WEG CFW701 Drive Fault Codes & Diagnostic Guide
Complete fault code reference directory, trip alarm causes, and step-by-step troubleshooting procedures for the WEG CFW701 HVAC-R variable frequency drive series. Search or filter through the complete fault code directory below.
Power Range
1.1 – 132 kW (1.5 – 175 HP)
Supply Voltage
200–240V / 380–480V / 500–600V AC
Control Modes
Scalar V/F & VVW Vector (Vectrue®)
Operator Interface
HVAC Graphic HMI (Backlit Display)
Complete WEG CFW701 Drive Fault Code Directory
Use the search box in the table below to quickly find your code (e.g., type F006, F021, or Overcurrent).
| Fault / Alarm and Meaning | Cause and Remedy |
|---|---|
| F0006 Input Voltage Imbalance or Phase Loss The mains voltage imbalance is too high or phase loss at the supply line has occurred. | Cause:
Note: This fault may not occur if the load at the motor shaft is too low or nonexistent. Parameter P0357 sets the time for the trip, and P0357 = 0 disables this fault. Remedy: Verify input mains connections and check input fuses. Check the line voltages. Setting parameter P0357 to 0 disables this fault check. |
| F0021 DC Link Undervoltage A DC link undervoltage condition has occurred. | Cause: The input voltage is too low and the DC link voltage dropped below the minimum permitted value (monitor the parameter P0004):
Remedy: Monitor parameter P0004. Check physical input terminals. Ensure correct configuration of parameter P0296 to match incoming rated mains voltage. Check pre-charge circuit paths. |
| F0022 DC Link Overvoltage A DC link overvoltage condition has occurred. | Cause: Too high input voltage, resulting in a DC link voltage higher than the maximum permitted value:
Remedy: Check incoming supply voltage. Adjust deceleration ramp time or reduce load inertia. Check values in parameters P0151, P0153, or P0185. |
| A0046 High Load at the Motor It is the motor overload alarm. | Cause:
Note: This alarm can be disabled by setting parameter P0348 = 0 or 2. Remedy: Verify parameters P0156, P0157, and P0158. Check motor shaft for mechanical overload. Adjust parameter P0348 to 0 or 2 if desired to disable. |
| A0047 IGBT Overload Alarm It is the IGBT overload alarm. | Cause:
Note: This alarm can be disabled by setting parameter P0350 = 0 or 2. Remedy: Verify motor operating loads and current. Setting P0350 to 0 or 2 disables this alarm. |
| F0048 IGBT Overload Fault It is the IGBT overload fault. | Cause:
Remedy: Analyze load conditions to prevent high current output. Check drive/inverter capacity matching. |
| A0050 IGBT High Temperature The NTC temperature sensors located in the IGBTs detected a high temperature alarm. | Cause:
Note: This alarm can be disabled by setting parameter P0353 = 2 or 3. Remedy: Clean the heatsink fins. Verify fan operation. Check surrounding ambient temperature. Alarm can be bypassed by setting parameter P0353 to 2 or 3. |
| F0051 IGBT Overtemperature The NTC temperature sensors located in the IGBTs detected a high temperature fault. | Cause:
Remedy: Clean the heatsink fins. Inspect the cooling fan and replace if defective. Check ambient room temperature. |
| F0070 Overcurrent/Short-circuit An overcurrent or a short-circuit at the output, at the DC link, or at the braking resistor, has occurred. | Cause:
Remedy: Inspect motor terminals and cables for short circuits. Check braking resistor wiring. Verify physical state of the output IGBT stages. |
| F0071 Output Overcurrent An output overcurrent has occurred. | Cause:
Remedy: Adjust acceleration ramp to be longer, or reduce load inertia. Adjust parameters P0135, P0169, and P0170. |
| F0072 Motor Overload The motor overload protection has tripped. | Cause:
Note: This fault can be disabled by setting parameter P0348 = 0 or 3. Remedy: Verify motor rated currents and adjust parameters P0156, P0157, and P0158. Check mechanical load on shaft. Setting parameter P0348 to 0 or 3 disables this fault. |
| F0074 Ground Fault A ground fault occurred either in the cable between the inverter and the motor or in the motor itself. | Cause:
