WEG CFW701 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW701 HVAC-R variable frequency drive series. Search or filter through the complete fault code directory below.

Dedicated HVAC-R Drive Power: 1.1 to 132 kW (1.5 to 175 HP) Scalar V/F & VVW Voltage Vector
Power Range 1.1 – 132 kW (1.5 – 175 HP)
Supply Voltage 200–240V / 380–480V / 500–600V AC
Control Modes Scalar V/F & VVW Vector (Vectrue®)
Operator Interface HVAC Graphic HMI (Backlit Display)

Complete WEG CFW701 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type F006, F021, or Overcurrent).

Fault / Alarm and MeaningCause and Remedy
F0006

Input Voltage Imbalance or Phase Loss

The mains voltage imbalance is too high or phase loss at the supply line has occurred.

Cause:



  • A Phase Loss at the inverter input.

  • The input voltage imbalance is > 5%.




Note: This fault may not occur if the load at the motor shaft is too low or nonexistent. Parameter P0357 sets the time for the trip, and P0357 = 0 disables this fault.



Remedy:


Verify input mains connections and check input fuses. Check the line voltages. Setting parameter P0357 to 0 disables this fault check.
F0021

DC Link Undervoltage

A DC link undervoltage condition has occurred.

Cause:


The input voltage is too low and the DC link voltage dropped below the minimum permitted value (monitor the parameter P0004):

  • Ud < 223 V: For 200 / 240 V three-phase input voltage.

  • Ud < 170 V: For 200 / 240 V single-phase input voltage (models CFW701XXXXS2 or CFW701XXXXB2, P0296 = 0).

  • Ud < 385 V: For 380 V input voltage (P0296 = 1).

  • Ud < 405 V: For 400 / 415 V input voltage (P0296 = 2).

  • Ud < 446 V: For 440 / 460 V input voltage (P0296 = 3).

  • Ud < 487 V: For 480 V input voltage (P0296 = 4).

  • Ud < 530 V: Input voltage 500 / 525 V (P0296 = 5).

  • Ud < 580 V: Input voltage 550 / 575 V (P0296 = 6).

  • Ud < 605 V: Input voltage 600 V (P0296 = 7).

  • Phase loss at the inverter input.

  • Pre-charge circuit failure.

  • Parameter P0296 was set to a value higher than the power supply rated voltage.





Remedy:


Monitor parameter P0004. Check physical input terminals. Ensure correct configuration of parameter P0296 to match incoming rated mains voltage. Check pre-charge circuit paths.
F0022

DC Link Overvoltage

A DC link overvoltage condition has occurred.

Cause:


Too high input voltage, resulting in a DC link voltage higher than the maximum permitted value:

  • Ud > 400 V: For 220 / 230 V models (P0296 = 0).

  • Ud > 800 V: For 380 / 480 V models (P0296 = 1, 2, 3, or 4).

  • Ud > 1000 V: For 500 / 600 V models (P0296 = 5, 6 or 7).

  • The inertia of the driven-load is too high or the deceleration time is too short.

  • The parameter P0151, P0153, or P0185 setting is too high.





Remedy:


Check incoming supply voltage. Adjust deceleration ramp time or reduce load inertia. Check values in parameters P0151, P0153, or P0185.
A0046

High Load at the Motor

It is the motor overload alarm.

Cause:



  • The settings of parameters P0156, P0157, and P0158 are too low for the used motor.

  • There is excessive load at the motor shaft.




Note: This alarm can be disabled by setting parameter P0348 = 0 or 2.



Remedy:


Verify parameters P0156, P0157, and P0158. Check motor shaft for mechanical overload. Adjust parameter P0348 to 0 or 2 if desired to disable.
A0047

IGBT Overload Alarm

It is the IGBT overload alarm.

Cause:



  • The inverter output current is too high.




Note: This alarm can be disabled by setting parameter P0350 = 0 or 2.



Remedy:


Verify motor operating loads and current. Setting P0350 to 0 or 2 disables this alarm.
F0048

IGBT Overload Fault

It is the IGBT overload fault.

Cause:



  • The inverter output current is too high.





Remedy:


Analyze load conditions to prevent high current output. Check drive/inverter capacity matching.
A0050

IGBT High Temperature

The NTC temperature sensors located in the IGBTs detected a high temperature alarm.

Cause:



  • High surrounding air temperature (>50 °C (122 °F)) and high output current.

  • Blocked or defective cooling fan.

  • Very dirty heatsink.




Note: This alarm can be disabled by setting parameter P0353 = 2 or 3.



Remedy:


Clean the heatsink fins. Verify fan operation. Check surrounding ambient temperature. Alarm can be bypassed by setting parameter P0353 to 2 or 3.
F0051

IGBT Overtemperature

The NTC temperature sensors located in the IGBTs detected a high temperature fault.

