WEG CFW-08 Drive Fault Codes & Diagnostic Guide

Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW-08 variable frequency drive series. Search or filter through the complete fault code directory below.

General Purpose Micro Drive Power: 0.25 to 15 kW (0.33 to 20 HP) Scalar (V/f) & VVW Sensorless Vector
Power Range 0.25 – 15 kW (0.33 – 20 HP)
Supply Voltage 200–240V / 380–480V (1/3-Phase)
Control Modes Scalar (V/f) & VVW Vector
Operator Interface Integrated LED Keypad (HMI-CFW08)

Complete WEG CFW-08 Drive Fault Code Directory

Use the search box in the table below to quickly find your code (e.g., type E01, E04, or Overcurrent).

Fault Code & MeaningCause & Remedy

E00



Output Overcurrent

(between phases or between phase and ground)

Cause:

  • Short-circuit between two motor phases.

  • Short-circuit between ground and one or more output phases.

  • Motor cable capacitance to ground too high, causing peak current at the output.

  • Inertia of the load too high, or acceleration ramp too short.

  • P169 set too high.

  • Undue set of P136 and/or P137 (in V/F control).

  • Undue set of P178 and/or P409 (in vector control).

  • IGBT transistor module is short-circuited.




Remedy:
Check wiring for short circuits. Check motor insulation.

Adjust parameters P169, P136, P137, P178, or P409.

Increase acceleration time.



Note regarding long cables (>50m): High capacitance can cause E00. To fix:
1. Reduce switching frequency (P297).
2. Connect a load reactor in series with motor supply line (Refer to Section 8.16).



Reset Method: Power-on, Manual, Auto-reset, or DI.

E01



DC Link Overvoltage

Cause:

  • Power supply voltage too high (Ud > 410V for 200-240V models; Ud > 820V for 380-480V models).

  • Load inertia too high or deceleration ramp too short.

  • Setting of P151 too high.




Remedy:
Check input power supply voltage.

Increase deceleration ramp time.

Adjust P151 setting.



Reset Method: Power-on, Manual, Auto-reset, or DI.

E02



DC Link Undervoltage

Cause:
Power supply voltage too low (Ud < 200V for 200-240V models; Ud < 360V for 380-480V models). Read value in parameter P004.


Remedy:
Check input power supply voltage and connections.



Reset Method: Power-on, Manual, Auto-reset, or DI.

E04



Inverter Overtemperature

Cause:

  • Ambient temperature too high (>40°C).

  • Output current too high.

  • Blower locked or defective.

  • Blocked airflow.




Remedy:
Allow the inverter to cool down before trying to reset.

Check blower installed inside.

Check ambient temperature and ventilation.

For types with internal RFI-filters, check for internal airflow overtemperature.



Reset Method: Power-on, Manual, Auto-reset, or DI.

E05



Motor/Inverter Overload (Ixt Function)

Cause:

  • P156 set too low for the motor being used.

  • Motor is under an actual overload condition.




Remedy:
Adjust P156 setting.

Check motor load conditions.



Reset Method: Power-on, Manual, Auto-reset, or DI.

E06



External Fault

Cause:
Ani DI (DI3 and/or DI4) programmed for external fault detection is open (not connected to GND - XC1).


Remedy:
Check external wiring and connection to GND (XC1).



Reset Method: Power-on, Manual, Auto-reset, or DI.

E08



CPU Error (Watchdog)

Cause:
Electrical noise.


Remedy:
Check grounding and shielding to reduce electrical noise.



Reset Method: Power-on, Manual, Auto-reset, or DI.

E09



Program Memory Error (Checksum)

Cause:
Memory with corrupted values.


Remedy:
Contact WEG (Refer to section 7.3).



Reset Method: Contact WEG.

E10



Keypad Error

Cause:

  • Defective contact in the HMI-CFW08-RS cable.

  • Electrical noise in the installation (electromagnetic interference).




Remedy:
Check keypad cable connection.

Check installation for noise sources/shielding.



Reset Method: Power-on, Manual, Auto-reset, or DI.

E14



Self-Tuning Fault

Cause:

  • Motor is not connected to the inverter output.

  • Wrong motor connection (wrong voltage, lack of one phase).

  • The used motor is too small for the inverter (P401 < 0.3 x P295). Use V/F control.

  • The value of P409 (stator resistance) is too high for the used inverter.




Remedy:
Check motor connections.

Verify motor sizing compatibility.

Check P409 value.



Reset Method: Power-on or Manual.

E24



Programming Error

Cause:
Incompatible parameters were programmed.


Remedy:
Refer to table 5.1 to check parameter compatibility.



Reset Method: Automatically reset when parameters are changed.

E31



Keypad (HMI) Connection Fault

Cause:

  • Keypad cable disconnected.

  • Electrical noise in the installation.




Remedy:
Reconnect keypad cable.

Check for electromagnetic interference.



Reset Method: Automatically reset when communication is reestablished.

E41



Self-Diagnosis Fault

Cause:
Inverter power circuit is defective.


Remedy:
Contact WEG (Refer to section 7.3).



Reset Method: Contact WEG.

How to Clear & Reset WEG CFW-08 Drive Faults

  1. Keypad Reset (O Key): Press the red O (STOP / RESET) key on the integrated HMI keypad while the error code (e.g., E00 to E41) is flashing on the 4-digit display.
  2. Digital Input Reset (DI): If an available digital input (DI1 to DI4) is assigned to function No Error / Reset via parameters P263 to P266 = 12, cycle the corresponding contact input (pulse from open to closed).
  3. Auto-Reset Configuration: If automatic restart is desired, configure parameter P340 (Auto-reset time). When set above 0 seconds, the drive automatically attempts to reset resettable trips once the timer elapses.
  4. Serial / Fieldbus Command: Transition Bit 7 (Error Reset) of the command word from `0` to `1` through WEG SuperDrive software via RS-232/RS-485 serial communication, or through fieldbus networks (CANopen / DeviceNet).
  5. Power Cycle: Disconnect AC mains line power. Wait at least 10 minutes until the internal DC link capacitors discharge completely and the LED display turns off before reconnecting power.
⚠️ High-Voltage Electrical Safety Warning: Always disconnect line input power and wait at least 10 minutes for internal capacitors to discharge. Verify with a calibrated digital multimeter that DC bus voltage across terminals [+UD] and [BR] (or intermediate DC bus) has dropped strictly below 50VDC before inspecting motor terminals U, V, W or removing terminal strip covers on the WEG CFW-08 drive.