Note: This fault can be disabled by setting parameter P0343 = 0. Remedy: Verify insulation of motor and output cabling phases. If cable is extremely long, add output reactor or set P0343 to 0. |
| F0076 Motor Current Unbalance Fault of motor current unbalance. | Cause:
Note: This fault can be disabled by setting parameter P0342 = 0. Remedy: Verify all output cable connections between inverter output and motor terminal box. Check vector control tuning and orientation. Verify encoder cables and phasing. Setting P0342 to 0 disables this fault. |
| F0078 Motor Overtemperature Fault related to the PTC temperature sensor installed in the motor. | Cause:
Note: It can be disabled by setting parameter P0351 = 0 or 3. An analog input and an analog output must be set for the PTC function. Remedy: Assess motor mechanical status. Check start/stop cycles. Verify thermistor cabling and loop resistance (measure to verify > 100 Ω). Check parameter P0351 settings. |
| F0080 CPU Watchdog Microcontroller watchdog fault. | Cause:
Remedy: Optimize grounding and cable paths. Ensure control cables are separated from high-current power lines. |
| F0084 Auto-Diagnosis Fault Auto-Diagnosis Fault. | Cause:
Remedy: Inspect control board to power pack connections. Verify component and firmware compatibility. Contact technical support if an internal hardware defect is suspected. |
| A0090 External Alarm External alarm monitored through a digital input. | Cause:
Note: It is necessary to program a digital input for “No external alarm”. Remedy: Verify terminal wiring on DI1 through DI8. Secure screw contacts. |
| F0091 External Fault External fault monitored through a digital input. | Cause:
Note: It is necessary to program a digital input for “No external fault”. Remedy: Verify terminal wiring loops to the assigned digital inputs. Ensure signal switches are functioning. |
| A0098 Activate General Enable General Enable signal is missing during the self-tuning. | Cause:
Remedy: Check the digital input assigned to keep the drive enabled during the self-tuning routine. |
| F0099 Invalid Current Offset The current measurement circuit is presenting an abnormal value for null current. | Cause:
Remedy: This typically indicates hardware damage. Replace the power module or contact technical service. |
| A0110 High Motor Temperature Fault detected through PTC type temperature sensors installed in the motor. | Cause:
Note: It can be disabled by setting parameter P0351 = 0 or 2. An analog input and an analog output must be set for the PTC function. Remedy: Verify the mechanical motor load and operating conditions. Verify thermistor cabling and parameters. |
| A128 Serial Communication Timeout It indicates that the inverter stopped receiving valid telegrams during a certain period. | Cause:
Note: It can be disabled by setting parameter P0314 = 0.0 s. Remedy: Check serial connections, shield grounding, and wiring. Adjust master polling times, or disable timeout by modifying P0314. |
| F0150 Motor Overspeed Overspeed fault. | Cause:
Note: It trips when the actual speed exceeds the value of P0134 x (100 % + P0132) / 100% for more than 20 ms. Remedy: Adjust overspeed limit parameters P0161 and P0162. For lifting or hoist applications, verify brake coordination and torque limits. |
| F0151 FLASH Memory Module Fault FLASH Memory Module (MMF-01) fault. | Cause:
Remedy: Verify the physical slot connection of the FLASH memory card. Replace the memory module if card is damaged. |
| A0152 High Internal Air Temperature This alarm indicates that the internal air temperature is too high. | Cause:
Note: It can be disabled by setting parameter P0353 = 1 or 3. Remedy: Ensure enclosure or cabinet ventilation fan is operating correctly. Clear blockages from airflow grilles. Check parameter P0353. |
| F0153 Internal Air Overtemperature It indicates internal air overtemperature fault. | Cause:
Remedy: Shut down the inverter and check enclosure ventilation. Verify cooling fan function. |
| F0156 Undertemperature The temperature sensors located in the IGBTs or in the rectifier detected a low temperature, below -30 °C ( -22 °F), fault. | Cause:
Remedy: Check the installation environment. Provide heating element control inside the cabinet for operation in cold environments. |
| F0157 Parameter Table Data Loss There was a problem during the initialization, during the parameter table loading routine. Some recent parameter modifications may have been lost. | Cause:
Remedy: Verify current parameter modifications. Avoid switching off the control board too quickly during parameter editing. |
| F0158 Parameter Table Fault There was a problem during the initialization, during the parameter table loading routine. All the parameters were lost and the factory settings were loaded. | Cause:
Remedy: Check control unit card condition. Re-upload or re-verify firmware version. |
| A0159 Incompatible HMI Incompatible HMI. | Cause:
Remedy: Ensure the correct HMI model designed for the CFW701 series is installed. |
| F0160 Safety Stop Relays Safety stop relay fault. | Cause:
Remedy: Verify +24 V loop is applied correctly to the safety relays coil. Replace safety module card if internal relay is defective. |
| A0163 AI1 Broken Cable It indicates that the AI1 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range. | Cause:
Remedy: Inspect analogue input 1 loop cabling for breaks. Tighten screw terminal contacts. |
| F0078 Motor Overtemperature Fault related to the PTC temperature sensor installed in the motor. | Cause:
Note: It can be disabled by setting parameter P0351 = 0 or 3. An analog input and an analog output must be set for the PTC function. Remedy: Check the mechanical load on the motor shaft and resolve any blockages. Reduce high start/stop duty cycles if possible. Measure thermistor wire resistance to ensure it is > 100 Ω. Verify proper installation and wiring. |
| F0080 CPU Watchdog Microcontroller watchdog fault. | Cause:
Remedy: Optimize grounding and cable paths. Ensure control cables are separated from high-current power lines. |
| F0084 Auto-Diagnosis Fault Auto-Diagnosis Fault. | Cause:
Remedy: Verify internal control board and power pack connections. Update control unit firmware if needed. Contact technical support if a hardware defect is suspected. |
| A0090 External Alarm External alarm monitored through a digital input. | Cause:
Note: It is necessary to program a digital input for “No external alarm”. Remedy: Check digital input terminal loops and secure connections to prevent open circuit alarms. |
| F0091 External Fault External fault monitored through a digital input. | Cause:
Note: It is necessary to program a digital input for “No external fault”. Remedy: Check digital input terminal loops and ensure external switches are not triggering open circuits. |
| A0098 Activate General Enable General Enable signal is missing during the self-tuning. | Cause:
Remedy: Check and close the digital input assigned to keep the drive enabled during the self-tuning routine. |
| F0099 Invalid Current Offset The current measurement circuit is presenting an abnormal value for null current. | Cause:
Remedy: Inspect internal current sensors or control board circuitry. Hardware replacement may be required. |
| A0110 High Motor Temperature Fault detected through PTC type temperature sensors installed in the motor. | Cause:
Note: It can be disabled by setting parameter P0351 = 0 or 2. An analog input and an analog output must be set for the PTC function. Remedy: Check motor load and cooling. Verify that thermistors are installed and parameters are set. |
| A128 Serial Communication Timeout It indicates that the inverter stopped receiving valid telegrams during a certain period. | Cause:
Note: It can be disabled by setting parameter P0314 = 0.0 s. Remedy: Check serial connections, shield grounding, and wiring. Adjust master polling times, or disable timeout by modifying P0314. |
| F0150 Motor Overspeed Overspeed fault. | Cause:
Note: It trips when the actual speed exceeds the value of P0134 x (100% + P0132) / 100% for more than 20 ms. Remedy: Check and adjust parameters P0161 and P0162. For hoist applications, ensure braking logic is aligned. |