Cause:



  • High surrounding air temperature (>50 °C (122 °F)) and high output current.

  • Blocked or defective cooling fan.

  • Very dirty heatsink.





Remedy:


Clean the heatsink fins. Inspect the cooling fan and replace if defective. Check ambient room temperature.
F0070

Overcurrent/Short-circuit

An overcurrent or a short-circuit at the output, at the DC link, or at the braking resistor, has occurred.

Cause:



  • Short-circuit between two motor phases.

  • Short-circuit between the dynamic braking resistor connection cables.

  • Shorted IGBT modules.





Remedy:


Inspect motor terminals and cables for short circuits. Check braking resistor wiring. Verify physical state of the output IGBT stages.
F0071

Output Overcurrent

An output overcurrent has occurred.

Cause:



  • Excessive load inertia or too short acceleration ramp.

  • Parameters P0135, or P0169 and P0170 settings are too high.





Remedy:


Adjust acceleration ramp to be longer, or reduce load inertia. Adjust parameters P0135, P0169, and P0170.
F0072

Motor Overload

The motor overload protection has tripped.

Cause:



  • The settings of parameters P0156, P0157, and P0158 are too low for the used motor.

  • There is excessive load at the motor shaft.




Note: This fault can be disabled by setting parameter P0348 = 0 or 3.



Remedy:


Verify motor rated currents and adjust parameters P0156, P0157, and P0158. Check mechanical load on shaft. Setting parameter P0348 to 0 or 3 disables this fault.
F0074

Ground Fault

A ground fault occurred either in the cable between the inverter and the motor or in the motor itself.

Cause:



  • Short-circuit to the ground in one or more output phases.

  • Motor cable capacitance is too large, resulting in current peaks at the output.




Note: This fault can be disabled by setting parameter P0343 = 0.



Remedy:


Verify insulation of motor and output cabling phases. If cable is extremely long, add output reactor or set P0343 to 0.
F0076

Motor Current Unbalance

Fault of motor current unbalance.

Cause:



  • Loose connection or broken wiring between the motor and inverter connection.

  • Vector control with wrong orientation.

  • Vector control with encoder, encoder wiring or encoder motor connection inverted.




Note: This fault can be disabled by setting parameter P0342 = 0.



Remedy:


Verify all output cable connections between inverter output and motor terminal box. Check vector control tuning and orientation. Verify encoder cables and phasing. Setting P0342 to 0 disables this fault.
F0078

Motor Overtemperature

Fault related to the PTC temperature sensor installed in the motor.

Cause:



  • Excessive load at the motor shaft.

  • Severe duty cycle (too many starts / stops per minute).

  • Too high surrounding air temperature.

  • Loose connection or short-circuit (resistance < 100 Ω) in the wiring connected to the motor thermistors.

  • Not installed motor thermistors.

  • Blocked motor shaft.




Note: It can be disabled by setting parameter P0351 = 0 or 3. An analog input and an analog output must be set for the PTC function.



Remedy:


Assess motor mechanical status. Check start/stop cycles. Verify thermistor cabling and loop resistance (measure to verify > 100 Ω). Check parameter P0351 settings.
F0080

CPU Watchdog

Microcontroller watchdog fault.

Cause:



  • High electrical noise.





Remedy:


Optimize grounding and cable paths. Ensure control cables are separated from high-current power lines.
F0084

Auto-Diagnosis Fault

Auto-Diagnosis Fault.

Cause:



  • Defect in the inverter internal circuitry.

  • Firmware incompatible with an accessory.





Remedy:


Inspect control board to power pack connections. Verify component and firmware compatibility. Contact technical support if an internal hardware defect is suspected.
A0090

External Alarm

External alarm monitored through a digital input.

Cause:



  • A digital input (DI1 to DI8) programmed for “No external alarm” is open.




Note: It is necessary to program a digital input for “No external alarm”.



Remedy:


Verify terminal wiring on DI1 through DI8. Secure screw contacts.
F0091

External Fault

External fault monitored through a digital input.

Cause:



  • A digital input (DI1 to DI8) programmed for “No external fault” is open.




Note: It is necessary to program a digital input for “No external fault”.



Remedy:


Verify terminal wiring loops to the assigned digital inputs. Ensure signal switches are functioning.
A0098

Activate General Enable

General Enable signal is missing during the self-tuning.

Cause:



  • The digital input programmed for “General Enable” is open.





Remedy:


Check the digital input assigned to keep the drive enabled during the self-tuning routine.
F0099

Invalid Current Offset

The current measurement circuit is presenting an abnormal value for null current.

