WEG CFW09 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW09 (CFW-09) variable speed drive series. Search or filter through the complete fault code directory below.
Power Range
1.1 – 1100 kW (1.5 – 1500 HP)
Supply Voltage
220–230V / 380–480V / 500–690V AC
Control Modes
V/f, VVW, Sensorless & Vector (Closed Loop)
Operator Interface
Detachable Smart Keypad & SuperDrive PC
Complete WEG CFW09 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type E00, E01, or Overcurrent).
| Fault / Alarm and Meaning | Cause and Remedy |
|---|---|
| E00 Output Overcurrent / Short-circuit | Cause:
Remedy: Check output motor cabling for phase-to-phase short-circuits. Check dynamic braking resistor connection leads for insulation wear or shorts. Reduce load inertia, or increase the acceleration ramp time. Verify control parameters and decrease parameters P169 to P172 if set too high. Reset options: Power-on, Manual reset (Key 0), Overcurrent Auto-reset, DIx, Serial, Fieldbus. |
| E01 Overvoltage (Ud) / DC Link Overvoltage | Cause: The DC-bus voltage of the inverter has exceeded the permissible limits (check Ud in parameter P004):
Remedy: Verify incoming mains supply voltage stability (P004). Increase deceleration ramp time or reduce load inertia. Use a dynamic braking resistor if necessary. Decrease parameters P151 or P153 if set too high. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E02 Undervoltage (Ud) / DC Link Undervoltage | Cause: The DC-bus voltage of the inverter has fallen below the permissible limits (check Ud in parameter P004):
Remedy: Check input mains voltages. Check terminal blocks and check for missing phases. Verify pre-charge contactor and auxiliary circuit fuses (refer to manual section 3.2.3). Ensure parameter P296 matches your actual rated supply voltage. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E03 Input Undervoltage / Phase Loss | Cause: Power supply voltage is too low, check supply line voltage:
Remedy: Check mains supply line for phase drops or drops in voltage. Verify general supply voltage stability. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E04 Inverter Overtemperature or Pre-charge Circuit Defective | Cause:
Remedy: Verify cooling fan is functioning and clean any dust from the heatsink. Improve cabinet airflow. Verify ambient working temperatures (ensure between -10 °C and 40 °C). Check supply lines and auxiliary circuit fuses (refer to manual section 3.2.3). Verify polarity on analog input channels AI1/AI2. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E05 Inverter / Motor Overload (I × t Function) | Cause:
Remedy: Verify motor nominal currents and check P156, P157, and P158 against nameplate data. Check mechanical load on shaft. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E06 External Fault | Cause:
Remedy: Verify external cabling loops to the assigned digital inputs. Ensure terminal block XC12 on the control board CC9 is fully seated. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E07 Encoder Fault | Cause:
Note: This fault is valid only if P202 = 4 (Vector with Encoder). Remedy: Check encoder connection sequence to XC9. Verify mechanical mounting of encoder (refer to manual section 8.2). Swap encoder if defective. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E08 CPU Error (watchdog) | Cause:
Remedy: Optimize cabinet grounding and shield terminations to mitigate noise. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E09 Program Memory Error (Checksum) | Cause:
Remedy: This indicates internal card memory failure. Please contact WEG technical support. Reset: Contact WEG. |
| E10 Error in the Copy Function | Cause:
Remedy: Verify firmware and software versions match between target inverter and HMI file before copying. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E11 Ground Fault | Cause:
Remedy: Verify insulation of motor cables and motor winding. If cable is extremely long, shorten lines or add an output reactor. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E12 Braking Resistor Overload | Cause:
Remedy: Increase deceleration ramp time. Adjust mechanical shaft load. Verify and correct parameter configurations for P154 and P155. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx. |
| E13 Incorrect encoder sense of rotation | Cause:
Note: This is valid for P202 = 4 (Encoder), with P408 = runs to Imr. This fault can only occur during Self-tuning. Remedy: Do not reset this fault and restart without first correcting the direction of either the encoder or the motor. Swap motor output phases (U, V, W) or invert encoder channels A and B. Correct physical mount orientation of the encoder. |
| E15 Motor Phase Loss | Cause:
Remedy: Check motor cables and winding loop continuity. Verify parameter P401 rating settings. Review vector control orientation parameters and check encoder connections. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E17 Overspeed Fault | Cause:
Remedy: Verify speed loop tuning and speed feedback channels. Check mechanical load variations. |
| E24 Programming Error | Cause:
Remedy: This fault is automatically reset when the incompatible parameters are correctly programmed. Resolve conflicting parameter values according to manual Table 4.2 definitions. |
| E31 Keypad (HMI) Connection Fault | Cause:
Remedy: This fault is automatically reset when HMI communication with the inverter is reestablished. Check keypad RJ45/serial cable connections. Protect the cable from electromagnetic noise. |
| E32 Motor Overtemperature | Cause:
Note: Overtemperature protection (4). Remedy: Check motor load status and duty cycles. Reduce starts/stops per minute. Verify thermistor cabling loop resistance is not < 100 Ω. Check configuration parameter P270. Verify motor shaft is free to rotate. Reset options: Power-on, Manual reset (Key 0), Auto-reset, DIx, Serial, Fieldbus. |
| E33 Speed without Control | Cause:
Note: Control parameter (8). Remedy: Check mechanical brakes and load stability. |
| E34 Long Period at Torque Limitation | Cause:
Note: Torque limit parameter (9). Remedy: Reduce motor load. Verify brake opening coil, connections, and limit switches. |
| E41 Self Diagnosis Fault | Cause:
Remedy: Contact WEG technical support for control card evaluation. Reset: Contact WEG. |
How to Clear & Reset WEG CFW09 Drive Faults
- Keypad Reset: Press the red O (Stop / Reset) key on the detachable smart HMI keypad. If operating under remote automation control (REM), toggle to local mode (LOC) via the LOC/REM key before executing a manual reset.
- Digital Input Reset (DI): If programmed in parameters P263 to P268 (DI1 to DI6 function) for “Fault Reset” (option 8 / Reset), activate the assigned digital input terminal momentarily to clear the trip.
- SuperDrive PC Software: Connect via the RS-232 / RS-485 serial communication interface (KSD-CFW09), open the WEG SuperDrive software, and click “Fault Reset” in the online diagnostic monitor.
- Fieldbus Network: Set the reset bit in the control word via serial communication protocols (Modbus RTU built-in, or optional Profibus DP / DeviceNet expansion cards).
- Power Cycle Reset: Disconnect AC line input power, wait for the DC link bus capacitors to fully discharge (wait until keypad display and status LEDs turn completely off, approx. 5 minutes), then reapply mains power.
⚠️ High-Voltage Electrical Safety Warning:
Always verify with a calibrated digital multimeter that intermediate DC bus voltage measures strictly below 50VDC across terminals [+DC / -DC] or [UDC+ / UDC-] before inspecting motor leads, opening terminal covers, or touching output terminals U, V, and W on the WEG CFW09 drive.