| F0151 FLASH Memory Module Fault FLASH Memory Module (MMF-01) fault. | Cause:
Remedy: Verify physical connection of the MMF-01 card. Replace the memory card if defective. |
| A0152 High Internal Air Temperature This alarm indicates that the internal air temperature is too high. | Cause:
Note: It can be disabled by setting parameter P0353 = 1 or 3. Remedy: Improve enclosure ventilation. Replace failed internal cooling fans. Set parameter P0353 to 1 or 3 if bypass is desired. |
| F0153 Internal Air Overtemperature It indicates internal air overtemperature fault. | Cause:
Remedy: Check and clear air grilles or replace defective fans. Reduce room/enclosure temperature. |
| F0156 Undertemperature The temperature sensors located in the IGBTs or in the rectifier detected a low temperature, below -30 °C ( -22 °F), fault. | Cause:
Remedy: Check the installation environment. Provide heating element control inside the cabinet for operation in cold environments. |
| F0157 Parameter Table Data Loss There was a problem during the initialization, during the parameter table loading routine. Some recent parameter modifications may have been lost. | Cause:
Remedy: Check parameter adjustments. Avoid powering down the control board immediately during configuration modifications. |
| F0158 Parameter Table Fault There was a problem during the initialization, during the parameter table loading routine. All the parameters were lost and the factory settings were loaded. | Cause:
Remedy: Verify control unit board condition. Re-upload or re-verify firmware version. |
| A0159 Incompatible HMI Incompatible HMI. | Cause:
Remedy: Install the designated HMI model for the CFW701 series. |
| F0160 Safety Stop Relays Safety stop relay fault. | Cause:
Remedy: Verify +24 V loop is applied correctly to the safety relays coil. Replace safety module card if internal relay is defective. |
| A0163 AI1 Broken Cable It indicates that the AI1 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range. | Cause:
Remedy: Inspect analogue input 1 loop cabling for breaks. Tighten screw terminal contacts. |
| A0164 AI2 Broken Cable It indicates that the AI2 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range. | Cause:
Remedy: Inspect analogue input 2 loop cabling for breaks. Tighten screw terminal contacts. |
| A0165 AI3 Broken Cable It indicates that the AI3 current (4-20 mA or 20-4 mA) reference is out of the 4 to 20 mA range. | Cause:
Remedy: Inspect analogue input 3 loop cabling for breaks. Tighten screw terminal contacts. |
| A0168 Speed Error too High Difference between speed reference and effective speed greater than the setting in P0360. | Cause:
Remedy: Ensure the motor is not overloaded or stalled. Check torque limits in P0360. |
| F0169 Speed Error too High Difference between speed reference and effective speed greater than the setting in P0360 for longer than P0361. | Cause:
Remedy: Ensure the motor is not locked or mechanically bound. Check limits set in P0360 and P0361. |
| A0170 Safety Stop The Safety Stop function is active. | Cause:
Remedy: Check the external safety circuits. Ensure STO commands are released for normal operation. |
| A0177 Fan Replacement Fan replacement alarm (P0045 > 50000 hours). | Cause:
Note: This function can be disabled by setting parameter P0354 = 0. Remedy: Perform preventive fan replacement maintenance. |
| F0179 Heatsink Fan Speed Fault This fault indicates a problem with the heatsink fan. | Cause:
Note: This function can be disabled by setting parameter P0354 = 0. Remedy: Check and clean the fan module. Replace if damaged. |
| F0182 Pulse Feedback Fault It indicates a fault in the output pulses feedback. | Cause:
Remedy: Inspect internal control unit feedback circuits. Hardware replacement may be required. |
| F0183 IGBT Overload + Temperature Overtemperature related to the IGBT overload protection. | Cause:
Remedy: Verify ambient cooling path functionality. Avoid running the drive continuously below 10 Hz during high overload conditions. |
| F0185 Pre-Charge Contactor Fault It indicates a fault at the pre-charge contactor. | Cause:
Note: For those models should be set P0355 = 0. Remedy: Verify input phase lines and trace fuses. Check pre-charge contactor and correct parameters in P0355. |
| A0210 Drive in Bypass mode Indicates that the drive is in Bypass mode. | Cause:
Remedy: Check digital input settings and external wiring assigned to Bypass mode activation. |
| A0211 Drive in Fire Mode Indicates that the drive is in Fire Mode. | Cause:
Remedy: Check the status of the digital input assigned to activate the Fire Mode. Confirm that external switch logic is correct and not stuck in the active state. |
| F0228 Serial Communication Timeout | Cause:
Remedy: Refer to the RS-232 / RS-485 Serial Communication Manual. Check cables, ground loops, and settings. |
| A0702 Disabled Inverter | Cause:
Remedy: Refer to the SoftPLC Manual. |
| A0704 / A0706 Two Enabled Movements / Reference not Programmed for SoftPLC | Cause:
Remedy: Verify SoftPLC program logic and configure reference parameters correctly. |
| F0711 Fault in the Execution of the SoftPLC Fault in the execution of the SoftPLC. | Cause:
Remedy: Verify program compatibility. Attempt a fresh upload of the user application. |
| A0750 Programming AIx for Main PID Controller Feedback It indicates to the user there is not analog input programmed for Main PID controller feedback. | Cause:
Remedy: Program the appropriate analog input parameter to option 5, 6, or 7. |
| A0752 Programming DIx for Main PID Controller Automatic/Manual Selection It indicates to the user there is not digital input programmed for Main PID controller Automatic/Manual selection. | Cause:
Remedy: Program the appropriate digital input parameter to option 20. |
| A0754 Programming Local Reference (P0221) for SoftPLC It indicates to the user that the origin of the speed reference in the Local situation is not programmed for SoftPLC. | Cause:
Remedy: Set parameter P0221 to 7 if utilizing the PID controller in local mode. |
| A0756 Programming Remote Reference (P0222) for SoftPLC It indicates to the user that the origin of the speed reference in the Remote situation is not programmed for SoftPLC. | Cause:
Remedy: Set parameter P0222 to 7 if utilizing the PID controller in remote mode. |
| A0758 Programming Indirect Engineering Unit 4 (P0516) for Hz or rpm It indicates to the user that the engineering unit parameters for motor speed is not programmed for Hz or rpm. | Cause:
Remedy: Configure parameter P0516 to option 13 (Hz) or 3 (rpm). |
| A0760 Low Level for Main PID Controller Feedback It indicates to the user that the Main PID controller feedback is low. | Cause:
Remedy: Check feedback loop lines. Verify parameters P1031 (threshold) and P1032 (delay). |
| F0761 Low Level for Main PID Controller Feedback It indicates to the user that the Main PID controller feedback is low. | Cause:
Remedy: Verify loop line pressure/flow. Check values set in parameters P1031 and P1032. |
| A0762 High Level for Main PID Controller Feedback It indicates to the user that the Main PID controller feedback is high. | Cause:
Remedy: Inspect process line for high limits. Verify values set in parameters P1033 and P1034. |
| F0763 High Level for Main PID Controller Feedback It indicates to the user that the Main PID controller feedback is high. | Cause:
Remedy: Inspect process line for high limits. Verify values set in parameters P1033 and P1034. |
| A0764 CFW701 in Sleep Mode It indicates to the user that the CFW701 frequency inverter is in Sleep mode. | Cause:
Remedy: Informational alarm status indicating sleep mode has engaged. To adjust this behavior, modify parameters P1036 (sleep speed) or P1037 (sleep delay time). |
| A0766 Dry Pump Detected It indicates to the user that the dry pump condition was detected for the pump driven by CFW701 frequency inverter. | Cause:
Remedy: Verify fluid flow to the pump. Verify configurations for parameters P1042, P1043, P1044, and P1045. |
| F0767 Dry Pump Detected It indicates to the user that the dry pump condition was detected for the pump driven by CFW701 frequency inverter. | Cause:
Remedy: Verify fluid flow to the pump. Verify configurations for parameters P1042, P1043, P1044, and P1045. |