Cause:



  • Defect in the inverter internal circuitry.





Remedy:


This typically indicates hardware damage. Replace the power module or contact technical service.
A0110

High Motor Temperature

Fault detected through PTC type temperature sensors installed in the motor.

Cause:



  • Excessive load at the motor shaft.

  • Severe duty cycle (too many starts / stops per minute).

  • Too high surrounding air temperature.

  • Not installed motor thermistors.

  • Blocked motor shaft.




Note: It can be disabled by setting parameter P0351 = 0 or 2. An analog input and an analog output must be set for the PTC function.



Remedy:


Verify the mechanical motor load and operating conditions. Verify thermistor cabling and parameters.
A128

Serial Communication Timeout

It indicates that the inverter stopped receiving valid telegrams during a certain period.

Cause:



  • Check the wiring and the ground installation.

  • The inverter has not received any new message within the time interval set in parameter P0314.




Note: It can be disabled by setting parameter P0314 = 0.0 s.



Remedy:


Check serial connections, shield grounding, and wiring. Adjust master polling times, or disable timeout by modifying P0314.
F0150

Motor Overspeed

Overspeed fault.

Cause:



  • Wrong settings of parameters P0161 and/or P0162.

  • Problem with hoist-type loads (mechanical drag).




Note: It trips when the actual speed exceeds the value of P0134 x (100 % + P0132) / 100% for more than 20 ms.



Remedy:


Adjust overspeed limit parameters P0161 and P0162. For lifting or hoist applications, verify brake coordination and torque limits.
F0151

FLASH Memory Module Fault

FLASH Memory Module (MMF-01) fault.

Cause:



  • Defective FLASH memory module.

  • Incorrect or loose physical connection of the FLASH memory module.





Remedy:


Verify the physical slot connection of the FLASH memory card. Replace the memory module if card is damaged.
A0152

High Internal Air Temperature

This alarm indicates that the internal air temperature is too high.

Cause:



  • High surrounding air temperature (>50 °C (122 °F)) and high output current.

  • Defective internal cooling fan (if existent).

  • High temperature (> 45 ºC) inside the cabinet.




Note: It can be disabled by setting parameter P0353 = 1 or 3.



Remedy:


Ensure enclosure or cabinet ventilation fan is operating correctly. Clear blockages from airflow grilles. Check parameter P0353.
F0153

Internal Air Overtemperature

It indicates internal air overtemperature fault.

Cause:



  • High surrounding air temperature (>50 °C (122 °F)) and high output current.

  • Defective internal cooling fan (if existent).





Remedy:


Shut down the inverter and check enclosure ventilation. Verify cooling fan function.
F0156

Undertemperature

The temperature sensors located in the IGBTs or in the rectifier detected a low temperature, below -30 °C ( -22 °F), fault.

Cause:



  • Surrounding air temperature ≤ -30 °C (-22 °F).





Remedy:


Check the installation environment. Provide heating element control inside the cabinet for operation in cold environments.
F0157

Parameter Table Data Loss

There was a problem during the initialization, during the parameter table loading routine. Some recent parameter modifications may have been lost.

Cause:



  • The control was switched off very fast while a parameter was being modified.





Remedy:


Verify current parameter modifications. Avoid switching off the control board too quickly during parameter editing.
F0158

Parameter Table Fault

There was a problem during the initialization, during the parameter table loading routine. All the parameters were lost and the factory settings were loaded.

Cause:



  • Firmware updating fault.

  • Defective control board.





Remedy:


Check control unit card condition. Re-upload or re-verify firmware version.
A0159

Incompatible HMI

Incompatible HMI.

Cause:



  • HMI of another product being used.





Remedy:


Ensure the correct HMI model designed for the CFW701 series is installed.
F0160

Safety Stop Relays

Safety stop relay fault.

Cause:



  • One of the safety relays is defective.

  • It does not have +24 V applied to its coil.





Remedy:


Verify +24 V loop is applied correctly to the safety relays coil. Replace safety module card if internal relay is defective.
A0163

AI1 Broken Cable

It indicates that the AI1 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range.

Cause:



  • Broken AI1 current loop cable.

  • Bad contact at the signal connection to the terminal strip.





Remedy:


Inspect analogue input 1 loop cabling for breaks. Tighten screw terminal contacts.
F0078

Motor Overtemperature

Fault related to the PTC temperature sensor installed in the motor.

Cause:



  • Excessive load at the motor shaft.

  • Severe duty cycle (too many starts / stops per minute).

  • Too high surrounding air temperature.

  • Loose connection or short-circuit (resistance < 100 Ω) in the wiring connected to the motor thermistors.

  • Not installed motor thermistors.

  • Blocked motor shaft.




