for longer than P0361. | Cause:
Remedy: Check if the motor is stalled or heavily overloaded. Verify torque limits. Check parameters P0360 and P0361. |
| F0182 Pulse Feedback Fault Pulse feedback circuit fault of the output voltage. | Cause:
Note: This monitoring can be disabled in parameter P0397. Remedy: Verify parameters P0295/P0296 configurations match rating plate. Set P0397 to 0 to disable if required. |
| F0228 Telegram Reception Timeout Indicates fault in the serial communication. The equipment stopped receiving valid serial telegrams for a period longer than the setting in P0314. | Cause:
Remedy: Check serial communication cables, connectors, and shield grounding lines. Ensure the master's polling interval is shorter than parameter P0314, or disable this timeout check in parameter P0314. Inspect the pulse feedback loop cabling. |
| F0700 Remote HMI Communication Fault No communication with remote HMI, but there is speed command or reference for this source. | Cause:
Remedy: Check parameter P0312 to verify that the HMI communication interface is configured correctly. Reconnect or replace the HMI serial cable. |
| F0709 SoftPLC Application Stopped SoftPLC application not running. | Cause:
Remedy: Verify parameter configurations for P1000 and P1001. Upload a compatible version of the SoftPLC application. |
| F0710 Size of the SoftPLC Application The size of the SoftPLC user’s program exceeded the maximum memory capacity. | Cause:
Remedy: Check the overall project size. Optimize and compress the SoftPLC user program blocks to stay within the permitted memory limits. |
| F0711 Fault on SoftPLC Application Fault found in SoftPLC user’s program. | Cause:
Remedy: Reload the user program onto the flash memory. Optimize program execution routines to prevent scan cycle timeouts. |
| F0712 Illegal SPLC Download This fault occurs when trying to load the user application while the resident is running. After the occurrence of F0712, the SoftPLC application selection is changed from resident to user – P1003 from 1 to 0. | Cause:
Remedy: Stop the active resident application before attempting to download a new user SoftPLC application. Verify settings in parameters P1000 and P1003. |
| F0761 Low Level of the Process Variable of the Internal PID Controller Fault that indicates the process variation of the internal PID controller has a low value. | Cause:
Remedy: Verify the process feedback sensor. Adjust parameters P1024 (threshold) and P1025 (delay time) if necessary. |
| F0763 High Level in the Process Variable of the Internal PID Controller Fault that indicates the process variation of the main PID controller has a high value. | Cause:
Remedy: Check for high limits in the process line (overpressure, high flow, etc.). Verify parameters P1026 and P1027. |
| F0767 Dry Pump Detected Fault that indicates the dry pump condition was detected for the pump driven by the inverter. | Cause: Parameter P1033 is programmed for 2, the motor speed is above the speed programmed in P1034, and the motor torque has remained below the value programmed in P1035 for the time programmed in P1036. Remedy: Verify the fluid flow to the pump and check for blockages or dry lines. Verify the parameter configurations for P1033, P1034, P1035, and P1036. |
| F0769 Broken Belt Detected Fault that indicates the broken belt condition was detected for the motor driven by the inverter. | Cause: Parameter P1037 is programmed for 2, the motor speed is above the speed programmed in P1038, and the motor torque has remained below the value programmed in P1039 for the time programmed in P1040. Remedy: Check the mechanical coupling belt/pulley state. Verify the parameter configurations for P1037, P1038, P1039, and P1040. |
| F0771 Filter Maintenance Fault that indicates the need of replacing the system filter. | Cause: Parameter P1041 is programmed for 2, and the total motor operation time shown in P1043 is above the value programmed in P1042. Remedy: Perform scheduled maintenance to replace the system filter. Reset the elapsed timer if required. |
| F0787 Low Level of the Process Variable of the External PID Controller Fault that indicates the feedback of the external PID controller has a low value. | Cause: Parameter P1055 is programmed for 2, and the process variable of the external PID controller remained below the value programmed in P1056 for the duration set in P1057. Remedy: Verify the process feedback loops and verify configurations in parameters P1055, P1056, and P1057. |
| F0789 High Level of the Process Variable of the External PID Controller Fault that indicates the feedback of the external PID controller has a high value. | Cause: Parameter P1055 is programmed for 2, and the process variable of the external PID controller remained above the value programmed in P1058 for the duration set in P1059. Remedy: Verify process line sensors. Check parameter thresholds set in P1055, P1058, and P1059. |
How to Clear & Reset WEG CFW501 Drive Faults
- Keypad Reset: Press the red O (Stop / Reset) key on the front keypad. If operating in Remote mode (REM), press the LOC/REM key to switch to Local mode before attempting a manual reset.
- Digital Input Reset (DI): If configured in parameters P0263 to P0266 (DI1 to DI4 function) for “Fault Reset” (option 8 / Reset), send a momentary +24 VDC pulse to the assigned terminal.
- BMS & Fieldbus Reset: Set Bit 7 (Fault Reset) from `0` to `1` in the Control Word (parameter P0682) via built-in BACnet MS/TP, Metasys N2, or Modbus RTU communications over RS-485.
- SuperDrive G2 PC Software: Connect via the USB / RS-485 interface using WEG SuperDrive G2 or WLP software, navigate to the diagnostic monitor, and trigger the “Fault Reset” function.
- AC Power Cycle: Disconnect line power to the drive, wait until the display screen and all LED indicators turn off completely (approx. 5 minutes for capacitor discharge), and restore mains power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC link bus voltage measures strictly below 50VDC across terminals [+DC / -DC] or [UDC+ / UDC-] before inspecting motor cables, removing protective covers, or touching terminals U, V, and W on the WEG CFW501 drive.