| A0768 Broken Belt Detected It indicates to the user that the broken belt condition was detected for the motor driven by CFW701 frequency inverter. | Cause:
Remedy: Check the mechanical coupling belt/pulley state. Verify the parameter configurations for P1046, P1047, P1048, and P1049. |
| F0769 Broken Belt Detected It indicates to the user that the broken belt condition was detected for the motor driven by CFW701 frequency inverter. | Cause:
Remedy: Check the mechanical coupling belt/pulley state. Verify the parameter configurations for P1046, P1047, P1048, and P1049. |
| A0770 Filter Maintenance It indicates to the user that the need to change the filter system. | Cause:
Remedy: Perform preventive system filter replacement. Reset the elapsed timer if required. |
| F0771 Filter Maintenance It indicates to the user that the need to change the filter system. | Cause:
Remedy: Perform preventive system filter replacement. Reset the elapsed timer if required. |
| A0780 Programming AIx for External PID Controller 1 Feedback It indicates to the user there is not analog input programmed for External PID controller 1 feedback. | Cause:
Remedy: Set parameter P0231 or P0236 or P0241 to option 8 to configure process feedback. |
| A0782 Programming DIx for External PID Controller 1 Automatic/Manual Selection It indicates to the user there is not digital input programmed for External PID controller 1 Automatic/Manual selection. | Cause:
Remedy: Set parameter P0263, P0264, P0265, or P0266 to option 21. |
| A0784 Programming AOx for External PID Controller 1 Output It indicates to the user there is not analog output programmed for External PID controller 1 output. | Cause:
Remedy: Configure parameter P0251 or P0254 to option 16 to set the analog output target. |
| A0786 Low Level for External PID Controller 1 Feedback It indicates to the user that the External PID controller 1 feedback is low. | Cause:
Remedy: Check the process feedback sensor and loop line. Verify configurations in parameters P1075, P1076, and P1077. |
| F0787 Low Level for External PID Controller 1 Feedback | Cause: Parameter P1075 is programmed in 2 and the External PID controller 1 Feedback value is remaining below the value programmed in P1076 for the time programmed in P1077. Remedy: Check the physical process line and feedback loop sensors. Verify the parameter configurations for P1075, P1076, and P1077. |
| A0788 High Level for External PID Controller 1 Feedback | Cause: Parameter P1075 is programmed in 1 and the External PID controller 1 feedback value is remaining above the value programmed in P1078 for the time programmed in P1079. Remedy: Verify that the process pressure, level, or variables are within expected system parameters. Check the sensor output and parameter values for P1075, P1078, and P1079. |
| F0789 High Level for External PID Controller 1 Feedback | Cause: Parameter P1075 is programmed in 2 and the External PID controller 1 feedback value is remaining above the value programmed in P1078 for the time programmed in P1079. Remedy: Verify that the process pressure, level, or variables are within expected system parameters. Check the sensor output and parameter values for P1075, P1078, and P1079. |
| A0790 Programming AIx for External PID Controller 2 Feedback | Cause: It indicates to the user there is not analog input programmed for External PID controller 2 feedback. Parameter P0231 or P0236 or P0241 is not programmed in 9. Remedy: Configure the designated analog input by setting parameter P0231, P0236, or P0241 to option 9. |
| A0792 Programming DIx for External PID Controller 2 Automatic/Manual Selection | Cause: It indicates to the user there is not digital input programmed for External PID controller 2 Automatic/Manual selection. Parameter P0263 or P0264 or P0265 or P0266 or P0267 or P0268 or P0269 or P0270 is not programmed in 22. Remedy: Configure the digital input by setting parameter P0263, P0264, P0265, P0266, P0267, P0268, P0269, or P0270 to option 22. |