Note: It can be disabled by setting parameter P0351 = 0 or 3. An analog input and an analog output must be set for the PTC function.



Remedy:


Check the mechanical load on the motor shaft and resolve any blockages. Reduce high start/stop duty cycles if possible. Measure thermistor wire resistance to ensure it is > 100 Ω. Verify proper installation and wiring.
F0080

CPU Watchdog

Microcontroller watchdog fault.

Cause:



  • High electrical noise.





Remedy:


Optimize grounding and cable paths. Ensure control cables are separated from high-current power lines.
F0084

Auto-Diagnosis Fault

Auto-Diagnosis Fault.

Cause:



  • Defect in the inverter internal circuitry.

  • Firmware incompatible with an accessory.





Remedy:


Verify internal control board and power pack connections. Update control unit firmware if needed. Contact technical support if a hardware defect is suspected.
A0090

External Alarm

External alarm monitored through a digital input.

Cause:



  • A digital input (DI1 to DI8) programmed for "No external alarm" is open.




Note: It is necessary to program a digital input for “No external alarm”.



Remedy:


Check digital input terminal loops and secure connections to prevent open circuit alarms.
F0091

External Fault

External fault monitored through a digital input.

Cause:



  • A digital input (DI1 to DI8) programmed for “No external fault” is open.




Note: It is necessary to program a digital input for “No external fault”.



Remedy:


Check digital input terminal loops and ensure external switches are not triggering open circuits.
A0098

Activate General Enable

General Enable signal is missing during the self-tuning.

Cause:



  • The digital input programmed for "General Enable" is open.





Remedy:


Check and close the digital input assigned to keep the drive enabled during the self-tuning routine.
F0099

Invalid Current Offset

The current measurement circuit is presenting an abnormal value for null current.

Cause:



  • Defect in the inverter internal circuitry.





Remedy:


Inspect internal current sensors or control board circuitry. Hardware replacement may be required.
A0110

High Motor Temperature

Fault detected through PTC type temperature sensors installed in the motor.

Cause:



  • Excessive load at the motor shaft.

  • Severe duty cycle (too many starts / stops per minute).

  • Too high surrounding air temperature.

  • Not installed motor thermistors.

  • Blocked motor shaft.




Note: It can be disabled by setting parameter P0351 = 0 or 2. An analog input and an analog output must be set for the PTC function.



Remedy:


Check motor load and cooling. Verify that thermistors are installed and parameters are set.
A128

Serial Communication Timeout

It indicates that the inverter stopped receiving valid telegrams during a certain period.

Cause:



  • Check the wiring and the ground installation.

  • The inverter has not received any new message within the time interval set in parameter P0314.




Note: It can be disabled by setting parameter P0314 = 0.0 s.



Remedy:


Check serial connections, shield grounding, and wiring. Adjust master polling times, or disable timeout by modifying P0314.
F0150

Motor Overspeed

Overspeed fault.

Cause:



  • Wrong settings of parameters P0161 and/or P0162.

  • Problem with hoist-type loads (mechanical drag).




Note: It trips when the actual speed exceeds the value of P0134 x (100% + P0132) / 100% for more than 20 ms.



Remedy:


Check and adjust parameters P0161 and P0162. For hoist applications, ensure braking logic is aligned.
F0151

FLASH Memory Module Fault

FLASH Memory Module (MMF-01) fault.

Cause:



  • Defective FLASH memory module.

  • Check the connection of the FLASH memory module.





Remedy:


Verify physical connection of the MMF-01 card. Replace the memory card if defective.
A0152

High Internal Air Temperature

This alarm indicates that the internal air temperature is too high.

Cause:



  • High surrounding air temperature (>50 °C (122 °F)) and high output current.

  • Defective internal cooling fan (if existent).

  • High temperature (> 45 ºC) inside the cabinet.




Note: It can be disabled by setting parameter P0353 = 1 or 3.



Remedy:


Improve enclosure ventilation. Replace failed internal cooling fans. Set parameter P0353 to 1 or 3 if bypass is desired.
F0153

Internal Air Overtemperature

It indicates internal air overtemperature fault.

Cause:



  • High surrounding air temperature (>50 °C (122 °F)) and high output current.

  • Defective internal cooling fan (if existent).





Remedy:


Check and clear air grilles or replace defective fans. Reduce room/enclosure temperature.
F0156

Undertemperature

The temperature sensors located in the IGBTs or in the rectifier detected a low temperature, below -30 °C ( -22 °F), fault.

Cause:



  • Surrounding air temperature ≤ -30 °C (-22 °F).





Remedy:


Check the installation environment. Provide heating element control inside the cabinet for operation in cold environments.
F0157

Parameter Table Data Loss

There was a problem during the initialization, during the parameter table loading routine. Some recent parameter modifications may have been lost.

Cause:



  • The control was switched off very fast while a parameter was being modified.





Remedy:


Check parameter adjustments. Avoid powering down the control board immediately during configuration modifications.
F0158

Parameter Table Fault

There was a problem during the initialization, during the parameter table loading routine. All the parameters were lost and the factory settings were loaded.

Cause:



  • Firmware updating fault.

  • Defective control board.





Remedy:


Verify control unit board condition. Re-upload or re-verify firmware version.
A0159

Incompatible HMI

Incompatible HMI.

Cause:



  • HMI of another product being used.





Remedy:


Install the designated HMI model for the CFW701 series.
F0160

Safety Stop Relays

Safety stop relay fault.

Cause:



  • One of the relays is defective.

  • It does not have +24 V applied to its coil.





Remedy:


Verify +24 V loop is applied correctly to the safety relays coil. Replace safety module card if internal relay is defective.
A0163

AI1 Broken Cable

It indicates that the AI1 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range.

Cause:



  • Broken AI1 current loop cable.

  • Bad contact at the signal connection to the terminal strip.





Remedy:


Inspect analogue input 1 loop cabling for breaks. Tighten screw terminal contacts.
A0164

AI2 Broken Cable

It indicates that the AI2 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range.

Cause:



  • Broken AI2 current loop cable.

  • Bad contact at the signal connection to the terminal strip.





Remedy:


Inspect analogue input 2 loop cabling for breaks. Tighten screw terminal contacts.
A0165

AI3 Broken Cable

It indicates that the AI3 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range.

Cause:



  • Broken AI3 current loop cable.

  • Bad contact at the signal connection to the terminal strip.





Remedy:


Inspect analogue input 3 loop cabling for breaks. Tighten screw terminal contacts.
A0168

Speed Error too High

Difference between speed reference and effective speed greater than the setting in P0360.

Cause:



  • Inverter in torque current limitation.





Remedy:


Ensure the motor is not overloaded or stalled. Check torque limits in P0360.
F0169

Speed Error too High

Difference between speed reference and effective speed greater than the setting in P0360 for longer than P0361.

Cause:



  • Inverter in torque current limitation for too long.





Remedy:


Ensure the motor is not locked or mechanically bound. Check limits set in P0360 and P0361.
A0170

Safety Stop

The Safety Stop function is active.

Cause:



  • The CFW701 went to the STO state.





Remedy:


Check the external safety circuits. Ensure STO commands are released for normal operation.
A0177

Fan Replacement

Fan replacement alarm (P0045 > 50000 hours).

Cause:



  • The heatsink fan maximum number of operating hours has been reached.




Note: This function can be disabled by setting parameter P0354 = 0.



Remedy:


Perform preventive fan replacement maintenance.
F0179

Heatsink Fan Speed Fault

This fault indicates a problem with the heatsink fan.

Cause:



  • Dirt on the blades and in the bearings of the fan.

  • Defective fan.

  • Defective fan power supply connection.




Note: This function can be disabled by setting parameter P0354 = 0.



Remedy:


Check and clean the fan module. Replace if damaged.
F0182

Pulse Feedback Fault

It indicates a fault in the output pulses feedback.

Cause:



  • Defect in the inverter internal circuitry.





Remedy:


Inspect internal control unit feedback circuits. Hardware replacement may be required.
F0183

IGBT Overload + Temperature

Overtemperature related to the IGBT overload protection.

Cause:



  • Too high inverter surrounding temperature.

  • Operation with output frequencies < 10 Hz under overload conditions.





Remedy:


Verify ambient cooling path functionality. Avoid running the drive continuously below 10 Hz during high overload conditions.
F0185

Pre-Charge Contactor Fault

It indicates a fault at the pre-charge contactor.

Cause:



  • Defective pre-charge contactor.

  • Open command fuse.

  • Phase loss at the L1/R or L2/S input.

  • Incorrect setting for mechanical models “E” powered by the DC Link (parameter P0355 is set to 1).




Note: For those models should be set P0355 = 0.



Remedy:


Verify input phase lines and trace fuses. Check pre-charge contactor and correct parameters in P0355.
A0210

Drive in Bypass mode

Indicates that the drive is in Bypass mode.

Cause:



  • The digital input programmed for activating the Bypass mode is active.





Remedy:


Check digital input settings and external wiring assigned to Bypass mode activation.
A0211

Drive in Fire Mode

Indicates that the drive is in Fire Mode.

Cause:



  • The digital input programmed for activating the Fire Mode is active.





Remedy:


Check the status of the digital input assigned to activate the Fire Mode. Confirm that external switch logic is correct and not stuck in the active state.
F0228

Serial Communication Timeout

Cause:



  • Timeout on serial communication link.