| A0794 Programming AOx for External PID Controller 2 Output | Cause: It indicates to the user there is not analog output programmed for External PID controller 2 output. Parameter P0251 or P0254 is not programmed in 17. Remedy: Configure the analog output by setting parameter P0251 or P0254 to option 17. |
| A0796 Low Level for External PID Controller 2 Feedback | Cause: Parameter P1095 is programmed in 1 and the External PID controller 2 feedback value is remaining below the value programmed in P1096 for the time programmed in P1097. Remedy: Check the physical process line and feedback loop sensors. Verify the parameter configurations for P1095, P1096, and P1097. |
| F0797 Low Level for External PID Controller 2 Feedback | Cause: Parameter P1095 is programmed in 2 and the External PID controller 2 feedback value is remaining below the value programmed in P1096 for the time programmed in P1097. Remedy: Check the physical process line and feedback loop sensors. Verify the parameter configurations for P1095, P1096, and P1097. |
| A0798 High Level for External PID Controller 2 Feedback | Cause: Parameter P1095 is programmed in 1 and the External PID controller 2 feedback value is remaining above the value programmed in P1098 for the time programmed in P1099. Remedy: Verify that the process pressure, level, or variables are within expected system parameters. Check the sensor output and parameter values for P1095, P1098, and P1099. |
| F0799 High Level for External PID Controller 2 Feedback | Cause: Parameter P1095 is programmed in 2 and the External PID controller 2 feedback value is remaining above the value programmed in P1098 for the time programmed in P1099. Remedy: Verify that the process pressure, level, or variables are within expected system parameters. Check the sensor output and parameter values for P1095, P1098, and P1099. |
| Capacitance Ground Fault Diagnostic Warning Note (1) | Cause: Very long motor cables, with more than 100 m (328.08 ft), present a high parasitic capacitance to the ground. The circulation of a leakage current through this capacitance may cause the activation of the ground fault circuit, and consequently an F0074 trip immediately after the inverter enabling. Remedy: Reduce the switching frequency set in parameter P0297. |
| Conn Lost HMI Communication Failure Warning | Cause: A bad contact in the HMI cable, or electrical noise in the installation, can cause a failure in the communication between the HMI and the control board. In such cases, the operation through the HMI becomes impossible. Remedy: Inspect and clean the HMI cable connections. Minimize electrical noise in the installation by rerouting cables or adding shielding. |
How to Clear & Reset WEG CFW701 Drive Faults
- Keypad Reset (O Key): Press the red O (STOP / RESET) key or the dedicated Reset softkey on the graphic HMI keypad. If running under Remote (REM) status, switch to Local (LOC) control if keypad reset is restricted.
- Digital Input Reset (DI): If an available digital input (DI1 to DI8) is programmed as No Fault / Reset via parameters P0263 to P0270 = 12, cycle the terminal contact (pulse from open to closed).
- Auto-Reset Configuration: Parameter P0340 (Auto-Reset Time) can be programmed with an automatic reset delay along with P0341 (Number of Reset Attempts) to clear transient trips automatically.
- HVAC Fieldbus / Serial Reset: Transition Bit 7 (Fault Reset) from `0` to `1` in the Control Word via embedded RS-485 interfaces (BACnet MS/TP, Metasys N2, Modbus-RTU) or optional network modules.
- Power Cycle: Disconnect AC line supply voltage. Wait at least 10 minutes for the DC link capacitors to fully discharge and the graphic display to turn off completely before restoring line power.
⚠️ High-Voltage Electrical Safety Warning:
Always disconnect incoming line power and wait at least 10 minutes for internal filter capacitors to discharge. Verify with a calibrated digital multimeter that intermediate DC bus voltage across terminals [+UD] and [-UD] (or [BR]) measures strictly below 50VDC before inspecting motor leads U/T1, V/T2, W/T3 or removing terminal covers on the WEG CFW701 drive.