Remedy:


Refer to the RS-232 / RS-485 Serial Communication Manual. Check cables, ground loops, and settings.
A0702

Disabled Inverter

Cause:



  • SoftPLC disabled state.





Remedy:


Refer to the SoftPLC Manual.
A0704 / A0706

Two Enabled Movements / Reference not Programmed for SoftPLC

Cause:



  • Multiple movements active or speed reference routing missing.





Remedy:


Verify SoftPLC program logic and configure reference parameters correctly.
F0711

Fault in the Execution of the SoftPLC

Fault in the execution of the SoftPLC.

Cause:



  • Incompatible applicative.

  • Fault during upload of the applicative.





Remedy:


Verify program compatibility. Attempt a fresh upload of the user application.
A0750

Programming AIx for Main PID Controller Feedback

It indicates to the user there is not analog input programmed for Main PID controller feedback.

Cause:



  • Parameter P0231 or P0236 or P0241 is not programmed in 5, 6 or 7.





Remedy:


Program the appropriate analog input parameter to option 5, 6, or 7.
A0752

Programming DIx for Main PID Controller Automatic/Manual Selection

It indicates to the user there is not digital input programmed for Main PID controller Automatic/Manual selection.

Cause:



  • Parameter P0263 or P0264 or P0265 or P0266 or P0267 or P0268 or P0269 or P0270 is not programmed in 20.





Remedy:


Program the appropriate digital input parameter to option 20.
A0754

Programming Local Reference (P0221) for SoftPLC

It indicates to the user that the origin of the speed reference in the Local situation is not programmed for SoftPLC.

Cause:



  • The main PID controller is enabled (P1017 in 1 or 2), the inverter is running in the LOCAL situation, but parameter P0221 is not programmed to 7.





Remedy:


Set parameter P0221 to 7 if utilizing the PID controller in local mode.
A0756

Programming Remote Reference (P0222) for SoftPLC

It indicates to the user that the origin of the speed reference in the Remote situation is not programmed for SoftPLC.

Cause:



  • The main PID controller is enabled (P1017 in 1 or 2), the inverter is running in the REMOTE situation, but parameter P0222 is not programmed to 7.





Remedy:


Set parameter P0222 to 7 if utilizing the PID controller in remote mode.
A0758

Programming Indirect Engineering Unit 4 (P0516) for Hz or rpm

It indicates to the user that the engineering unit parameters for motor speed is not programmed for Hz or rpm.

Cause:



  • Parameter P0516 is not programmed in 13 (Hz) or 3 (rpm).





Remedy:


Configure parameter P0516 to option 13 (Hz) or 3 (rpm).
A0760

Low Level for Main PID Controller Feedback

It indicates to the user that the Main PID controller feedback is low.

Cause:



  • Parameter P1030 is programmed in 1, and the Main PID controller feedback value is remaining below the value programmed in P1031 for the time programmed in P1032.





Remedy:


Check feedback loop lines. Verify parameters P1031 (threshold) and P1032 (delay).
F0761

Low Level for Main PID Controller Feedback

It indicates to the user that the Main PID controller feedback is low.

Cause:



  • Parameter P1030 is programmed in 2, and the Main PID controller feedback value is remaining below the value programmed in P1031 for the time programmed in P1032.





Remedy:


Verify loop line pressure/flow. Check values set in parameters P1031 and P1032.
A0762

High Level for Main PID Controller Feedback

It indicates to the user that the Main PID controller feedback is high.

Cause:



  • Parameter P1030 is programmed in 1, and the Main PID controller feedback value is remaining above the value programmed in P1033 for the time programmed in P1034.





Remedy:


Inspect process line for high limits. Verify values set in parameters P1033 and P1034.
F0763

High Level for Main PID Controller Feedback

It indicates to the user that the Main PID controller feedback is high.

Cause:



  • Parameter P1030 is programmed in 2, and the Main PID controller feedback value is remaining above the value programmed in P1033 for the time programmed in P1034.





Remedy:


Inspect process line for high limits. Verify values set in parameters P1033 and P1034.
A0764

CFW701 in Sleep Mode

It indicates to the user that the CFW701 frequency inverter is in Sleep mode.

Cause:



  • Main PID controller is enabled and in Automatic mode, and the motor speed is remaining below the speed value programmed in P1036 for the time programmed in P1037.





Remedy:


Informational alarm status indicating sleep mode has engaged. To adjust this behavior, modify parameters P1036 (sleep speed) or P1037 (sleep delay time).
A0766

Dry Pump Detected

It indicates to the user that the dry pump condition was detected for the pump driven by CFW701 frequency inverter.

Cause:



  • Parameter P1042 is programmed in 1, the pump is running faster than the speed programmed in P1043, and the motor torque is remaining below the torque value programmed in P1044 for the time programmed in P1045.





Remedy:


Verify fluid flow to the pump. Verify configurations for parameters P1042, P1043, P1044, and P1045.
F0767

Dry Pump Detected

It indicates to the user that the dry pump condition was detected for the pump driven by CFW701 frequency inverter.

Cause:



  • Parameter P1042 is programmed in 2, the pump is running faster than the speed programmed in P1043, and the motor torque is remaining below the torque value programmed in P1044 for the time programmed in P1045.





Remedy:


Verify fluid flow to the pump. Verify configurations for parameters P1042, P1043, P1044, and P1045.
A0768

Broken Belt Detected

It indicates to the user that the broken belt condition was detected for the motor driven by CFW701 frequency inverter.

Cause:



  • Parameter P1046 is programmed in 1, the motor is running faster than the speed programmed in P1047, and the motor torque is remaining below the torque value programmed in P1048 for the time programmed in P1049.





Remedy:


Check the mechanical coupling belt/pulley state. Verify the parameter configurations for P1046, P1047, P1048, and P1049.
F0769

Broken Belt Detected

It indicates to the user that the broken belt condition was detected for the motor driven by CFW701 frequency inverter.

Cause:



  • Parameter P1046 is programmed in 2, the motor is running faster than the speed programmed in P1047, and the motor torque is remaining below the torque value programmed in P1048 for the time programmed in P1049.





Remedy:


Check the mechanical coupling belt/pulley state. Verify the parameter configurations for P1046, P1047, P1048, and P1049.
A0770

Filter Maintenance

It indicates to the user that the need to change the filter system.

Cause:



  • Parameter P1050 is programmed in 1, and the total motor operation time shown in P1052 is greater than the time programmed in P1051.





Remedy:


Perform preventive system filter replacement. Reset the elapsed timer if required.
F0771

Filter Maintenance

It indicates to the user that the need to change the filter system.

Cause:



  • Parameter P1050 is programmed in 2, and the total motor operation time shown in P1052 is greater than the time programmed in P1051.





Remedy:


Perform preventive system filter replacement. Reset the elapsed timer if required.
A0780

Programming AIx for External PID Controller 1 Feedback

It indicates to the user there is not analog input programmed for External PID controller 1 feedback.

Cause:



  • Parameter P0231 or P0236 or P0241 is not programmed to option 8.





Remedy:


Set parameter P0231 or P0236 or P0241 to option 8 to configure process feedback.
A0782

Programming DIx for External PID Controller 1 Automatic/Manual Selection

It indicates to the user there is not digital input programmed for External PID controller 1 Automatic/Manual selection.

Cause:



  • Parameter P0263 or P0264 or P0265 or P0266 or P0267 or P0268 or P0269 or P0270 is not programmed to option 21.





Remedy:


Set parameter P0263, P0264, P0265, or P0266 to option 21.
A0784

Programming AOx for External PID Controller 1 Output

It indicates to the user there is not analog output programmed for External PID controller 1 output.

Cause:



  • Parameter P0251 or P0254 is not programmed to option 16.





Remedy:


Configure parameter P0251 or P0254 to option 16 to set the analog output target.
A0786

Low Level for External PID Controller 1 Feedback

It indicates to the user that the External PID controller 1 feedback is low.

Cause:



  • Parameter P1075 is programmed in 1, and the External PID controller 1 feedback value is remaining below the value programmed in P1076 for the time programmed in P1077.





Remedy:


Check the process feedback sensor and loop line. Verify configurations in parameters P1075, P1076, and P1077.
F0787

Low Level for External PID Controller 1 Feedback

Cause:


Parameter P1075 is programmed in 2 and the External PID controller 1 Feedback value is remaining below the value programmed in P1076 for the time programmed in P1077.



Remedy:


Check the physical process line and feedback loop sensors. Verify the parameter configurations for P1075, P1076, and P1077.
A0788

High Level for External PID Controller 1 Feedback

Cause:


Parameter P1075 is programmed in 1 and the External PID controller 1 feedback value is remaining above the value programmed in P1078 for the time programmed in P1079.



Remedy:


Verify that the process pressure, level, or variables are within expected system parameters. Check the sensor output and parameter values for P1075, P1078, and P1079.
F0789

High Level for External PID Controller 1 Feedback

Cause:


Parameter P1075 is programmed in 2 and the External PID controller 1 feedback value is remaining above the value programmed in P1078 for the time programmed in P1079.



Remedy:


Verify that the process pressure, level, or variables are within expected system parameters. Check the sensor output and parameter values for P1075, P1078, and P1079.
A0790

Programming AIx for External PID Controller 2 Feedback

Cause:


It indicates to the user there is not analog input programmed for External PID controller 2 feedback. Parameter P0231 or P0236 or P0241 is not programmed in 9.



Remedy:


Configure the designated analog input by setting parameter P0231, P0236, or P0241 to option 9.
A0792

Programming DIx for External PID Controller 2 Automatic/Manual Selection

Cause:


It indicates to the user there is not digital input programmed for External PID controller 2 Automatic/Manual selection. Parameter P0263 or P0264 or P0265 or P0266 or P0267 or P0268 or P0269 or P0270 is not programmed in 22.



Remedy:


Configure the digital input by setting parameter P0263, P0264, P0265, P0266, P0267, P0268, P0269, or P0270 to option 22.
A0794

Programming AOx for External PID Controller 2 Output

Cause:


It indicates to the user there is not analog output programmed for External PID controller 2 output. Parameter P0251 or P0254 is not programmed in 17.



Remedy:


Configure the analog output by setting parameter P0251 or P0254 to option 17.
A0796

Low Level for External PID Controller 2 Feedback

Cause:


Parameter P1095 is programmed in 1 and the External PID controller 2 feedback value is remaining below the value programmed in P1096 for the time programmed in P1097.



Remedy:


Check the physical process line and feedback loop sensors. Verify the parameter configurations for P1095, P1096, and P1097.
F0797

Low Level for External PID Controller 2 Feedback

Cause:


Parameter P1095 is programmed in 2 and the External PID controller 2 feedback value is remaining below the value programmed in P1096 for the time programmed in P1097.



Remedy:


Check the physical process line and feedback loop sensors. Verify the parameter configurations for P1095, P1096, and P1097.
A0798

High Level for External PID Controller 2 Feedback

Cause:


Parameter P1095 is programmed in 1 and the External PID controller 2 feedback value is remaining above the value programmed in P1098 for the time programmed in P1099.



Remedy:


Verify that the process pressure, level, or variables are within expected system parameters. Check the sensor output and parameter values for P1095, P1098, and P1099.
F0799

High Level for External PID Controller 2 Feedback

Cause:


Parameter P1095 is programmed in 2 and the External PID controller 2 feedback value is remaining above the value programmed in P1098 for the time programmed in P1099.



Remedy:


Verify that the process pressure, level, or variables are within expected system parameters. Check the sensor output and parameter values for P1095, P1098, and P1099.
Capacitance Ground Fault

Diagnostic Warning Note (1)

Cause:


Very long motor cables, with more than 100 m (328.08 ft), present a high parasitic capacitance to the ground. The circulation of a leakage current through this capacitance may cause the activation of the ground fault circuit, and consequently an F0074 trip immediately after the inverter enabling.



Remedy:


Reduce the switching frequency set in parameter P0297.
Conn Lost

HMI Communication Failure Warning

Cause:


A bad contact in the HMI cable, or electrical noise in the installation, can cause a failure in the communication between the HMI and the control board. In such cases, the operation through the HMI becomes impossible.



Remedy:


Inspect and clean the HMI cable connections. Minimize electrical noise in the installation by rerouting cables or adding shielding.

How to Clear & Reset WEG CFW701 Drive Faults

  1. Keypad Reset (O Key): Press the red O (STOP / RESET) key or the dedicated Reset softkey on the graphic HMI keypad. If running under Remote (REM) status, switch to Local (LOC) control if keypad reset is restricted.
  2. Digital Input Reset (DI): If an available digital input (DI1 to DI8) is programmed as No Fault / Reset via parameters P0263 to P0270 = 12, cycle the terminal contact (pulse from open to closed).
  3. Auto-Reset Configuration: Parameter P0340 (Auto-Reset Time) can be programmed with an automatic reset delay along with P0341 (Number of Reset Attempts) to clear transient trips automatically.
  4. HVAC Fieldbus / Serial Reset: Transition Bit 7 (Fault Reset) from `0` to `1` in the Control Word via embedded RS-485 interfaces (BACnet MS/TP, Metasys N2, Modbus-RTU) or optional network modules.
  5. Power Cycle: Disconnect AC line supply voltage. Wait at least 10 minutes for the DC link capacitors to fully discharge and the graphic display to turn off completely before restoring line power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect incoming line power and wait at least 10 minutes for internal filter capacitors to discharge. Verify with a calibrated digital multimeter that intermediate DC bus voltage across terminals [+UD] and [-UD] (or [BR]) measures strictly below 50VDC before inspecting motor leads U/T1, V/T2, W/T3 or removing terminal covers on the WEG CFW701 drive.